When taking over a shift, preliminary safety checks allow the boiler operator to identify any possible problems.
True
A routine set of duties helps the operator to complete all assigned tasks.
True
In general, boilers should be blown down every 24 hr.
True
The main steam stop valve should be closed during normal plant start-up.
True
The boiler vent must be closed during warm-up to prevent pressure from escaping.
False
A bottom blowdown can be used to control chemical concentrations in the boiler.
True
The furnace brickwork should be cooled rapidly for energy efficiency.
False
There should be pressure in the boiler when dumping.
False
The boiler should be blown down when it is on a heavy load.
False
The operator's hand must always be kept on the blowdown valve during blowdown.
True
The blowdown valve should be kept open long enough for the water level in the gauge glass to drop out of sight.
False
The quick-opening valve is opened first and closed last during blowdown.
True
The low water fuel cutoff is checked for proper operation with the burner firing.
True
Try cocks can be used as a boiler water level indicator.
True
Steam discharged from the top try cock indicates a low water level.
False
An evaporation test is performed by blowing down the low water fuel cutoff.
False
Water added to a boiler with a low water level condition could cause a boiler explosion.
True
Furnace explosions are caused by steam in the fuel oil.
False
Any abnormal odor of gas should alert the boiler operator to a possible leak.
True
The boiler must be filled with water heated to 50°F before it is started for the first time.
False
Bottom blowdown is performed by opening the gauge glass blowdown valve.
False
Leaking fuel oil in the furnace could lead to a furnace explosion.
True
The boiler should be inspected to determine the cause of a low water level condition.
True
The furnace should not be purged after a flame failure.
False
A boiler must be taken off-line before it can be inspected.
True
Main steam stop valves must be tagged out during a boiler inspection.
True
After a boiler is dumped, it should dry completely before cleaning.
False
A hydrostatic test is a steam test used to check for boiler leaks.
False
A malfunctioning steam trap can result in a steambound feedwater pump.
True
Tools and equipment must be provided for the boiler inspector during boiler inspection.
True
During a hydrostatic test, the boiler is half filled with water.
False
Dry lay-up is recommended for boilers that will be out of service for an extended period.
True
Moisture left on metal surfaces during dry lay-up could cause scale buildup.
False
More pounds of silica gel than quicklime are required when laying up a boiler dry.
True
All valves are opened during dry lay-up.
False
A scratch on the inside of a gauge glass can cause it to break.
True
A clean gauge glass is necessary to accurately determine boiler water level.
True
A boiler inspection is commonly performed by the plant manager.
False
An evaporation test lowers the boiler water level rapidly.
False
Two people should be present during an evaporation test.
True
All plants maintain boiler room logs for an 8-hour period.
False
A boiler room log can be used to determine the cause of a boiler shutdown.
True
Boiler lay-up is required when the boiler is out of service between shifts.
False
When warming up the boiler, the low water fuel cutoff should be blown down before the steam pressure gauge records pressure.
False
When shutting down the boiler, the main steam valve should be closed immediately after the furnace is shut down.
False
The first thing a boiler operator should do when taking over a shift is ___.
check the boiler water level
When the low water fuel cutoff is blown down, ___.
the burner should shut off
The boiler pressure should always be ___ the header pressure when cutting a boiler in on the line.
slightly below
The boiler should be blown down when it is ___.
on a light load
ASME code states that on boilers having two bottom blowdown valves, the ___ valve should be closest to the boiler.
quick-opening
After blowing down the water column and gauge glass, the water should ___ the gauge glass.
quickly enter
If water cannot be seen in the gauge glass, ___.
the burner should be secured
A furnace explosion can be caused by ___.
a buildup of combustible gases or vapors, leaking gas or fuel oil, & improper furnace purge
The ___ blowdown valve is used to dump the boiler.
bottom
The best method for checking for leaks in gas lines is ___.
applying soapy water
A(n) ___ test is used to check for leaks in the boiler.
hydrostatic
All traces of coal, soot, and ash must be removed to prevent ___ from forming when mixed with water.
sulfuric acid
A steambound pump is caused by ___.
excessive water temperature
A(n) ___ test is used to test the low water fuel cutoff.
evaporation
A ___ is used to record information regarding operation of the boiler during a given period of time.
boiler room log
The boiler must be ___ when the low water fuel cutoff is blown down.
firing
The flame scanner is removed with the burner firing, the ___.
burner should shut off
To prevent damage to the furnace brickwork, the furnace ___.
should be cooled slowly
Boiler ___ is a condition when a boiler is operating at or above its maximum allowable working pressure.
overpressure
Before dumping the boiler, the boiler heating surface should be ___.
cool enough to touch
The water column whistle valve is ___ during the hydrostatic test.
removed
During the hydrostatic test, pressure on the boiler is brought up to ___ times the MAWP.
Water used to fill the boiler during the hydrostatic test should be a minimum of ___°F.
70
___ is placed on the water side of the boiler when placing the boiler in dry lay-up.
Quicklime
Gauge glass nuts are tightened by hand and then turned ___ with a wrench.
1/4 of a turn
A ___ test is the most accurate method of testing the low water fuel cutoff.
evaporation
When testing a low water fuel cutoff, the burner should shut off when ___.
water is still visible in the gauge glass
The internal mechanism of a low water fuel cutoff should be periodically removed from the bowl to check and ___ the float ball.
clean
To correct a high water condition, a ___ is performed.
bottom blowdown
New ___ should be used when replacing a broken gauge glass.
packing nuts
A boiler is given a bottom blowdown to ___.
discharge sludge
A leak on gas lines and equipment must be repaired ___.
by authorized personnel
For maximum safety in operation of a low pressure boiler, the low water fuel cutoff should be tested ___.
daily
Boiler data that is commonly recorded on a boiler room log includes ___.
boilers on line, steam pressure, & condensate return temperature
All running auxiliaries (fuel oil pumps, fan, water pump, and burner) should be checked for proper ___.
temperature, pressure, & lubrication
The proper testing of boiler accessories is determined by procedures suggested by ___.
ASME Code
After testing the flame scanner, ___.
reset the programmer
During the evaporation test, the ___ is secured.
automatic city water makeup feeder
During a boiler inspection, the main steam stop valve is ___.
closed and tagged out
The ___ must be covered with water before water can be added safely.
heating surface