Return air ducts, outside air ducts, plenums, or concealed spaces may be of combustible construction when



(A) in an office building


(B) serving a dwelling unit


(C) the building is two stories or less


(D) the building has a sprinkler system

(B) serving a dwelling unit

602.2

Joints of duct systems shall be made substantially tight by means of ____



(A) tape, mastic, or gasketing


(B) an approved duct sealant


(C) fire-retardant caulking


(D) nonporous caulking



(A) tape, mastic, or gasketing

602.4

Metal ducts installed in or under a concrete slab shall be ____



(A) insulated


(B) encased in at least 2 inch thick concrete


(C) covered with 4 mil


(D) approved for underground use polyethylene wrap

(B) encased in at least 2 inch thick concrete

603.2

The minimum distance from the ground to any metal duct shall not be less than inches.



(A) 2


(B) 4


(C) 6


(D) 12

(B) 4

603.2

The receptacle shall be securely suspended from the floor members and shall not be more than ___ inches below the floor opening.



(A) 12


(B) 18


(C) 24


(D) 48

(B) 18

507.8.1

Exit corridors, when required to be fire-resistive construction by the ____ shall not have ventilating ceilings.



(A) Fire Code


(B) Authority Having Jurisdiction


(C) Building Code


(D) NFPA

(C) Building Code

606.1

Where it is required to move under ducts for access to areas of the crawl space a minimum vertical clearance of ___ inches shall be required.



(A) 24


(B) 20


(C) 22


(D) 18

(D) 18

603.1

Insulation applied to the surface of ducts, including duct coverings, linings, tapes, and adhesives, located in a building shall have a flame-spread index not greater than



(A) 25


(B) 50


(C) 100


(D) 200

(A) 25

604.1

Insulation applied to the surface of ducts, including duct coverings, linings, tapes, and adhesives, located in a building shall have a smoke-developed rating of not more than ___



(A) 25


(B) 50


(C) 100


(D) 200

(B) 50

604.1

Crimp joints for round ducts shall have a contact lap of at least ___ inch(es).



(A) 1


(B) 1.5


(C) 2


(D) 2.5

(B) 1.5

602.4

Electrical wiring in plenums shall comply with ____, and California Electric Code.



(A) NFPA 54


(B) NFPA 70


(C) NFPA 262


(D) NFPA 211

(C) NFPA 262

602.2(5)

The temperature of the air conveyed in approved factory-made air-ducts is limited to ___



(A) 125


(B) 212


(C) 250


(D) 400

(C) 250

603.3

Furnaces supplying warm air to an underfloor space used as a plenum shall be equipped with an approved temperature limit control that will limit the outlet temperature to ___°F.



(A) 120


(B) 150


(C) 200


(D) 250

(C) 200

607.7

Supports for rectangular ducts when suspended from above, shall be installed


(A) on two opposite sides of each duct


(B) at no more than 12 foot intervals


(C) with a minimum of two 3/4-inch straps


(D) with a minimum of 20 gauge wire

(A) on two opposite sides of each duct

603.2

D. horizontal swing

603.2.5

Air-moving systems supplying air in excess of 2,000 cfm shall be equipped with



(A) an automatic shutoff


(B) fire dampers


(C) a fire-extinguishing system


(D) volume dampers

(A) an automatic shutoff

608.1

Factory-made air ducts and faced insulations shall have legibly printed on the exterior surface the following information ____



(A) thermal resistance (R) value at installed thickness


(B) maximum operating temperature


(C) maximum operating velocity


(D) name or mark of the listing agency

(A) thermal resistance (R) value at installed thickness

604.1

Smoke detectors for air duct installation shall be ____



(A) approved


(B) installed in accordance with the Electrical Code


(C) compatible with operating velocities, pressures, temperature, and humidity of the system


(D) tested before installation

(C) compatible with operating velocities, pressures, temperature, and humidity of the system

608.1

Automatic shutoff is not required ____



(A) when rooms have direct exit to the building exterior and the travel distance is less than 100 feet


