True or false - ac and high temp systems require defrost

False

Coil temps that run above what temperature need defrost

30F

How long are run cycles?

20-22hrs

off cycle defrost will be used when evap Is below? And space temp is between?

When evap is below 30F


Space is between 35-40F

Temps

Cap tubes use what component for defrost

Constant cut in Tstat

Evap fans must stay on during what type of defrost

Force off cycle

Forced off cycle supplies how many hours defrost to run time

1 hour defrost to 2 hours run time

Colder applications will utilize what device with forced off cycle defrost

Time clocks

Three methods of shutting down compressors

Turn it off


Liquid line solenoid


Suction stop EPR

EPR operate by?

Inlet pressure regulator to a minimum setting

Suction stop EPR's have two points of operation, they are?

A point where the valve remains closed (cut out) and opens once pressures reach a certain point

supplementary defrost is used when the coil temp and space temp are below ____ and ______

When coil temp is below 32F


Space temp is 35F or lower

Types of supp heat (5)

Reverse


Electric


Kool-gas


Hot-gas


Water

Compressor is pumped down and shut off with the evap fans during which type of defrost

Electric

Explain electric sequence

- LLS de-energized


- system pumps down


-Fans shut off


-Heaters are energized


-Drip time countdown begins


System resumes operation

Why are the fans shut off during electric defrost

To maximize heating of the coil


To not release moisture to the box

Electric heaters should have what type of device associated with them?

High limit

What happens upon termination in electric defrost?

Fans are delayed to allow the coil to re-freeze

What initiates defrost?

A time clock

Tick tock

4 factors that terminate a defrost are?

Time


Temp


Pressure


Optical

Hot gas defrost are used on how many evaps?

Single and multiple evap systems

Hot gas from the discharge manifold defrosts in what type of supplementary defrost

Hot gas defrost

Two types of hot gas defrost are

One on one


Staggered

Hot gas lines for defrost flow rates are

1000-2000 ft/min

A problem with one on one hot gas defrosts is? How can this problem be fixed?

Runs out of hot gas


Drop out the condenser to raise head pressure

Where are one on one hot gas defrosts found

Ice machines

Another name for an ice machine defrost is?

Harvest cycle

One on one systems use how many evaps, how many comps?

1 of each

What does a vaporizer do?

Vaporizes left over liquid from the accumulator after the compressor

This device controls the flow of hot gas during defrosr

Hot gas regulator

Initial setting of the hot gas regulator?

15-25 psi differential

Most efficient method of defrost is

Hot gas defrost

Why are fans cycled off during hot gas defrost?

To prevent adding excess heat and moisture

A main problem faced with hot gas defrost is

Thermal stress

How can you avoid shocking a cold evap

Using a 2 stage defrost with a smaller solenoid - soft gas

Two types of defrost staggered systems

2 and 3 pipe systems

One evap is defrosted at 33% of capacity at any one time during

Hot gas staggered systems

33 - gg

Hot gas line, suction line, and liquid line are all included on an evaporator within

3 pipe systems

2 pipe systems have what kind of lines on their evaporators

Suction line


Liquid line

Hot gas line to ASC must equal the discharge line size on what type of defrosts?

One on one

How big are hot gas lines to be sized in a three pipe system

66% of the discharge line

Saturated vapor defrost is also known as

Kool gas defrost

Kool gas defrost is commonly found on

Rack systems

Kool gas defrost uses what from what device to defrost coils

Saturated vapour


The reciever

Less thermal shock is occured with this defrost method

Kool gas defrost

Refrigerant condensed where? During defrost is redirected where? To feed what? During kool defrost

Evap


Liquid line header


Other coils not in defrost

Must be a 2 pipe defrost system

Kool gas defrost

Kool gas defrost typically last

10 minutes

Defrosting how many systems at a time is preferred?

1 at a time

What must be kept up to achieve quick defrosts in kool gas

Reciever pressure

_____ approaches _____ in kool gas

Efficiency


Hot gas

Min water temp in water defrost is

50F

Water defrost has min gpm/sqft ? For how long?

3gpm


5-15 min

Gpm x what = total.min

Water defrost systems are commonly used where?

Ammonia systems

How long is a normal reverse cycle defrost

3-7 minutes

Reverse cycling defrost terminates by

Pressure control

A rapid decrease in liquid flow due to sudden closing if a valve is

Sudden liquid deceleration

What device will prevent split L's caused by liquid hammers

12" stand pipe

High pressure refrigeration injected into a cold coil is called

Condensation induced shock

Something shock

Volume causes a coil to collapse in

Condensation induced shock

Type of shock

These three forces can produce pressures of ____ to _____ psi

Atmospheric


Vapour


Liquid



2000-4000

Condensate is pitch is

4"/ft

Traps are located

Outside of the space

Continuous heater protection is how many watts at how many degrees

20 watts /ft 0F


30 watts /ft -20F

What type of defrost is this?

Kool gas

Name this defrost

Two pipe

Name this defrost

3 pipe

What type if defrost is this

One on one