True or false - ac and high temp systems require defrost |
False |
|
|
Coil temps that run above what temperature need defrost |
30F |
|
|
How long are run cycles? |
20-22hrs |
|
|
off cycle defrost will be used when evap Is below? And space temp is between? |
When evap is below 30F Space is between 35-40F |
Temps |
|
Cap tubes use what component for defrost |
Constant cut in Tstat |
|
|
Evap fans must stay on during what type of defrost |
Force off cycle |
|
|
Forced off cycle supplies how many hours defrost to run time |
1 hour defrost to 2 hours run time |
|
|
Colder applications will utilize what device with forced off cycle defrost |
Time clocks |
|
|
Three methods of shutting down compressors |
Turn it off Liquid line solenoid Suction stop EPR |
|
|
EPR operate by? |
Inlet pressure regulator to a minimum setting |
|
|
Suction stop EPR's have two points of operation, they are? |
A point where the valve remains closed (cut out) and opens once pressures reach a certain point |
|
|
supplementary defrost is used when the coil temp and space temp are below ____ and ______ |
When coil temp is below 32F Space temp is 35F or lower |
|
|
Types of supp heat (5) |
Reverse Electric Kool-gas Hot-gas Water |
|
|
Compressor is pumped down and shut off with the evap fans during which type of defrost |
Electric |
|
|
Explain electric sequence |
- LLS de-energized - system pumps down -Fans shut off -Heaters are energized -Drip time countdown begins System resumes operation |
|
|
Why are the fans shut off during electric defrost |
To maximize heating of the coil To not release moisture to the box |
|
|
Electric heaters should have what type of device associated with them? |
High limit |
|
|
What happens upon termination in electric defrost? |
Fans are delayed to allow the coil to re-freeze |
|
|
What initiates defrost? |
A time clock |
Tick tock |
|
4 factors that terminate a defrost are? |
Time Temp Pressure Optical |
|
|
Hot gas defrost are used on how many evaps? |
Single and multiple evap systems |
|
|
Hot gas from the discharge manifold defrosts in what type of supplementary defrost |
Hot gas defrost |
|
|
Two types of hot gas defrost are |
One on one Staggered |
|
|
Hot gas lines for defrost flow rates are |
1000-2000 ft/min |
|
|
A problem with one on one hot gas defrosts is? How can this problem be fixed? |
Runs out of hot gas Drop out the condenser to raise head pressure |
|
|
Where are one on one hot gas defrosts found |
Ice machines |
|
|
Another name for an ice machine defrost is? |
Harvest cycle |
|
|
One on one systems use how many evaps, how many comps? |
1 of each |
|
|
What does a vaporizer do? |
Vaporizes left over liquid from the accumulator after the compressor |
|
|
This device controls the flow of hot gas during defrosr |
Hot gas regulator |
|
|
Initial setting of the hot gas regulator? |
15-25 psi differential |
|
|
Most efficient method of defrost is |
Hot gas defrost |
|
|
Why are fans cycled off during hot gas defrost? |
To prevent adding excess heat and moisture |
|
|
A main problem faced with hot gas defrost is |
Thermal stress |
|
|
How can you avoid shocking a cold evap |
Using a 2 stage defrost with a smaller solenoid - soft gas |
|
|
Two types of defrost staggered systems |
2 and 3 pipe systems |
|
|
One evap is defrosted at 33% of capacity at any one time during |
Hot gas staggered systems |
33 - gg |
|
Hot gas line, suction line, and liquid line are all included on an evaporator within |
3 pipe systems |
|
|
2 pipe systems have what kind of lines on their evaporators |
Suction line Liquid line |
|
|
Hot gas line to ASC must equal the discharge line size on what type of defrosts? |
One on one |
|
|
How big are hot gas lines to be sized in a three pipe system |
66% of the discharge line |
|
|
Saturated vapor defrost is also known as |
Kool gas defrost |
|
|
Kool gas defrost is commonly found on |
Rack systems |
|
|
Kool gas defrost uses what from what device to defrost coils |
Saturated vapour The reciever |
|
|
Less thermal shock is occured with this defrost method |
Kool gas defrost |
|
|
Refrigerant condensed where? During defrost is redirected where? To feed what? During kool defrost |
Evap Liquid line header Other coils not in defrost |
|
|
Must be a 2 pipe defrost system |
Kool gas defrost |
|
|
Kool gas defrost typically last |
10 minutes |
|
|
Defrosting how many systems at a time is preferred? |
1 at a time |
|
|
What must be kept up to achieve quick defrosts in kool gas |
Reciever pressure |
|
|
_____ approaches _____ in kool gas |
Efficiency Hot gas |
|
|
Min water temp in water defrost is |
50F |
|
|
Water defrost has min gpm/sqft ? For how long? |
3gpm 5-15 min |
Gpm x what = total.min |
|
Water defrost systems are commonly used where? |
Ammonia systems |
|
|
How long is a normal reverse cycle defrost |
3-7 minutes |
|
|
Reverse cycling defrost terminates by |
Pressure control |
|
|
A rapid decrease in liquid flow due to sudden closing if a valve is |
Sudden liquid deceleration |
|
|
What device will prevent split L's caused by liquid hammers |
12" stand pipe |
|
|
High pressure refrigeration injected into a cold coil is called |
Condensation induced shock |
Something shock |
|
Volume causes a coil to collapse in |
Condensation induced shock |
Type of shock |
|
These three forces can produce pressures of ____ to _____ psi |
Atmospheric Vapour Liquid 2000-4000 |
|
|
Condensate is pitch is |
4"/ft |
|
|
Traps are located |
Outside of the space |
|
|
Continuous heater protection is how many watts at how many degrees |
20 watts /ft 0F 30 watts /ft -20F |
|
|
What type of defrost is this? |
Kool gas |
|
|
Name this defrost |
Two pipe |
|
|
Name this defrost |
3 pipe |
|
|
What type if defrost is this |
One on one |
|