Copper tubing can only be joined by

Flaring


Brazed


Compression

What type copper tube can be used underground max

Type K


Type L & G coated with PVC

Hoses must have a minimum pressure rating of

350psi

Max length of hose (permanent) is

10ft

Min length of hose on a construction heater is _____ and a max length of______

15ft


75ft

Max length of hose on portable appliance is

30ft

Eg. bbq

Hoses cannot be passed between rooms


True or False

True

Hanger space for 1/2 is

6ft

Hanger space for 3/4 to 1in is

8ft

1-1/4 to 2-1/2 is

10ft

Joints over 2in must be

Welded

Max length of vented appliance flex connector is

2ft

Garage heater

Max length of connector unvented appliance is

6ft

Dryer

Branch outlets must protrude thru walls and ceiling by at least

1in

Branch outlet must protrude from floor at least

2in

Minimum depth of a dirt pocket

3in or the diameter of pipe it serves whichever is greater

Can defective piping or tubing be used

No

Street fittings can be used


True or False

False

A union or swing joint maybe installed in a concealed space


True or False

False

Minimum depth of a buried gas line is

15in

How far must a commercial gas line be buried under a driveway or parking lot

24in

Gas lines covered with more than 25ft of concrete or pavement requires a

Vent/inspection point

Commercial gas lines need to be identified by

Painted yellow


Marked every 20ft

Copper tubing must be marked every

6ft

Gas cocks must be installed

On final drop or riser as close as possible to the appliance

on a residential gas line the gas cock may be located up to a max _____ft but it must be accessible

50ft

Gas SO valves must be located where between two buildings

At both buildings

The minimum size of threaded pipe is

1/2in

The minimum pressure test is

15psi for 15min

The minimum size face on a gauge is

3in

For welded pipe the minimum test is

50psi or 1.5 times max operating pressure for 180min

After pressure testing the gas line must be purged. When purging a gas line larger than 4in you must use

Carbon dioxide or nitrogen

Minimum size fresh air for residential is

4in dia

The minimum size of a vent or vent connector is

3in

When using ROT the size of vent on a single appliance is

The same size as the draft hood

When using a ROT for manifold vent the size of the vent is

The combined area of all vents


A2+B2=sq root C2

When sizing a 2psi system size from the meter to where first

System regulator

When sizing 2psi system what do you size secondly

From to the meter to the furthest appliance regulator

On a 2psi manifold system, size to the system regulator first, then manifold then

Furthest appliance

What is the maximum pressure permitted for residential

2psi

In a ventilated space you may use a system regulator equipped with a

Ball check leak limiting device

The maximum allowable gas vented by a system regulator to a vented space without internal relief is

1cu ft for propane


2.5 cu ft for nat gas

Regulators should always be in the vertical plane with the vent

Pointing down

For inlet pressures up to 5psi, the discharge set point on the line relief must be no less than

2 times and no more than 3 times the outlet pressure of the regulator

Vent terminations must be at least how far from a dryer vent

3ft

Vent terminations must be how far from a mechanical inlet

10ft

What is the ROT when venting one appliance through a chimney

One size larger than the appliance outlet

What is the maximum length of an air supply duct without increasing the size

20ft

The maximum pressure drop for a low pressure gas line is

1in wc

The maximum pressure drop for high pressure gas line is

50% of initial pressure

An outdoor air supply is not required for a single HWT with an input of up to _____ where there are no other appliances requiring air supply

50mbh

The ROT for sizing common vent connector is

A2+B2=C2


Size = sq root C2

ROT for sizing two drafthood appliances into a common vent

100% of largest btu plus 50% of other

The total vent height must be at least

10ft

To size venting only use what rating

Input

What venting table is the most economical

C4

If there are a combination of drafthood and fan assist appliances, which should be sized first

Fan assist

If a fan assist vent has more than one elbow, derate the “max” from the table by ______% to determine size

