There is some discrepancy on calibration intervals- in some places an electronic capture hood is 12 month intervals, sometimes 6 months. Same for thermal anemometer.

Question- does the 12 ACPH minimum for rooms with a CACI have to be HEPA supply??

If cleanroom has a VLF built in, what are requirements?


1. Must be unidirectional


2. Verified air sweeps over and away from product under dynamic conditions.


3. Velocity profile across entrance plane into work area is required.


4. Acceptable velocity range should be confirmed with airflow smoke pattern test.


5. They are typically 80-100 fpm.


6. Entrance plane is typically 6" below the HEPA filter or diffuser.



Displacement airflow only acceptable for what types of rooms?

Medium risk, non hazardous drugs
Preferred equipment for room segregation (i.e. DP)

Electronic manometer with a resolution to at least thousandths of an inch water column.

Sampling rate of photometer?




Sampling area of probe?


1 CFM




max opening of 1.7 in2 and minimum dimension of 0.5 inches.

Recommended RH and temp?






Use what instruments?


35-60%




Typically 68 or cooler




1% RH


0.1C