What does ventilation do?

Helps with.....


1- Combustion


2- Correct operation of flues


3 - Cooling


dispute heat and condenstion

Bad ventilation or air supply to the burner can cause...

VITIATION

Incomplete Combustion causes what?

carbon monoxide

What is adventitious air?

Is the standard calculated amount or air flow with in a building or room


Equivalent to 7kw or 35square cm?

What's the difference between Net and Gross?

Nett is the actual usable heat.

How do you convert Gross to Nett?

Divide by 1.11


see the worked example in hints.

27kw gross boiler


27 divided by 1.11 = 24.32kw

DFE fires require what ventilation if instructions don't specify?

100cm' to the outside.

DFEs in excess of 20kw need a vent sized at 50% of the chimney throat.

An open Flued appliance not exceeding 7kw needs how much ventilation?

None as this is covered under the adventitious air allowance

What is the ventilation requirements for an open Flued appliance of


21kw nett

70 cm'

21-7=14 14 * 5 = 70

What is the ventilation requirements for an appliance of 21kw gross

59.5 cm'

21 / 1.11 =18.9


18.9 - 7 = 11.9


11.9 * 5 = 59.5

Can a ventilation path go through a bathroom or shower room?

Not allowed.

Can a ventilation path go through a bedroom?

Not permitted if the appliance is over 14kw gross (12.7kw nett) or not fitted with a oxygen depletion device.

To help stop the spread of smoke from a fire at what height should a vent be from the floor?

450mm

An oven in a room between 5 to 10 cube Mts, with door to outside requires what size free vent

None


But must have openable or equivalent to outside.

An oven in a room 5 to 10 cube Mts without a door to the outside. Vent required?

50 square cm and an operable window

Instantaneous water heater max 12kw gross in a room of less than 5 cube Mts requires how much ventilation

Not permitted.


5 to10mts needs 100cm' + window


10 to 20 Mts needs 50cm' + window


Over 20mts cubed only a window