Heater Drain Pump Trips



Test Question

1. Lo-Lo Level in suction Heater - note U1 is 5A/B and U2 is 4A/B!


2. Main Turbine Trip


3. Overcurrent


4. Overload


5. Both Suction valves (HMO-563/564) closed on MHDP

Heater Drain Pump Suction Valves



Test Question


1. One must be fully OPEN to start MHDP.


2. Position of suction x-ties determines which Heater Lo-Lo Level will trip MHDP.

Heater Drain Pump ELO will modulate open when flow is?

<1250 gpm

Heater Drain Pumps provide about ____% of the flow to the MFPs.
25

Which heaters do not have alternate drains to the Condenser in U1?






U2?

6A/B & 4A/B in Unit 1




6A/B only in Unit 2

Bleed steam isolation valves close on?

1. Turbine Trip


2. Hi-Hi heater level

FW heater alternate drains open on ______ and fail _____ on a loss of air:




The normal drains fail _____:

1. High heater level


2. open


3. closed

Drain Cooler Terminal Temperature Difference (DCTTD) is calculated by:

Drain Temperature Out - Feedwater Temp In

The Reheater Coolant Drain Tank (RCDT) and Moisture Separator Drain Tank (MSDT) goes to which heaters in both units?




Test Question

U1: RCDT - 6A/B, MSDT - 5A/B




U2: RCDT - 6A/B, MSDT 4A/B

Bleed Steam check valves are installed to prevent what?




Test Question

Turbine overspeed