A typical setting for the high pressure cut-out control on a recovery unit used for evacuating the refrigerant from a low pressure chiller is:

10 PSIG

A charged low pressure refrigeration system can be efficiently leak checked by:

Raising system pressure by heating with circulated hot water or heating blankets.

The existence of air in a low pressure system, causes _______

High head pressure

Which safety precaution should be adhered to for low pressure systems?

Do not siphon refrigerant by mouth, avoid spilling liquid refrigerant on the skin, use gloves and safety goggles when working with liquid refrigerant ( all of the above)

Refrigerant-11 at 14.7 PSIA will boil at about:

74.5°F

When there is excessive moisture collecting in the purge unit of a low pressure refrigeration system, this indicates that the _________.

Condenser or chiller barrel tubes are leaking.

ASHRAE standard 15-1994 requires equipment room refrigerant sensors for what safety group classification?

All refrigerant safety groups ( A1 B2 A2)

When recharging a refrigeration system with R-11, what vapor pressure is necessary in the shells before charging with liquid?

16.9" Hg vacuum

After reaching the required recovery vacuum on a chiller, you should:

Wait for at least a few minutes to see if the system pressure rises, indicating that there is still refrigerant in liquid form or in the oil.

A hydrostatic tube test kit is used to:

Determine if a tube leaks

When charging a chiller, refrigerant vapor is introduced into the system before charging with liquid. This is because :

Liquid charged into a deep vacuum will cause the refrigerant to boil and may lower temperatures enough to freeze the water in the tubes.

When evacuating a system, the use of too large a vacuum pump can cause:

Trapped water to freeze.

On a low-pressure chiller with an open type compressor, the ________ is very susceptible to leaks.

Shaft seal

What steps may be taken to prevent air accumulation into an idle low pressure refrigeration system?

System pressure should be maintained slightly above atmospheric

Commercial and industrial process Refrigeration systems must be repaired when the leak rate exceeds ______ percent of the charge per year.

35

When recovering vapor from a low pressure refrigeration system the:

System water pumps, the recovery compressor, and the recovery condenser water should all be on.

Where does refrigerant go after it leaves the purge unit of a low pressure centrifugal system?

Evaporator

The purge unit takes it suction from the :

Top of the condenser

Which of the following repairs would ALWAYS be considered "major" under EPA's regulations?

Replacement of an evaporator coil

Charging refrigerant liquid into a refrigeration system when it is under 29 inchesHg vacuum can cause the:

System water to freeze.

According to the EPA, there is approximately ________ refrigerant vapor left in an average 350 ton R-11 chiller at 0PSIG pressure once all the R-11 liquid has been removed?

100 LBS

An oil sample should be taken when _______

There has been a compressor burnout

Both CFC-11 and HCFC-123 chillers require purge units because :

The system operates below atmospheric pressure

Refrigerant recovery typically starts with _______ it is faster.

Liquid recovery

Under EPA's regulations __________ is used to pressurize a low-pressure chiller for the purpose of opening the system for a non-major repair?

Warming the refrigerant

The primary water source for a recovery unit condensing coil is ________

Local municipal water supply.

Which statement is NOT true of the recycling and recovery equipment manufactured after November 15, 1993?

It must be able to handle more than one refrigerant

A system does not have to be evacuated all the way to the required level when:

Leaks in the appliance make evacuation to the prescribed level unattainable

Which action listed below is the proper method to reduce refrigerant loss from a purge unit on a CFC-11 chiller?

Leak test and repair the chiller

Identify the pressure corresponding to 32F for R-123:

20" Hg vacuum

What precaution should be taken prior to recovering refrigerant from a chiller suspected of having tube leaks

Drain the water sides of the evaporator and condenser

Pressure relief valves must never be:

Installed in series

If you are going to be removing oil from a low-pressure system, you should heat the oil because :

Less refrigerant will be contained in the oil at the higher temperature

After recovering the liquid refrigerant you must:

Recover the vapor refrigerant

EPA regulations require that any appliances containing more than 50 pounds of refrigerant(except for commercial and industrial process refrigeration) must be repaired when the leak rate exceeds ______ of the charge per year.

15%

If you are using a recovery machine manufactured BEFORE November 15, 1993, you must evacuate any low-pressure appliance to _______ before making a major repair.

25" Hg vacuum

On low-pressure chillers, moisture typically enters the refrigerant system through:

Air leaks from areas with gaskets or fittings

Refrigerant-11 at a pressure of 17 inches Hg vacuum has a saturation temperature of:

35°F

The lowest access point on a low pressure centrifugal air-conditioning unit is the:

Evaporator charging valve

A rupture disc on a recovery vessel for low pressure refrigerants relieves at:

15PSIG

According to ASHRAE guideline 3-1996 if the pressure in a system rises from 1mm Hg to a level above __________ during a standing vacuum test, system should be checked for leaks.

2.5mm Hg

During chiller evacuation, water is circulated to:

Prevent freezing of the water

When charging an R-410A water chiller, you must first charge with vapor to a pressure of at least __________ before switching to liquid charging.

120 PSIG

If you leak test a low pressure chiller with nitrogen in excess of 10 PSIG you could cause the _______ to fail.

Rupture disc

ASHRAE Standard 15-1994 requires that each machinery room must activate an alarm and mechanical ventilation before refrigerant concentrations exceed :

The TLV-TWA (threshold limit valve -time weighted average )

Which repair WOULD NOT fail under the EPA definition for " MAJOR MAINTENANCE, SERVICE, OR REPAIR "?

Replacing an oil filter

Refrigerant is added to a centrifugal machine through the:

Evaporator charging valve

What is meant by the term " high efficiency purge unit"?

Those purge units which discharge a low percentage of refrigerant with the air which they remove

The PRIMARY purpose of a purge unit on a CFC -11 chiller is to:

Remove noncondensables from the system

If you are using a recovery machine manufactured AFTER November 15, 1993, you must evacuate any low-pressure appliance to _ _ _ _ _ before making a major repair.

25mm of Hg absolute

If you suspect a leak in the water box of a chiller, you should place the leak detector probe ________ and sniff for refrigerants.

Through a drain valve

To determine how much vapor to charge into an evacuated chiller, you should charge with vapor until ____________.

The system pressure corresponds to a refrigerant saturation temperature of 36F

ASHRAE Standard 15-1994 requires the use of room sensors and alarms to detect :

Refrigerant leaks

The discharge from a rupture disc should be piped_______ for venting?

Outdoors

A centrifugal chiller's rupture disk is connected to the chiller's

Evaporator

To remove ice from sight glasses or viewing glasses use:

An alcohol spray

The maximum test pressure for leak testing a low pressure centrifugal is:

10 PSIG

According to ASHRAE standard 34 what is the safety classification of R-123?

B1

Excessive running of a purge system on a low pressure chiller generally indicates that the:

System is leaking

The typical design burst pressure for a rupture disk on a low-pressure centrifugal air-conditioning system is set at______

15 PSI

During the evacuation of a system containing large amounts of moisture, you can prevent freezing of this moisture by increasing the pressure with _________ gas.

Nitrogen