What is the maximum length of a fixture drain?

1200 mm or 4 feet

2.4.8.2

What is the minimum depth of trap seal required on acid waste system?

50 mm or 2 inch

2.2.3.1

What is the minimum length of fixture drain serving a 3" floor drain connected to the building drain?

450 mm or 18 inches

2.5.1.1 (4)

What is the maximum hydraulic load that may be drained to a relief vent serving a circuit vent?

6 fixture units

2.5.3.1 (4)

What is the minimum size of a vent serving an oil interceptor?

1 size smaller than the inlet pipe.

What is the minimum amount of storeys you need before a yoke vent is required?

12 storeys

2.5.4.3

What is the minimum height of an air break?

1" or 1 pipe diameter

2.3.3.11. (2)

What is the minimum height of an air gap?

1" or 2 pipe diameters

2.6.2.9

What is the maximum distance between flow-controlled roof drains?

30 meters

2.4.10.4. (2d)

How do you convert fixture units to litres when sizing a combined sewer?

If fixture units is 260 or less, use 2,360 litres. If fixture units is more than 260, use 9.1 litres per fixture unit.

2.4.10.5

How do you calculate the volume of water on a roof drain?

Area of the roof in square meters times the 15 minute rainfall for that area. Add 50% of the area of the largest vertical surface adjacent to the roof.

2.4.10. (1)

What is the maximum water temperature at a shower head?

49*C or 120*F

Clause 2.2.10.7

What size of anchor is used to secure a water closet carrier to the floor?

1/2"

What two accessories are required to be installed with a lavatory in a public washroom?

Soap and a means of drying your hands

What type of overflow is used on a commercial kitchen sink?

Standing overflow

What is the minimum depth of oakum required in a caulked lead drainage joint?

1 inch

2.3.2.1.(2)

What is the minimum wall thickness required when constructing a T-drill joint in copper tube?

Type K or L can be used, so type L is the minimum.

2.3.3.2.

What is the minimum height of an air break?

1 inch or 1 pipe diameter

2.3.3.11.(2)

What is the maximum spacing of vertical supports in a plumbing system?

7.5 meters

2.3.4.4.(2)

What size of hanger rod is required to support a 4" horizontal pipe?

3/8" or 8 mm

2.3.4.5.(5)

What is the minimum depth of backfill that must be carefully placed and tamped over an underground pipe?

12" or 300 mm

2.3.5.1.

What are the pressure test requirements for a DWV system?

At least 3 meters water column on all joints for a minimum 15 minutes. If freezing, can do a 5 psi air test.

2.3.6.4, 2.3.6.5.

What is the minimum test pressure for a potable water system?

Service pressure if using water to test, or 100 psi if using air.

2.3.7.2.(1)