(B) when rooms have direct access to exit corridors


(C) in R1 Occupancies


(D) in buildings of less than two stories

(A) when rooms have direct exit to the building exterior and the travel distance is less than 100 feet

608.1

When smoke detectors are required as part of an automatic shutoff system, they shall be installed in the _____



(A) return air duct ahead of any fresh-air inlet


(B) main supply air duct served by such equipment


(C) fresh-air inlet


(D) main return and the main supply duct

(B) main supply air duct served by such equipment

608.1(5)

Factory-installed smoke detectors installed in listed air-moving equipment may be used in lieu of smoke detectors installed in the main ____ served by such equipment.



(A) supply-air duct


(B) return-air duct


(C) outside-air duct


(D) supply and return air ducts

(A) supply-air duct

608.1(5)

The use of under-floor space as a supply plenum shall be limited to ____



(A) single-family dwellings


(B) residential construction


(C) dwelling units not more than two stories in height


(D) those structures where combustible construction is allowed

(C) dwelling units not more than two stories in height

607.2

Where gypsum products are exposed in ducts or plenums, the air temperature shall be restricted to a range from ____ °F.



(A) 0 to 120


(B) 32 to 125


(C) 50 to 125


(D) 50 to 212

(C) 50 to 125

602.1

When gypsum products are exposed in ducts or plenums, the ____



(A) gypsum shall be listed for such use


(B) moisture content shall be controlled so the material is not adversely affected


(C) gypsum products shall be adequately sealed


(D) gypsum product must be plenum rated

(B) moisture content shall be controlled so the material is not adversely affected

602.1

Exhaust ducts under positive pressure and venting systems shall not extend into or through _____



(A) ducts or plenums


(B) occupied spaces


(C) unheated spaces


(D) hazardous occupancies

(A) ducts or plenums

602.1

Ducts exposed to mechanical damage by vehicles or from other causes shall be



(A) prohibited


(B) protected by approved barriers


(C) reinforced


(D) enclosed

(B) protected by approved barriers

603.4

The minimum dimensions for access openings for fire dampers shall be ____



(A) adequate to permit inspection and maintenance of the damper and its operating parts


(B) the same size as the minimum dimension of the duct


(C) large enough to permit removal of the damper


(D) the diagonal of the access opening shall be the same length as the damper

(A) adequate to permit inspection and maintenance of the damper and its operating parts

605.5

The use of rated corridors in fire-resistive construction to convey air to or from adjoining rooms is



(A) an acceptable practice


(B) prohibited by the code


(C) permitted when the openings are protected with fire dampers


(D) permitted in buildings of three stories or less

(B) prohibited by the code

602.1

Each access door for a smoke damper or fire damper shall be labeled with letters not less than inch(es) high.



(A) 1/2


(B) 3/4


(C) 1


(D) 11/2

(A) 1/2

605.5

Smoke dampers and/or fire dampers shall be installed in a manner to ensure _____



(A) actuation by a control device


(B) closure within reasonable time limits


(C) no interference of dampers' operating parts from duct liners or external insulation


(D) movement within the rated partition

(C) no interference of dampers' operating parts from duct liners or external insulation

605.6

Fire dampers shall be



(A) field tested for operation (B) periodically inspected


(C) labeled by an approved agency


(D) securely fastened to duct work

(C) labeled by an approved agency

605.2

Smoke dampers shall



(A) comply with the referenced standard for leakage-rated dampers


(B) be tested by a certified installer


(C) be labeled by the manufacturer


(D) not be required in buildings less than four stories

(A) comply with the referenced standard for leakage-rated dampers

605.1

Vibration isolators to isolate equipment from metal ducts shall be of an approved material and not exceed ___ inches in length.



(A) 6


(B) 8


(C) 10


(D) 12

(C) 10

602.7

Insulation R-value need not exceed R 3.5 for a supply or return runout to an air terminal or outlet in a heating or cooling system when the runout length is less than ___ feet.



(A) 5


(B) 7


(C) 10


(D) 12

(C) 10

604.1(3)