List the procedures followed when installing a central air conditioner.
1. Setting blower & condensingunit
2. Installing the duct work
3. Running the thermostat wire
4. Installing refrigerant lines
5. Installing condensation lines
6. Installing gas pipe
7. Installing flue
What is the advantage of locating the blower unit at the center of the house when possible?
Easier and faster duct install
Name four things to consider when setting the condensing unit?
1. Proper air flow
2. Noise
3. Water drainage
4. Sun
What are the three things that you must watch for to prevent air from re–circulating in the condenser?
1. Installing too close to other objects
2. Overhang too close to top
3. Condensing units too close together
When installing a condensing unit under an overhang, what is the least amount of distance that the overhang can be from the top of the condenser?
4 ft
Why is it important to properly size the duct work?
Proper air flow
How many C.F.M. do we need for every ton of air conditioning?
400 per ton
Approximately how much C.F.M. comes out of a typical register?
100 cfm
Which load are the ducts sized for the heating or cooling load?
Cooling load
What is the component called in the duct system that connects the furnace to the trunk line?
Plenum
The ________________ distributes the air to the branches.
Trunk
What is installed in the trunk line to make sure that we have the proper air flow all the way through the trunk line?
Transitions
When installing round duct together what must you do to be sure that the connection is sealed properly?
Screw & Tape together
How many feet apart do you install hanger strap on the duct work to make sure that it is supported properly?
6 feet
When do we insulate the duct work?
Unconditioned spaces
Why is duct work insulated?
Prevent sweating, efficiency
What are the two refrigerant lines called that is installed between the condensing unit and blower unit?
1. Suction
2. Liquid
What will be the typical size of the liquid line when piping the condensing unit to the blower unit?
3/8 inch
What is the typical size suction line on a unit that is between 3 to 4 tons?
3/4 inch OD
Is soft or hard copper generally used to run the refrigerant lines on air conditioner?
Soft copper