Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
25 Cards in this Set
- Front
- Back
EPA regulations require that all appliances containing more than 50 pounds of refrigerant (except for commercial and industrial process refrigeration) be repaired when the leak rate exceeds ________ percent of the charge per year. |
15 % |
|
During vapor removal from a low pressure refrigeration system; |
the system water pumps, the recovery compressor, and the recovery condenser water should all be on. |
|
Which of the following repairs would ALWAYS be considered "major" under EPA's regulations? |
Replacement of an evaporator coil. |
|
EPA regulations require that leaking commercial and industrial process refrigeration be repaired when the leak rate exceeds ________ percent of the charge per year. |
35 % |
|
When leak testing a low pressure centrifugal with nitrogen, what is the maximum test pressure? |
10 psig. |
|
Where would you place a leak detector probe to check gas leaks into the water box with water removed? |
Through a drain valve. |
|
When removing oil from a low pressure system, the temperature should be 130 degrees F because; |
less refrigerant will be contained in the oil at the higher temperature. |
|
Why do chillers using CFC-11 and HCFC-123 require purge units? |
System operates below atmospheric pressure. |
|
R-11 or R-123 system refrigerant removal starts with; |
liquid removal. |
|
Charged low pressure refrigeration machines may be most efficiently leak checked by; |
raising system pressure by heating with circulated hot water or heating blankets. |
|
Charging refrigerant liquid into a refrigeration system under a 29 inch Hg vacuum can cause the; |
refrigerant liquid to freeze. |
|
What is the primary water source for a recovery unit condensing coil? |
Local municipal water supply. |
|
A hydrostatic tube test kit will; |
determine if a tube leaks. |
|
A centrifugal chiller's rupture disk is connected to the chiller's; |
evaporator. |
|
How do you determine when enough vapor has entered the refrigeration system before you charge refrigerant liquid? |
Refrigerant saturation temperature increases to 36 degrees F. |
|
When using recovery or recycling equipment manufactured BEFORE November 15, 1993, technicians must evacuate low-pressure appliances to the following level before making a major repair: |
25 inches of Hg vacuum. |
|
After reaching the required recovery vacuum on an appliance, you should; |
wait for at least a few minutes to see if the system pressure rises, indicating that there is still refrigerant in liquid form or in the oil. |
|
Appliances need not be evacuated all the way to the prescribed level when; |
leaks in the appliance make evacuation to the prescribed level unattainable. |
|
The PRIMARY purpose of a purge unit on a CFC-11 chiller is to; |
remove non-condensables from the system. |
|
When using recovery and recycling equipment manufactured AFTER November 15, 1993, technicians must evacuate low-pressure appliances to the following level before disposing of the appliance: |
25 mm of Hg absolute. |
|
Under EPA's regulations, which of the following methods can be used to pressurize an R-11 or R-123 system for the purpose of opening the system for a non-major repair? |
Adding nitrogen. |
|
ASHRAE Standard 15 - 1994 requires the use of room sensors and alarms to detect; |
refrigerant leaks. |
|
Under what code group of ASHRAE Standard 34 does R-123 fall? |
B1. |
|
Approximately how much refrigerant vapor is left in an average 350 ton R-11 chiller at 0 psig pressure once all the R-11 liquid has been removed? |
100 lbs. |
|
Refrigerant-11 at a pressure of 18.1 inches Hg vacuum has a saturation temperature of; |
32 degrees F. |