What is the CENELEC standard for Information Technology - Cable Installation?
CENELEC EN 50174
What is the CENELEC standard for Information Technology - Generic Cabling Systems
CENELEC EN 50173
What is the CENELEC standard for Application of Equipotential Bonding and Earthing in Buildings with Information Technology Equipment
CENELEC EN 50130
What is the CENELEC standard for Information Technology - Cabling Installation - Testing of Installed Cabling
CENELEC EN 50346
What is the optimm temperature that a battery should be maintained
77 degrees F
The recommended Bend Radius for a cable during installation is typically greater than the recommended bend radius after the cable is installed. True or False?
True
The mazimum pulling force guideling for a 2-or 4- strand fiber cable is what?
50 lbs
The minimum bend radius for a 2- or 4-fiber optical cable is what under no-load conditions
1 inch
The minimum bend radius for a 2- or 4-fiber optical cable is what under pulling tension
2 inch
What are the Standard Test Methods for Fire Test of Through-Penetration Fire Stops?
UL 1479 and ASTM E814
What is the permitted substitute for a fiber optic cable rated OFNP
None
What does OFNP stand for
Optical Fiber Non-Conductive Plenum
The magnitude of disturbances in Telecommunications Facilities depend upon what three things
1) Influence characteristics of the disturbing system
2) Inductive Coupling characteristics of the disturbing systems
3) Interference suseptability of the telecommunications facility
The Interference characteristics of the disturbing system depends on what four things
1) The balance of the system
2) The fundemental and harmonic content
3) Current Magnitude (for magnetic coupling)
4) Voltage Magnitude (fpr electrostatic coupling)
The coupling characteristics (coupling impedence) is a function of what 5 things?
1) Frequency
2) Seperation distance
3) Lenght of exposure
4) Earth Resistance
5) Shielding effect between the Telecommunication Facilities
The three types of protection for electrical power stations are:
1) Isolating transformers
2) Neutralizing Transformers
3) Mutual Drainage Reactors
What are the three types of tunnel construction methods
1) Open-cut (ground exavation
2) Boring (or tunneling
3) Prefabrication (used for underwater)
The Majority of all FA systems are of the PLFA type.
True or False?
True
PLFA stands for ???
Power Limited Fire Alarm
Most PLFA circuits operate at less than or equal to how many volts
24 volts
The portion of the Ethernet physical layer responsible for the interfacing to the transmission medium is called the ____________sublayer.
Physical Media Dependent (PMD)
What are the seven layers of the OSI Model
apstndp
1) Physical
2) Data Link
3) Network
4) Transport
5) Session
6)Presentation
7) Application
What is an MCS?
Mobile Switching Center
What is a ECP?
Executive Cellular Processor sometimes referred to as a homel location register.
How many BTU's = 1 ton of airconditioning required
12,000
1 Watt = how many BTU's
3.413 BTU
What is the lozz of a 4-way splitter at 450MHz
6.8dB
What is the loss of a 2-way splitter at 450MHz
3.5dB
What is the typical impedence for private line circuits?
600 ohms
The maximum allowable attenuation for horizontal 62.5/125 or 50/125 micrometer multimode link is what?
2.0dB
802.11a operates at what maximum data rate
54 Mb/s
802.11b operates at what frequency
2.4 GHz
Power converter usually produce only common-mode (CM) noise. True or False
False
Power converters usually produce both common-mode (CM) and differential mode (DM) noise
True
The temperature in the ER should be maintained at what temperature?
64 and 75 degrees F
The relative humidity in the ER should be maintained at what level?
30 to 50%
What is the typical impedence preferred for the private line circuits?
600 ohms
Ethernet in the 1st Mile is also known as?
802.3ah
ITU G.655 non-zero shifted optical fiber represents the majority of the installed base of single mode optical fiber. True or False
False
ITU-T G.652 non-zero shifted optical fiber represents the majority of the installed base of single mode optical fiber. True or False
True
Which of the following coordinates the access, paging, and handoff function within a cellular system?
1) ESN
2)ESP (Executive Call Processing)
3)MCS (Mobile Switching Center
4) DCS
3) MCS
Which is more efficient
1) Syncronous Transmission
2) Asyncronous Transmission
1) Syncrynous Transmission - because no start stop bits are required (Digital baseband speeds as low as 2.4Kb/s)
Access floor in general office areas are designated at:
1) 2 inches
2) 5 inches
3) 4 inches
4) 6 inches
5) 8 inches
5) 8 inches
Power converter produce only differential-mode (DM) noise:
True or False?
