• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
  • Read
    Toggle On
    Toggle Off
Reading...
Front

Card Range To Study

through

image

Play button

image

Play button

image

Progress

1/25

Click to flip

Use LEFT and RIGHT arrow keys to navigate between flashcards;

Use UP and DOWN arrow keys to flip the card;

H to show hint;

A reads text to speech;

25 Cards in this Set

  • Front
  • Back

EPA regulations require that all appliances containing more than 50 pounds of refrigerant (except for commercial and industrial process refrigeration) be repaired when the leak rate exceeds ________ percent of the charge per year.

15 %

During vapor removal from a low pressure refrigeration system;

the system water pumps, the recovery compressor, and the recovery condenser water should all be on.

Which of the following repairs would ALWAYS be considered "major" under EPA's regulations?

Replacement of an evaporator coil.

EPA regulations require that leaking commercial and industrial process refrigeration be repaired when the leak rate exceeds ________ percent of the charge per year.

35 %

When leak testing a low pressure centrifugal with nitrogen, what is the maximum test pressure?

10 psig.

Where would you place a leak detector probe to check gas leaks into the water box with water removed?

Through a drain valve.

When removing oil from a low pressure system, the temperature should be 130 degrees F because;

less refrigerant will be contained in the oil at the higher temperature.

Why do chillers using CFC-11 and HCFC-123 require purge units?

System operates below atmospheric pressure.

R-11 or R-123 system refrigerant removal starts with;

liquid removal.

Charged low pressure refrigeration machines may be most efficiently leak checked by;

raising system pressure by heating with circulated hot water or heating blankets.

Charging refrigerant liquid into a refrigeration system under a 29 inch Hg vacuum can cause the;

refrigerant liquid to freeze.

What is the primary water source for a recovery unit condensing coil?

Local municipal water supply.

A hydrostatic tube test kit will;

determine if a tube leaks.

A centrifugal chiller's rupture disk is connected to the chiller's;

evaporator.

How do you determine when enough vapor has entered the refrigeration system before you charge refrigerant liquid?

Refrigerant saturation temperature increases to 36 degrees F.

When using recovery or recycling equipment manufactured BEFORE November 15, 1993, technicians must evacuate low-pressure appliances to the following level before making a major repair:

25 inches of Hg vacuum.

After reaching the required recovery vacuum on an appliance, you should;

wait for at least a few minutes to see if the system pressure rises, indicating that there is still refrigerant in liquid form or in the oil.

Appliances need not be evacuated all the way to the prescribed level when;

leaks in the appliance make evacuation to the prescribed level unattainable.

The PRIMARY purpose of a purge unit on a CFC-11 chiller is to;

remove non-condensables from the system.

When using recovery and recycling equipment manufactured AFTER November 15, 1993, technicians must evacuate low-pressure appliances to the following level before disposing of the appliance:

25 mm of Hg absolute.

Under EPA's regulations, which of the following methods can be used to pressurize an R-11 or R-123 system for the purpose of opening the system for a non-major repair?

Adding nitrogen.

ASHRAE Standard 15 - 1994 requires the use of room sensors and alarms to detect;

refrigerant leaks.

Under what code group of ASHRAE Standard 34 does R-123 fall?

B1.

Approximately how much refrigerant vapor is left in an average 350 ton R-11 chiller at 0 psig pressure once all the R-11 liquid has been removed?

100 lbs.

Refrigerant-11 at a pressure of 18.1 inches Hg vacuum has a saturation temperature of;

32 degrees F.