• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
  • Read
    Toggle On
    Toggle Off
Reading...
Front

Card Range To Study

through

image

Play button

image

Play button

image

Progress

1/48

Click to flip

Use LEFT and RIGHT arrow keys to navigate between flashcards;

Use UP and DOWN arrow keys to flip the card;

H to show hint;

A reads text to speech;

48 Cards in this Set

  • Front
  • Back
  • 3rd side (hint)
Appliances other than gas shall be vented in accordance with the manufacturer's instructions and NFPA _____.



(A) 54

(B) 96


(C) 101


(D) 211

(D) 211

801.3

Equipment not required to be vented includes _____.



(A) listed gas furnaces


(B) listed water heaters


(C) listed ranges


(D) listed unit heaters

(C) listed ranges

802.2.1

Gas utilization equipment requiring venting shall be permitted to be vented by means of a mechanical draft system of either forced or induced draft design except for _____.



(A) furnaces


(B) water heaters


(C) incinerators


(D) room heaters

(C) incinerators

802.3.3.1

A listed vented wall furnace would use vents.



(A) Type B


(B) Type B-W


(C) Type L


(D) Single-wall metal pipe

(B) Type B-W

Table 802.4

No portion of a venting system shall pass through a _____ or furnace plenum.



(A) furnace enclosure


(B) fabricated air duct


(C) refrigerant machinery room


(D) concealed space

(B) fabricated air duct

802.3.5

Factory-built chimneys used to vent appliances that operate at ____ pressure shall be listed for such application.



(A) positive


(B) negative


(C) neutral


(D) other than positive

(A) positive

802.5.1

A chimney for residential-type or low-heat gas utilization equipment shall extend at least ____ feet above the highest point where it passes through a roof of a building.



(A) 2


(B) 3


(C) 4


(D) 5

(B) 3

802.5.4

A chimney for medium-heat equipment shall extend at least ____ feet higher than any portion of any building within ____ feet.



(A) 5, 10


(B) 10, 10


(C) 10, 25


(D) 10, 30

(C) 10, 25

802.5.4.1

The minimum height of a chimney shall be at least ____ feet above the highest connected draft hood or flue collar.



(A) 3


(B) 5


(C) 6


(D) 8



(B) 5

802.5.4.2

Where a chimney serves both gas and liquid fuel, and two or more openings are provided, the openings shall be ____.



(A) at the same level


(B) at different levels


(C) on opposite sides


(D) on a horizontal section

(B) at different levels

802.5.8.1

A listed combination gas and solid fuel-burning appliance connected to a single chimney flue shall be equipped with a(n) ____ to shut off the gas to the main burner.



(A) manual reset device


(B) automatic reset device


(C) emergency shutoff


(D) interrupting valve

(A) manual reset device

802.5.8.2

The remaining space surrounding a chimney liner, vent, or plastic piping installed within a masonry chimney flue ____ to vent another appliance.



(A) may be used


(B) needs jurisdictional approval


(C) shall not be used


(D) can be used if size is adequate

(C) shall not be used

802.5.11

A gas vent passing through a roof shall extend ____ a roof flashing, roof jack, or roof thimble and terminate with a ____.


(A) into, suitable cap


(B) through, termination cap a


(C) within, metal covering


(D) entirely through, listed termination cap

(D) entirely through, listed termination cap

802.6

Any angle greater than degrees from the vertical direction is considered



(A) 30, vertical


(B) 45, horizontal


(C) 60, vertical


(D) 75, horizontal

(B) 45, horizontal

802.6.1

The total horizontal distance of a vent plus the horizontal vent connector shall not exceed ____ percent of the vertical height of the vent.



(A) 25


(B) 50


(C) 75


(D) 100

(C) 75

802.6.1

Vents serving fan-assisted combustion system appliances shall be installed in accordance with the ____ or other approved engineering methods.



