• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
  • Read
    Toggle On
    Toggle Off
Reading...
Front

Card Range To Study

through

image

Play button

image

Play button

image

Progress

1/8

Click to flip

Use LEFT and RIGHT arrow keys to navigate between flashcards;

Use UP and DOWN arrow keys to flip the card;

H to show hint;

A reads text to speech;

8 Cards in this Set

  • Front
  • Back

How do you control jet reaction

Position on stable ground


Start with pressure and flowrate that can be coped with and increase as and when needed


Have minimum 2 people when on high flow rate and pressure


Hose run out in straight line behind branch branch operator

Mercury ground monitor operating ranges

Raises/lowers 30-60 degrees


Side movement 20 degrees either side of centre


Nozzle can be lowered to 20 degrees if an operator stays with the unit

When should a ground monitor be used

Larger volume of water/foam is required than can be provided by hand branches


Operation require extinguishing media to be thrown a greater distance


Operations require extinguishing media over long period of time in same area of operations

What is the flow rate and pressure of the hosereel

Pressure - 30 bar preset, 42 bar max. Flowrates - 50, 100, 150, 230

Explain the pressure and flowrate of the RB101/Delta 400

Pressure - 6 bar optimum, 3 bar min, 7 bar max. Flowrate - 130, 230, 300, 400

Explain Projet 2 pressure and flowrate

Pressure - 7 bar optimum, 3.5 bar minimum


Flowrate at 7bar - Spray, 300 - Jet, 630 - Both, 930


Flowrate at 3.5bar - Spray, 200 - Jet, 400 - Both, 640



Has 57m throw

What is hte flowrate and pressure of the mercury ground monitor

Pressure - 7 bar, 3.5 bar minimum


Flowrates - 950, 1400, 1900. Deluge 1750

What are the features of RB101

Flow rate control ring


Pistol grip handle


Stirrup handle on/off


Pattern adjustment collar


Spinning teeth at nozzle - 5 broken or 3 in a row is a defect


Effective operation for pulse spray tech