Face velocity of a supply register should be?
|
500 to 700 fpm
|
|
Face velocity of a return grille should be limited to
|
400 fpm
|
|
If a packaged heat/cool unit is equipped with an economizer
|
provide "free cooling" on certain days of the year
|
|
When installing an economizer it is important to check
|
that the vanes do not bind during operation
|
|
you just finished installing a 60,000 btuh output gas furnace and now you need to determine the volume of air that is flowing out of this furnace. you measure the supply temperature to be 105 F and the return temperature to be 68 F. What is the CFM at the bonnet
|
1500 CFM
|
|
The sensible heat equation can be used to determine air flow in which of the following systems
|
fossil fuel heating
|
|
where will your temperature probes be located for a delta T?
|
2 and 4
|
|
a manufacturer recommends a temperature rise between 35F and 55F. You have a temperature rise of 60F. How should you resolve this?
|
increase the blower speed
|
|
what could cause a higher than recommended temperature rise over a furnace
|
a clogged air filter
|
|
once a gas piping system has been assembled it should be pressure tested with
|
compressed air
|
|
a piping system that is pressurized with natural gas should be leak tested with
|
an electronic leak detector and/or soap bubbles
|
|
electronic leak detectors are calibrated in
|
ppm
|
|
what type of soap solution should be used to check for gas leaks?
|
one specifically designed for that purpose
|
|
which of the following is a diaphragm type differential pressure gage
|
magnehelic
|
|
a differential pressure gage reads pressures that are
|
differential or relative to atmosphere
|
|
a high supply side static pressure is an indication of
|
a clogged evaporator coil
|
|
a high return side static pressure is an indication of
|
a dirty air filter
|
|
why do you cross break ductwork
|
to add strength and rigidity
|
|
a duct traverse yields
|
the average CFM based on the average velocity multiplied by the square feet of duct
|
|
a direct drive blower wheel with damaged or missing vanes can cause
|
loss of air flow, motor damage and noise
|
|
during a PM call on a gas furnace you find loose and corroded wires. What, if anything, should be done?
|
retighten all loose wires and replacethe corroded portions of the wires
|
|
when preparing to perform an air balancing procedure
|
all volume dampers should be open, the blower should be adjusted to the desired speed, and the air filter should be cleaned or replaced
|
|
which of the following should be included in an air balancing report
|
supply, return, and total static pressure
|
|
in a trunk and branch duct system, trunk velocity should be kept between
|
700 to 900 fpm
|
|
horizontal runs of flexible duct should be supported every
|
5 feet
|
|
minimum strap width for hanging flexible duct is
|
1 1/2"
|
|
maximum sag for horizontal runs of flexible duct is
|
1/2" per foot
|
|
ductwork installed in unconditioned spaces should be
|
insulated
|
|
ducts installed in damp crawl spaces should be
|
wrapped with insulationand wrapped with a vapor barrier
|
|
human comfort can be defined in terms of
|
dry bulb temperature, relative humidity, and air velocity
|
|
The proper manifold pressure for natural gas is
|
3.2" to 3.8" of water column
|
|
the proper manifold pressure for LP gas is
|
11" to 13" of water column
|
|
inlet pressure to a gas valve should never exceed
|
14" of water column
|
|
in a combination gas valve
|
the pilot valve is in series with the main valve
|
|
a two stage gas valve has?
|
two pressure regulators and two main valves
|
|
manometers used to measure gas pressure are calibrated in
|
inches of water column
|
|
when reading a u-tube manometer
|
the columns are added
|
|
one psig is equal to
|
27.72" of water column and 2.3' hd.
|
|
the older mechanical thermostats and the newer electronic thermostats
|
are made to be compatible
|
|
which of the following thermostat types can be programmed for a different time schedule each day of the week
|
7 day programmable
|
|
to choose the proper air cleaner for a given application you must know?
|
the volume of return air
|
|
which of the following would be used to delay the off time for a blower
|
delay on break relay
|
|
which of the following is a category I furnace?
|
83% AFUE
|
|
venting a two pipe condensing furnace through the roof requires a maximum separation of the two pipes of
|
18"
|
|
when horizontally venting a condensing gas furnace be sure to
|
maintain a 12" separation between the inlet and the outlet of the two pipoes
|
|
when venting a category IV furnace what is the minimum separation from the vent pipe discharge to a forced air inlet into the building
|
3 feet
|
|
relative to combustion air a confined space is defined as
|
an area with less than 50 ft^3 of volume for each 1000 btuh of input for all appliances in that area
|
|
what is the required volume of air to sustain combustion?
|
50 ft^3 per 1000 btuh input
|
|
combustion air can be supplied to a confined space by
|
one opening within 12" of the floor and one opening within 12" of the ceiling
|
|
in venting tables for category I furnaces the "Vent Height" can be defined as
|
the distance from the outlet of the draft diverter to the chimney cap
|
|
the primary heat exchanger is typically made of
|
aluminized steel
|
|
the secondary heat exchanger is typically made of
|
stainless steel
|
|
a counterflow furnace installed in a closet must be mounted on
|
a combustible floor base
|
|
what else is important with regard to a closet installation of a two pipe 90% furnace in a residence
|
Noise transmission
|
|
an attic installation of a horizontal gas furnace requires
|
the use of a zero clearance furnace or a non-combustible mounting base
|
|
on a call for heat with an induced draft furnace, which of the following is the next event in the sequence of operation
|
draft inducer is energized
|
|
on a no heat call you find the following: R to W is made, The inducer is running, no main burner. What is most likely the cause of these symptoms?
|
A pressure switch stuck closed
|
|
on a call for heat the integrated circuit board will check for which of the following before energizing the draft inducer?
|
An open pressure switch
|
|
what device proves that the inducer motor is running and that the venting system is not obstructed
|
pressure switch
|
|
on a call for heat, after the pressure switch closes the next event is
|
HSI is energized
|
|
on a call for heat, after the HSI is energized the next event is
|
main burner circuit is energized
|
|
on a call for heat, after the main burner is energized the next event is
|
flame is proved
|
|
on a call for heat, after the flame is proven the next event is
|
blower motor is energized
|
|
the products of complete combustion include
|
co2, nitrogen, water vapor, and heat
|
|
primary combustion air
|
is mixed with the gas in the venturi before ignition
|
|
secondary combustion air
|
is supplied to the burner after ignition to sustain combustion
|
|
too much primary air can cause
|
the flame to lift off the burner
|
|
which of the following produces a hard, noisy blue flame
|
in-shot burner
|
|
ribbon burners must be properly aligned
|
to insure proper flame carry-over
|
|
modern residential gas burners are made from
|
sheet metal
|
|
which ignition system is de-energized once the main burner flame is established
|
interrupted
|
|
the pilot flame must envelope how much of the thermocouple
|
3/8" to 1/2"
|
|
a thermopile generates
|
750 DC mV
|
|
the ACCA manual used to perform residential load calculations is
|
Manual J
|
|
AFUE can be calculated by
|
useful output/input
|
|
a large difference between the wet bulb and the dry bulb temperatures is an indication of
|
low relative humidity
|
|
which of the following is used to measure RH%
|
sling psychrometer
|