Most common compressor?

Reciprocating

Most compressors are?

Belt driven

What component of pneumatic system stores the air?

Receiving tank

Pneumatic system must be free of what impurities?

Oil, water, dirt

What cools the air between a 2 stage compressor?

Intercooler

Why must a compressor be located in coolest location possible?

Cool air is denser. Making compressor more efficient

Delta P for compressor?

15psi

Pressure relief valve set at?

10psi over cut out

Pressure drop should not exceed?

5psi

When air reaches 100 percent humidity, it's known as?

Dew point

How does air dryer remove moisture from air?

Silica gel, activated alumina

Where is air dryer installed?

Downstream of receiver tank

Moisture trap locations?

Bottom of receiver tank, bottom of drip legs, low points

Piping used for pneumatic systems?

Black iron, type K and L copper

What do unloaders do?

Decrease pressure in cylinders

Where are pre filters installed?

Suction inlet

Aftercoolers have 2 styles?

Water cooled and air cooled

Aftercoolers installed where?

Between compressor and receiving tank, graded towards tank


If aftercoolers exceeds 3m in length, what happens to suction piping?

Increase one size

Diaphragm compressor would be installed where?

Hospitals, food processing plants, medical

What's the purpose of oil lubricantors on pneumatic system?

Lubes tools

Where is aftercooler located?

As close as possible to receiver tank. Upstream

Condensate drain on compressor does what?

Expels moisture

Horizontal pipe need to installed how?

Sloped toward end drains