(A) installation instructions and Section 803


(B) vent manufacturer's and GAMA tables


(C) UL venting tables and Section 803


(D) installation instructions and GAMA tables

(A) installation instructions and Section 803

802.6.1

A 14 inch diameter gas vent extending through a metal flashing less than 8 feet from a vertical wall must extend at least ____ feet above the vertical wall.



(A) 1.25

(B) 1.5


(C) 1.75


(D) 2

(D) 2

802.6.2(1)

A Type B or Type L gas vent shall terminate at least ____ feet in vertical height above the highest connected draft hood or flue collar.



(A) 4


(B) 5


(C) 6


(D) 8

(B) 5

802.6.2.1

A Type BW gas vent shall terminate at least ____ feet above the bottom of the wall furnace.



(A) 10


(B) 10.5


(C) 12


(D) 14

(C) 12

802.6.2.2

A gas vent extending through an outside wall shall not terminate adjacent to the wall or below ______.


(A) eaves or parapets


(B) street grates


(C) foliage


(D) roof gutters

(A) eaves or parapets

802.6.2.3

For sizing an individual gas vent for a single draft hood-equipped appliance, the effective area of the vent connector and the gas vent shall not be less than the area of the draft hood outlet or greater than ____ times the draft hood outlet area.



(A) 4


(B) 5


(C) 6


(D) 7

(D) 7

802.6.3.1(3)

For sizing a gas vent connected to two appliances with draft hoods, the area of the vent shall be not less than the larger hood plus ____ percent of the smaller draft hood outlet.



(A) 40


(B) 50


(C) 60


(D) 75

(B) 50
802.6.3.1(4)
For sizing gas vents for Categories II, III, and IV appliances, the gas vent shall comply with ____



(A) Section 803.0


(B) standard venting practices


(C) the equipment manufacturer's instructions


(D) the National Fuel Gas Code

(C) the equipment manufacturer's instructions

802.6.3.2

A common vent serving Category I appliances in multistory installations is permitted, providing the venting system is designed and installed in accordance with _____.



(A) approved engineering methods and this code


(B) the equipment manufacturer's installation instructions


(C) standard venting practices (D) the local jurisdiction's Fire Code

(A) approved engineering methods and this code

802.6.4

Single-wall metal pipe shall not be used ______ for venting gas appliances.



(A) unless approved by the Authority Having Jurisdiction (B) outdoors in cold climates (C) in high humidity locations (D) unless positively sealed

(B) outdoors in cold climates

802.7.1

Single-wall metal pipe used to vent gas appliances shall not originate in any _____.



(A) commercial kitchen


(B) furnace enclosure


(C) unoccupied attic or concealed space


(D) unheated space

(C) unoccupied attic or concealed space

802.7.3.2

A mechanical draft venting system shall terminate at least ___ feet above any forced air inlet within 10 feet.



(A) 3


(B) 4


(C) 5


(D) 6

(A) 3

802.8.1

A mechanical draft venting system, of other than direct-vent type, shall terminate at least ____ feet below or horizontally from a door, operable window, or gravity air inlet into any building.



(A) 1


(B) 2


(C) 3


(D) 4

(D) 4

802.8.2

The bottom of any mechanical draft or direct-vent terminal shall be at least ____ inches above grade.



(A) 6


(B) 9


(C) 12


(D) 18

(C) 12

802.8.2

A vent connector shall be made of noncombustible ____ material capable of withstanding the vent gas temperature produced by the gas utilization equipment.



(A) durable


(B) metallic


(C) metal or plastic


(D) corrosion-resistant

(D) corrosion-resistant

802.10.1.1

Vent connectors shall not be covered with ____.



(A) insulation


(B) paint


(C) a combustible surface


(D) building materials

(A) insulation

802.10.1.3(2)

A low-heat appliance with a single-wall galvanized steel vent connector that is 7 inches in diameter shall have a connector thickness of not less than ____ inch.



(A) 0.019


(B) 0.023


(C) 0.029


(D) 0.034

(B) 0.023

Table 802.10.1.4

A medium-heat appliance with a steel vent connector that is 15 inches in diameter shall have a connector thickness of not less than ____ inch.