False
Power converters produce both common mode (CM) and differential-mode noise:
True or False?
True
Power converters produce only common-mode (CM) noise:
True or False?
False
ACR stands for:
Attenuation to Crosstalk Ration
ACR is the calculated difference between attenuation and crosstalk measurement for twisted pair cabling:
True or False?
True
Which of the following are not inductive coupling characteristics?
1) Current Magnetude (magnetude coupling)
2) None of these
3) Earth Reistivity
4) Shield effect between the
telecommunication facility.
5) Voltage Coupling (Electostatic Coupling)
1) Magnetic Coupling
5) Electrostatic Coupling
In residential cabling systems the AP must be notified if the the total cable lenght from the DP to the farthest outlet exceeds:
1) 150 Meters
2) 200 Meteres
3) 100 Meters
4) 90 Meters
1) 150 Meters
Which of the following Data Center tiers will allow for any planned site infrastructure activity without disruptin the computer hardware in any way:
1) Tier 1
2) Tier 2
3) Tier 3
4) Tier 4
3) Tier 3
4) Tier 4
Which of the following makes it possible to segment an organizations network into multiple broadcast domains:
1) Router
2) Hub
3) Switch
4) All
1) Router
To reduce EMI in Tunnes, which of the following is the recommended overall telephone circuit balance for metropitan area circuits:
1) 30 dB or >
2) 40 dB or >
3) 60 dB or >
4) 50 dB or >
3) 60db or >
Which of the following fiber types is desirable because of their invrease physical flexibility:
1) Loose buffered
2) Tight buffered
3) 62.5/125
4) 50/125
2) Tight buffered
What is the most common distance between loading points for D Loading
1) 450 feet
2) 4500 feet
3) 6000 feet
4) 600 feet
2) 4500 feet
LVD means ?
Low Voltage Disconnect
FA Central Services has six elements to meet the certification level required by:
1) NFPA 72
2) JIS X5150
3) UL 1034
4) CENELEC EN 50174
1) NFPA 72
Which of the following cause a difference between real power (in watts) and the apparent power (in volt amperes) required by the load in an AC circuit:
1) Inductance
2) Capacitance
3) Resistance
4) All of the above
1) Inductance
2) Capacitance
NEC Artical covering CATV and Radio Distribution Systems
1) Article 510
2) TIA/EIA 569
3) Article 820
4) Article 770
3) Article 820
Standard "Commercial Building Telecommunication Cabling Standard General Requirement"
ANSI/EIA-568-B.1
Administration Standard for Commercial Telecommunications Infrastructure
ANSI/EIA-606-1
Residential Telecommunication Cabling Standard
ANSI/EIA-570-A
Commercial Building Standards for Telecommunications Pathways and Spaces
ANSI/EIA-569-B
Commercial Building Telecommunications Standard, Part 2 Balanced Twisted Pair Cabling Components
ANSI/EIA-568-B.2
Optical Fiber Cabling Compents Standard
ANSI/EIA-568.B.3
Commercial Building Cabling Standard Par 1 General Requirements Addendum 1 - minimum 4-Pair UTP
ANSI/EIA-568.B.1-1
A symmetrical noise voltage that appears equally in each action signa carrying conductor is the definition of what?
Differential-mode voltage
Fire Test of Through Penetration Firestops
UL 1479
Standard Test Methods for Fire test of Thru-Penetration Fire Stops
ASTM E814
Which Standard applies to equipment racks used in TE in the US?
ANSI/EIA-310-D
The combined cable lenghts for patch cords and equipment connects in the work area (WA) and the telecommunications room (TR) should not exceed what length?
10 meters (33 feet)
What cable length is allowed between the HC(FD) and the telecommunication outlet (TO)
90 meters (295 feet)
What is the typical impedence preferred for central office switching system line circuits
900 ohms
Data Center Infrastructure Standard
TIA-942
What is the AC frequency of the sine waves cycle s in one second in North America
60 Hz
Primary AC frequency in other countries is what?
50 Hz
What are the characteristics of inductive coupling
1) Current Magnitude (magnetic coupling)
2) Voltage Magnitude (Electrostatic coupling)
What are the video transmission protocols.
1) PAL (Phase Alternation Line)
2) NTSC (National Television System Communication)
3) Ethernet
4) RS-170 (Monochrome broadcas standard)
The "Standard test method of building construction materials" is?
ASTM E119
HC (FD) jumpers and patch cords should not exceed a length of ?
5 meters (16 feet) per link