15%

If a drafthood appliance has more than one elbow, derate the “max” from the table by ____% to determine size

10%

If a common vent connector has more than two elbows, derate the CVC by ____% for each additional elbow

10%

If the CVC has an offset, derate the “max” from the table by ____% to determine size

20%

If corrugated chimney liner is used, derate the “max” from table by ____%

20%

The maximum length of a manifold CVC is

1.5 times the diam of the CVC

What appliance cannot be vented individually into a chimney

Fan assist

When venting a fan assist appliance into a chimney you must also have

Drafthood appliance venting into chimney

The smallest allowable size of a chimney is equal to

4in diam pipe

The maximum capacity of a chimney is not more than ____% of the input of the appliance

125%

A single appliance cannot be connected to a chimney without

A lateral horizontal offset

What is the minimum gsg to be used on an incinerator

20gsg

What is the minimum gsg for single wall venting under 6in

28gsg

The minimum dimension for a vent is ____in but in no case shall the area of the vent be less than the area of a ____in inside diam

2in


3in

BH vent must terminate ____in above a roof or ____in above any obstruction within _____in

18in


18in


18in

ROT for chimney size. Always size the chimney how many sizes larger than the drafthood or flue collar

1 size

A chimney must terminate at least ____ft above a roof or ____ft above any portion within _____ft

3ft


2ft


10ft

What tables are to be used for sizing air supply for a type A

8.1 or 8.2

When an appliance is located in an enclosure (type B) a permanent opening of not less than ___in per _____btu shall be installed not more than ____in or less than ____in above the floor

1in per 1000btu


18in


6in

When one or more appliances are in an enclosure (type b), an additional opening shall be located as near the ______ as practicable. But in no case _____ than the _____drafthood

Ceiling


Lower


Lowest

An air duct shall terminate within ____ft above and within ____ft horizontally from the burner

1ft


2ft

A drafthood or flue collar cannot be reduced except from

5in to 4in

Appliances over 400mbh shall be ventilated at the highest point practical but shall not terminate within ____in of a combustion inlet and shall not be smaller than____in

12in


10in

Appliances over 400mbh shall have a permanent opening not less than_____in per _____btu upto and including 1000btu

1in/7000btu

An appliance over 1000mbh shall have a permanent opening not less than _____in per ____btu for the first 1000mbh plus 1in for every ______btu for the remaining btu

1in per 7000mbh


1in per 14000mbh

Power burners should have a permanent opening not less than _____in per ______btu

1in/30000btu

A manual damper cannot be used on _______ appliances

Residential

What appliance may be installed in a bathroom

Direct vent

What is the minimum distance from a building opening of a vent terminal

12in

What is the minimum distance from a mechanical air intake of a direct vent terminal

10ft

The minimum distance from a direct vent terminal to ground level is

12in

The minimum distance between a direct vent terminal and a public sidewalk is

7ft

A vent must have two free to air sides and the deck must be at least _____in above the vent

12in

If a power vent is installed to a Cat 1 appliance side wall vented, they must be

Interlocked

What is the minimum required fixed opening when a automatic damper is installed on appliance with a standing pilot

20%

A “tight” building is what type

Type A

A “loose” building is what type

Type B

Type A building


When two types of appliance are in the same enclosed space size the _______ first using table 8.1 and then the combined btu on table 8.2

Drafthood

The maximum temperature of vent gasses allowed into a B vent is

470F

What height above a roof must a vent terminate

2ft

What is the minimum height above grade for a vent to terminate

12in

What is the minimum size vent for a Cat 1 appliance

3in

What is the minimum clearance to combustibles for a single wall vent connector

6in

What is the minimum effective vent height for a Cat 1 appliance

5ft

Can ROT be applied to two different types of appliances using one B vent connector

No. Can not combine drafthood and fan assist appliances into a dbl wall vent connector

What is the minimum size of a ventilation air opening when input exceeds 400mbh

10% or 10in2