what is the mag sprink pub?
S9522-AA-HBK-010
what is the HSD FUSIBLE LINK temperature?
161 +/- 1
what is the other name for F ALARM?
ICJ 105
what is the transmission tubing lines made of?
ROCKHIDE
what is the minimum loop between vented check valves and prpv?
4"
what is the purpose of the loop between vented check valves and prpv?
shock mounting
can transmission line be sectionally replaced if punctured?

yes or no and why?
no because it must be SEAMLESS
what is the max amount of copper tubing that can be exposed?
1"
how much of the copper tubing must be covered by rock?
1/8"
is it ok to paint the rockhide covering?
no becuse it adds extra insulation that can compromise the heat sensing ability plus it's flammable
what type of fitting goes on the transmission tubing ends?
37° flare fitting
what's the maximum hsd's per prpv?
12
what's the max OSI per PRP?
not to exceed 24 OSI
what's an R4Q?
it's the quarterly pms flush
what OSI do you pump the mag sprink to for a flush?
16-20 OSI then allow to settle
what's the minimum LOOP for flex hoses?
10" (wire mesh tubing)
what's an 81M
spring loaded lift check valve
what's the purpose of a spring loaded lift check valve?
to prevent backflow
what's HORCV stand for?
hydraulically operated remote control valve

What's the purpose of HORCV

allows system to be secured from a station other than the one that actuated it

what's CM15
most common type of 3way manual control valve
what happens to drain line during open loop?
steady flow through drain line one
what happens to drain lines during a closed loop?
steady flow from drain line two and a gush of water from #3 which turns into a diminished flow
what is an orifice plate made of?
MONEL (70% copper and 30% nickel)
what size hole is in an orifice plate?
.098" diamater hole OR #40 drill bit
how do you order an orifice plate?
ask the machine shop.. they make them. hence the reason we say #40 drill bit
how do you clean copper tubing of the mag sprink?
with a brass brush and water only (not hot sauce!!)
what type of system is the mag sprink?
dry type
what's another name for MSV?
CLA-VALVE
what's the operating PSI of the MSV?
40 PSI
whats the operating PSI of a navy standard msv?
55 PSI
where should the FD alarm be located?
1.5 to 2 inches from deck

At what temperature does the F alarm light off at?

105° +/- 1

which do you shut off first, local or remote??
the one that's in OPEN goes to NEUTRAL FIRST
what's the purpose of PORT BRAVO?
check for leaking of diaphram
what's purpose of PORT CHARLIE?
troubleshoot air pressure trapped in POWERTROL
another name for PORT CHARLIE
CHATTERING VALVE

what does it mean if there's a leak at port DELTA?

o-ring retainer (around stem) is fucked

what's purpose of PORT ALPHA?
inlet of water

What max area do HSD's protect?

120 sqft

how many hsd's are required per space?
2 min
hsd's must be installed within how many feet of a BOUNDARY BULKHEAD?
8
hsd's shall not be loacted within how many feet of ventilation?
5
can you put hsd's above or below cooling coils?
NO
how far from bulkheads and i beams minimum distance for placement of HSD'S
at least 1 foot away
max length of transmission tubing?
50 ft