Where are the potable water main isolation valves located in the power 2 block?

Northeast of b - 3703.



North of b - 3703 in pipe way (no back flow preventer).



North of the warehouse.



T-1250 safety shower (no back flow preventer).

What is the purpose of a backflow preventer?

They act as check valves preventing any contamination in the block from getting into the site header.

What does the potable water system supply?

It is used to for drinking, restrooms, kitchens, safety showers, eyewash stations, etc.

How will the control room know if a safety shower is activated?

There's a toggle switch positioned at the valves that send an alarm to the dcs when the valve gets opened.

What implications does a freeze precaution have on the system?

High flow will create low pressure.

Where are the safety showers located?

Building 3703 eyewash.



Building 3703 lab eyewash.



Building 3705 flammable room eyewash.



T-1250 safety shower.



CT-1000 safety shower.



Building 3709 eyewash.



Soap tank safety shower.



Gt-100 chemical area safety shower.



Gt-200 chemical area safety shower.



Gt-300 chemical area safety shower.



Gt-400 chemical area safety shower.



Building 3707 eyewash.



Building 3808 eyewash.

What provisions should be made if the potable water system is taken out of service?

Place full coolers in the kitchen areas.



Place dak-packs full of water in the restrooms.



All chemical feed and storage areas will be monogoggle required.



Post do not drink signs in consumption areas.



Portable eyewash stations should be kept in the labs, shops, and wherever maintenance is being performed.



Work permits must include special instructions / precautions.



Make announcement over PA.


What must happen prior to drinking potable water once it's returned to service?

Dead end sections must be flushed and EOB will advise when the water is safe to consume.

When and who performs potable water system flushes?

Weekly, the day operator.

What are the thermal detectors set points?

Electrical package - 160°



Mechanical package - 225°



Turbine enclosure - 325°