43 Cards in this Set

  • Front
  • Back
  • 3rd side (hint)
A hood or that portion of a primary collection means designed for collecting cooking vapors and residues shall be constructed of and be supported by steel not less than No. (MSG).



(A) 24


(B) 16


(C) 18


(D) 22

(C) 18

508.1.1

Type 1 hoods constructed of stainless steel shall have a thickness of not less than inch.



(A) 0.0625


(B) 0.0250


(C) 0.030


(D) 0.037

(D) 0.037

508.1.1

Type II hoods constructed of copper shall be of copper sheets not less than ounces per square inch.



(A) .24


(B) .17


(C) .32


(D) .12

(B) .17

508.1.1(2)

On a common duct system the bleed-air duct shall have a fire damper at least inches from the exhaust duct connection.



(A) 3


(B) 6


(C) 12


(D) 24

(C) 12

511.4.2

Except where enclosures are required, hood, grease removal devices, exhaust fans, and ducts shall have a clearance of at least inches to combustible materials.



(A) 6


(B) 18


(C) 24


(D) 12

(B) 18

507.2

Field-applied grease duct enclosures shall be listed in accordance with



(A) NFPA 96


(B) UL 723


(C) ASTME E 2336


(D) ASHRAE 90.1

(C) ASTME E 2336

507.2.5

For canopy-type hoods, the inside edge shall overhang or extend a horizontal distance of not less than inches beyond the edge of the cooking surface on all open sides.



(A) 3


(B) 6


(C) 8


(D) 12

(B) 6

508.4.1

For canopy-type hoods, the vertical distance between the lip of the hood and the cooking surface shall not be more than feet.



(A) 5


(B) 3


(C) 6


(D) 4

(D) 4

508.4.1

The distance between the grease removal device of commercial cooking equipment and the cooking surface shall not be less than inches.



(A) 12


(B) 18


(C) 24


(D) 36

(B) 18

508.4.1

The volume of air exhausting through a non-canopy-type hood to the duct system shall be not less than ___ per lineal foot of cooking equipment.



(A) 1,200


(B) 2,500


(C) 300


(D) 600

(C) 300

508.4.2

Replacement air quantity shall be adequate to prevent negative pressures in the commercial cooking area from exceeding inch water column.



(A) 0.01


(B) 0.02


(C) 0.04


(D) 0.06

(B) 0.02

511.3

Compensating hoods shall extract at least ___ percent of their required exhaust air flow from the kitchen area.



(A) 5


(B) 10


(C) 15


(D) 20

(D) 20

511.3

Duct systems serving a Type I hood shall slope not less than toward an approved grease reservoir.



(A) 1


(B) 1/4


(C) 1/8


(D) 1/2

(B) 1/4

510.1.3

Where horizontal ducts exceed ___ feet in length the slope shall be not less than 1 inch per lineal foot.



(A) 25


(B) 50


(C) 30


(D) 75

(D) 75

510.1.3

No solid-fuel cooking device shall be permitted within __ feet of any deep-fat frying unit.



(A) 2


(B) 3


(C) 5


(D) 6

(B) 3

517.8.3

In a six-story building, the duct enclosure shall have a fire-resistance rating of not less than



(A) 20 minutes


(B) 1 hour


(C) 2 hours


(D) 3 hours

(C) 2 hours

510.7.1.2

A duct shall be permitted to contact noncombustible floors, interior walls, and other noncombustible structures or supports, but it shall not be in contact for more than ____ percent of its surface area per each lineal foot of contact length.



(A) terms and listings


(B) 30


(C) 50


(D) 25

(A) terms and listings

510.2.1

On horizontal ducts, at least one ____ opening shall be provided for personnel entry.



(A) 30 in. by 30 in.


(B) 20 in. by 20 in.


(C) 12 in. by 12 in.


(D) 24 in. by 24 in.

(B) 20 in. by 20 in.

510.3.3.1

For rooftop terminations of exhaust ducts serving commercial kitchen equipment, the exhaust flow shall be directed up and away from the surface of the roof and a minimum of ___ above the roof surface.



(A) 12 inches


(B) 3 feet


(C) 2 feet


(D) 40 inches

(D) 40 inches

510.8.1(2)

h

h

h

h

h

h

Grease filter drip trays shall be kept to the minimum size needed to collect grease and shall have a capacity not exceeding ____ gallon(s).



(A) 1/2


(B) 1


(C) 2


(D) 5

(B) 1

509.2.4.1

Access panels shall have a gasket or sealant that is rated for ____ degrees Fahrenheit and be grease-tight.