(A) 0.034


(B) 0.053


(C) 0.067


(D) 0.093

(C) 0.067

Table 802.10.1.5

Where the size of a Category I vent connector is increased to overcome installation limitations and to obtain capacity equal to equipment input, the size increase shall be made at the ____.



(A) vent connection


(B) draft hood outlet


(C) vent manifold


(D) common vent

(B) draft hood outlet

802.10.2.4

A vent connector shall slope upward at a slope of no less than ___ inch per foot.



(A) 1/8


(B) 1/4


(C) 1/2


(D) 1

(B) 1/4

802.10.6

Vent connector supports shall be _____.



(A) adequate for the design and weight of the material


(B) placed at intervals 6 feet or less


(C) placed at intervals 8 feet or less


(D) placed at intervals 10 feet or less inch per foot.

(A) adequate for the design and weight of the material

802.10.8

A vent connector shall not pass through any ceiling, floor, or _____.


(A) partition


(B) masonry wall


(C) fire-resistance-rated wall


(D) exterior wall

(C) fire-resistance-rated wall

802.10.12

Draft hoods and barometric draft regulators shall be installed ____ the equipment so as to prevent pressure differences between the draft hood or regulator and the combustion air supply.



(A) within 5 feet of


(B) within 8 feet of


(C) within 10 feet of


(D) in the same room or enclosure as

(D) in the same room or enclosure as

802.12.4

Automatically operated vent dampers shall be of ____.



(A) a listed type


(B) the size and model recommended by the equipment manufacturer


(C) a voltage suitable for the appliance


(D) a metallic type

(A) a listed type

802.14

When using the venting tables for multiple appliance venting outlined in Section 803.0, the horizontal portion of the vent connector is generally limited to ____ inches in length per inch of connector diameter or reductions in capacity apply.



(A) 12


(B) 18


(C) 24


(D) 36

(B) 18

803.2.1

If a listed corrugated chimney liner is installed, the maximum capacity shall be ____ for Type B vents.



(A) the same as the table capacity


(B) reduced by 5 percent of the table capacity


(C) reduced by 10 percent of the table capacity


(D) reduced by 20 percent of the table capacity.

(D) reduced by 20 percent of the table capacity.

803.2.18

If the vent connectors are combined prior to entering the vertical portion of the common vent, the maximum capacity of the common vent _____.



(A) shall be reduced by 10 percent


(B) shall be reduced by 15 percent


(C) shall be reduced by 20 percent


(D) vent remains the same

(A) shall be reduced by 10 percent

803.2.3

Connector rise is measured from the draft hood or connector collar to the ____.



(A) lowest point at which the gas streams come together


(B) centerline where the gas streams come together


(C) outlet of the common vent (D) base of the common vent

(B) centerline where the gas streams come together

803.2.10

Interpolation for calculating capacities _____.



(A) is not permitted


(B) is permitted for dimensions that fall between table entries (C) must be approved by Authority Having Jurisdiction (D) is permitted if the vent size is increased

(B) is permitted for dimensions that fall between table entries

803.1.16

Chimney venting systems using mechanical draft shall be sized accordance with _____.



(A) Category I venting tables


(B) manufacturer's installation instructions


(C) approved engineering methods


(D) NFPA 211

(C) approved engineering methods

802.6.3.3

Through-the-wall vents for Category II and Category IV and non-categorized condensing appliances shall not terminate over _____.



(A) private walkways


(B) public walkways


(C) building exists


(D) outdoor air intake openings

(B) public walkways

802.8.4

Unless a vertical vent is designed in accordance with approved engineering methods, the flow area of the vent shall not exceed ____ times the flow area of the flue collar or draft hood outlet area of the appliances.



(A) four


(B) five


(C) six


(D) seven

(D) seven

803.1.9

The minimum cross sectional area of a common vent shall be _____ connector.



(A) two times the area of the largest vent


(B) four times the area of the largest vent


(C) equal to or larger than the smallest vent


(D) equal to or greater than the area of the largest

(D) equal to or greater than the area of the largest

803.2.6