  • Front
  • Back

What is the difference between an IP and DSi system

DSi system has no pilot

What is the average distance for a spark gap for an IP system

1/8 in

What is the average distance for spark gap for a DSi system

1/8 in

What is the advantage of a combined ignitor sensor over separate ones

There is no distinct advantage

Can a continuous trial ignition module be used on propane

No

What type of current is returns to the module as flame current

Microamps DC

What nominal voltage should be present at the MV terminals when the unit is firing

24 volts ac

When replacing ignition modules what is the most important Factor

Parameters such as lockout and trials for ignition must match

Why is the proper grounding of an ignition module so important

This path proves the flame

When taking the flame current on a working ignition system the module Sparks until lock out of curse you have checked at the meter setup and connected to the Circuit properly what could cause a system to suddenly stopped working

The fuse in a meter has burned out

Why is there a delay between powering the module and igniter warm up period

To allow for a brief pre-purge cycle

What voltage is supplied to the module for the hot surface ignitor

Line voltage AC

What voltage is supplied to the module for the gas valve

24-volt AC

After the igniter is powered why does it take so long for the main burner gas to come on

To allow the igniter to reach operating temperatures

What type of current is returned to the module

Microamps DC

What happens if the 24 volt power supply leads are reversed on the universal module

The module lockout and flash a code

A hot surface ignition system energizes the igniter and turns on the main burner gas. The main burner lights but goes out after a brief time. What is wrong with this module?

The flame is not being proved