(A) 2,300


(B) 1,300


(C) 1,700


(D) 1,500

(D) 1,500

510.3.3.4

Exhaust fans with duct work connected to both sides shall have access for cleaning and inspection within ____ feet of each side of the fan.



(A) 2


(B) 4


(C) 3


(D) 5

(C) 3

510.3.2

The air velocity through any duct shall be not more than ____ feet per minute.



(A) 1,500


(B) 500


(C) 1,000


(D) 2,500

(D) 2,500

511.2

Exhaust fan housing shall be constructed of carbon steel not less than No. ____ (MSG) in thickness.



(A) 10


(B) 16


(C) 14


(D) 18

(B) 16

511.1.4

The bleed-air duct shall have a fire damper at least ___ inches from the exhaust duct connection.



(A) 6


(B) 24


(C) 18


(D) 12

(D) 12

511.4.2

An inspection and servicing of the cooking equipment shall be made at least ____ by qualified persons.



(A) monthly


(B) quarterly


(C) annually


(D) semi-annually

(C) annually

515.3

All deep-fat fryers shall be installed with at least a ____ inch space between the fryer and surface flames from adjacent cooking equipment.



(A) 16


(B) 10


(C) 18


(D) 12

(A) 16

515.1.1.3

If the building is less than four stories in height, the enclosure wall shall have a fire-resistance rating of not less than ____ hour(s)



(A) 2


(B) 1/2


(C) 1/4


(D) 1

(D) 1

510.7.1.1

All seams, joints, and penetrations of the hood enclosure that direct and capture grease-laden vapors and exhaust gases shall have a continuous _____ to the hood's lower outermost perimeter.



(A) liquid-tight external weld


(B) liquid-tight internal braze


(C) liquid-tight external braze (D) liquid-tight internal seal

(A) liquid-tight external weld

508.2

All kitchen exhaust ducts on the exterior of the building shall be protected by paint or other suitable weather-protective coating or shall be constructed of noncorrosive ____



(A) copper


(B) galvanized steel


(C) aluminum


(D) stainless steel

(D) stainless steel

510.6.1

Access panels for ducts serving commercial kitchen equipment shall have a gasket or sealant rated for a minimum of ____ degrees F.



(A) 1,200


(B) 1,500


(C) 800


(D) 1,300

(B) 1,500

510.3.3.4

Required enclosures for ducts for commercial kitchen equipment shall have a fire-resistance rating of not less than ___ for a building four stories or more in height.



(A) 2 hours


(B) 3 hours


(C) 1 hour


(D) 20 minutes

(A) 2 hours

510.7.1.2

Noncombustible and limited-combustible enclosures for kitchen duct exhausts shall maintain a clearance between the duct and the interior surface of the enclosure of not less than ___ inches.



(A) 18


(B) 12


(C) 3


(D) 6

(D) 6

510.7.1.3

Exhaust fans with duct-work connected to both sides shall have access for cleaning and inspection within of each side of the fan.



(A) 3 feet


(B) 18 inches


(C) 12 inches


(D) 2 feet

(A) 3 feet

510.3.2

All hoods shall be secured in place by ____ supports.



(A) combustible


(B) noncombustible


(C) manufacturer's recommended


(D) listed

(B) noncombustible

508.1.1(2)

Rooftop terminations of exhaust ducts shall be provided with a grease collection container that is



(A) noncombustible


(B) closed


(C) rainproof


(D) all of the above

(D) all of the above

510.8.1.3

Ducts for type II hoods shall be ____




(A) welded or brazed


(B) constructed of materials as set forth in chapter 6


(C) at least steel of 24 gauge


(D) constructed of at least 16 us gauge steel

(C) at least steel of 24 gauge

508.1.1(2)

The difference between inside dimensions of overlapping duct sections shall not exceed



(A) 1/4


(B) 3/8


(C) 3/4


(D) 1/8

(A) 1/4

Figure 510.5.2.1(1)

When a 20 inch by 20 inch access panel is not possible on horizontal ducts, openings large enough to permit thorough cleaning shall be provided at __ foot intervals.



(A) 6


(B) 10


(C) 12


(D) 8

(C) 12

510.3.3.1(A)

In line exhaust fans shall be of the type with the motor located outside the airstream and with belts and pulleys protected from the airstream by a ____ housing.



(A) noncombustible


(B) stainless steel


(C) limited-combustible


(D) grease-tight

(D) grease-tight

511.1.2

A placard identifying the use of the extinguisher as a secondary backup means to the automatic fire suppression system shall be conspicuously placed _____



(A) on the front door of the restaurant


(B) at the entrance to the cooking area


(C) near each portable fire extinguisher in the cooking area


(D) at the entrance to the kitchen

C) near each portable fire extinguisher in the cooking area

513.2.1