When using the Standard Method, the minimum required volume of indoor combustion air shall be __cubic feet per ___ Btu/h.



(A) 20, 1,000


(B) 30, 2,000


(C) 40, 2,000


(D) 50, 1,000

(D) 50, 1,000

701.4.1

Combining spaces in different stories, the openings in doors or floors shall have a total minimum free area of ____ square inch(es) per 1,000 Btu/h.



(A) 1


(B) 2


(C) 3


(D) 4

(B) 2

701.5(2)

Outdoor combustion air openings shall have a minimum of ____ inch(es).



(A) 1


(B) 2


(C) 3


(D) 4

(C) 3

701.6

Two combustion air openings communicating directly to the outdoors shall commence within ___ inches of the top and ____ inches of the bottom of the enclosure.



(A) 2, 12


(B) 6, 12


(C) 12, 12


(D) 18, 12



(C) 12, 12

701.6.1

The One Permanent Opening Method requires that equipment shall have a minimum clearance of _____ inch(es) from the front of the appliance.



(A) 1


(B) 2


(C) 4


(D) 6

(D) 6

701.6.2

Appliances located in a confined space with air taken from outside the structure by means of one vertical or horizontal duct shall have a minimum free area of 1 square inch per ____ Btu/h.



(A) 1,000


(B) 2,000


(C) 3,000


(D) 1 square inch per 4,000

(C) 3,000

701.6.2

Engineered combustion air installations shall provide adequate supply of combustion, ventilation, and dilution air and shall be approved by the ____.



(A) manufacturer's instructions


(B) Authority Having Jurisdiction


(C) contractor


(D) owner

(B) Authority Having Jurisdiction

701.8

Where all combustion air is provided by a mechanical air supply system, the combustion air shall be supplied from outdoors at a minimum rate of ____ cubic ft. per 1,000 Btu/h.



(A) 0.10


(B) 0.20


(C) 0.25


(D) 0.35

(D) 0.35

701.9

Where exhaust fans are installed, additional air shall be provided to replace the ____ air.



(A) primary


(B) secondary


(C) exhausted


(D) combustion

(C) exhausted

701.9.1

Where the design and free area are not known, it shall be assumed that wood louvers will have _____ percent free area.



(A) 15


(B) 25


(C) 35


(D) 45

(B) 25

701.10(1)

Where the design and free area are not known, it shall be assumed that metal louvers will have ____ percent free area.



(A) 25


(B) 45


(C) 50


(D) 75

(D) 75
701.10(1)
_____ louvers shall be interlocked with the equipment so they are proven in the full open position prior to main burner ignition and during main burner operation.



(A) Wood


(B) Metal


(C) Motorized


(D) Mechanical

(C) Motorized

701.10(3)

Combustion air ducts shall serve a _____ space.



(A) single


(B) duplexed


(C) confined


(D) filtered

(A) single

701.11(3)

Intakes for combustion air ducts located exterior to the building shall have the lowest side of the combustion air intake at least ____ inches vertically from the adjoining ground level.



(A) 2


(B) 6


(C) 12


(D) 18

(C) 12
701.11(6)
_____ operated dampers shall not be installed in combustion air openings.



(A) Manually


(B) Mechanical


(C) Louvered


(D) Direct

(A) Manually

701.12

Horizontal upper combustion air ducts shall not slope _____



(A) upward


(B) downward toward the source of combustion air.


(C) flat


(D) even

(B) downward toward the source of combustion air.
701.11(7)
The remaining space surrounding a chimney liner, gas vent, special gas vent, or plastic piping installed within a masonry, metal. or factory-built chimney shall not be used to supply combustion air unless it is _____ for installation in a solid fuel burning fire place.



(A) approved


(B) designed


(C) specifically prohibited


(D) included

(B) designed

701.11(8)

The Known Air Infiltration Rate Method requires (15 ft3/ACH) x (ifan11,000 Btu/h) for fan-assisted appliances, but no smaller than ___ cubic feet per 1,000 Btu/h.



(A) 15


(B) 20


(C) 25


(D) 30

(D) 30

701.4.2(3)

The One Permanent Opening Method requires the equipment have a clearance of at least ____ inch(es) from the side and back.



(A) 1


(B) 3


(C) 5


(D) 8

(A) 1

701.6.2

Combustion air is not required for _____



(A) natural draft appliances


(B) gas heating appliances


(C) fuel-burning equipment


(D) domestic clothes dryers

(D) domestic clothes dryers

701.1(2)

Combustion air ducts, except in dwellings, shall be ____



(A) galvanized steel


(B) 6 inch minimum width


(C) vertical only


(D) horizontal only

(A) galvanized steel

701.11(1)

When determining combustion air requirements, operation of exhaust fans, kitchen ventilating systems, clothes dryers, and fireplaces shall ____



(A) have makeup air provided


(B) be excluded


(C) be in separate rooms


(D) all be in same room

(A) have makeup air provided

701.3

Combustion air ducts that terminate in an attic shall be screened _____.



(A) at neither end


(B) at the lower end


(C) at the upper end


(D) None of the above apply

(D) None of the above apply

701.11(5)

Power-actuated movable louvers admitting combustion air may be used _____.



(A) with prior approval


(B) without prior approval


(C) This is not permitted by code


(D) when interlocked with the appliance

(D) when interlocked with the appliance

701.10(3)

Appliances located in a combined space with all air taken from the inside of the building and from the same story shall have each opening for combustion air sized at 1 square inch per ____ Btu/h but not less than 100 in.2.



(A) 1,000


(B) 2,000


(C) 3,000


(D) 4,000

(A) 1,000

701.5(1)

Appliances located in a confined space with all air taken from the outside by means of two horizontal ducts shall have each opening sized based on 1 square inch per ____ Btu/h.



(A) 1,000


(B) 2,000


(C) 4,000


(D) 5,000

(B) 2,000

701.6.1(2)

Dampers in combustion air ducts or plenums are ____



(A) required


(B) fire dampers


(C) prohibited


(D) volume dampers

(C) prohibited

701.12

The required size of combustion air openings shall be _____.



(A) based on the net free area of each opening


(B) in accordance with the Building Code


(C) sized without louvers and grills in place


(D) as approved by the Authority Having Jurisdiction

(A) based on the net free area of each opening

701.10(1)

Using the Known Infiltration Method: What's the smallest size room a 100,000 Btu fan-assisted appliance be installed in without any additional combustion air? _____



The ACH is .25 Given: (15 ft3/ACH) x (l'an/1,000 Btu/h) 'fan= fan-assisted appliance input in Btu per hour ACH= air change per hour




(A) 3,300 ft3


(B) 4,800 ft3


(C) 6,000 ft3


(D) 7,200 ft3

(C) 6,000 ft3

701.4.2


EQ 701.4.2(2)

Using the Known Infiltration Method. What's the smallest size room a 100,000 Btu draft hood-equipped appliance can be installed in without any additional combustion air? ____.



The ACH is .25 Given: (21 ft3/ACH) x (Iother /1,000 Btu/h) 'other =ail appliances other than fan-assisted input in Btu per hour ACH = air change per hour




(A) 4,800 ft3


(B) 5,800 ft3


(C) 8,400 ft3


(D) 9,500 ft3

(C) 8,400 ft3
701.4.2

EQ 701.4.2(1)

In a room that is 25x25x10, the available volume for combustion air would be ____.



(A) 625 ft2


(B) 2,800 ft3


(C) 5,000 ft3


(D) 6,250 ft3

(D) 6,250 ft3

701.4.1