Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
41 Cards in this Set
- Front
- Back
- 3rd side (hint)
How long is hose tested for?
|
5 min
|
|
|
HOSE testing at 300 psi
|
super inch
1 3/4 2 1/2 |
|
|
HOSE testing at 200 psi
|
1" and 1 1/2" forestry single jacket
|
|
|
what is testing psi for 5"
|
185 psi
|
|
|
Hose testing basic ops procedures
|
1. no more than 300'
2.close all nozzles and tighten leaking couplings 3.gradually raise by 50lbs 4.hose records on FS-4 |
|
|
Annual Hydrant Testing
|
annually
2" straight and curved pipe pitot gauge hose bib connection and guage hydrant cap and guage hydrantwrench field flow worksheet - FS 28 |
|
|
Hydrant flow equation
|
HF = (square root of) (S)- 20
________ (s-R) x GPM s=static r=residual |
|
|
dry vacuum test - vacuum shall not drop more than
|
10 in Hg in 5 min
|
|
|
priming test and warm up - primer should be no longer than ___ for pump 1500gpm and ___ for pumps >1500gpm
|
30 sec and 45 sec
|
|
|
capacity test - readings taken every
|
5 min for 20 min - never used auxiliary cooler to keep engine temp within normal range
|
|
|
relief valve test - maintain ___ psi - between ___ and ___ seconds
|
150psi and 3-10 seconds. rise in discharge pressure shall not exceed 30 psi - also test at 90 psi and 250 psi
|
|
|
overload test
|
test pumpers reserve power. 100% capacity at 165psi
|
|
|
200 psi test
|
70& at 200psi - 10 min test, 5 min intervals
|
|
|
on air cylinder station, check moisture monitor for
|
Should be blue, if 90 or 100 section is white, do not use compressor.
|
|
|
set carbon monoxide monitor at filling station to
|
to half green and half red
|
|
|
high low pressure selector valve should be set at...
|
2400 PSI at selector valve and 2200 PSI at regulator. For high pressure cylinders set the charge selector valve to 4500 PSI and regulator to 4500 PSI
|
|
|
Open the charge control valve(s) approximately on air fill station
|
1/8 turn
|
|
|
pist-n-lube
|
Mix 2 ox. of Pist-N-Lube (the entire plastic container) with one gallon of gasoline.
Every 60 days |
|
|
Radiological meters
|
Santa Clara County Civil Defense recently designated twenty-two (22) locations as Radiological Monitoring Stations
|
|
|
Circul-Air Hose Dryer
|
DL555, 220-volt electric heat drying time is approximately 12 hours. Each dryer will hold 10 lengths of fire hose.
|
|
|
wildland helmet headlamp
|
HL-4AA that has a shatter-proof lens, which can be adjusted from a spot to a flood pattern. The Headlite is equipped with two bulbs, one is a spare that is stored in the lens shell. The bulb is rated at 5 volts.
|
|
|
electric smoke ejector
|
The fan operates at:
3200-5200 CFM 1/3 HP 2000 Watts start – 700 Watts run 115 – 230 V OPERATING PROCEDURE: |
|
|
Tempest “Ventmaster” Ventilation Chain Saw
|
power plant Husquvarna 371XP. 4.3 cubic inch engine 1.63 pints of 2-stroke fuel. automatic bar oiling. 0.89 pints of bar oil. 15 lbs. with fuel and oil. Champion RCJ7Y spark plug .020. 20 inch Titanium bar and carbide chain, the “Raptor”.
|
|
|
depth gauge should be set to
|
1/4 to 3/8 inches
|
|
|
sawzall
|
a.Wood Cutting Blades (6 inch):
Ab. ll Purpose Blades (3-4 inch): Scroll-cutting metal 1/8” through 3/16”. c. Wood/Metal Cutting Blades (8-12 inch): d. Metal Cutting Blades (6 inch): Metal 3/16” through 3/4”, . |
|
|
floating pumps
|
The Waterous “Floto-Pump” uses a float type throttle
The Hale “Fyr-Flote” uses a pressure activated throttle control, |
|
|
The Hurst model JL32B “Jaws of Life”
|
hydraulic rescue tool gives between 12,000 – 18,000 pounds of working force at the tips
Opens to 32” at tips Closing pressure 18,700 pounds Width of unit 15” Weight 72 pounds with fluid and connectors |
|
|
HURST TOOL CUTTERS MODEL JL-90
|
Cutting force – 15 tons
Weight – 33 lbs. Opening at tip – 4” Length – 30” Width – 11 ½” Height – 11” Opening/closing time – 5.0 seconds |
|
|
HURST TOOL RAMS MODEL JL-20A, JL-30A, JL-60A
|
model/ open L/ closed L / open F / closed F / weight
1. 20 28” 14 ½” 15,000 lbs 7,000 lbs 18 ½ lbs 2. 30 36.62” 22.92” 15,000 lbs 7,000 lbs 31 lbs 3. 60 62.72” 36” 15,000 lbs 7,000 lbs 44 lbs |
|
|
barry marchisio channel block tool
|
The block assembly is a piece of 4” channel, about 24” long, with a 6” leg welded on one end. There are also two small “steps” which are double gusseted and welded on the main leg of the channel.
|
|
|
air chisel operating procedures
|
1. Body metals such as doors and panels: 90-100 psi
2. Heavy, thick metals such as frames, posts, locks bolts: 250 psi Lower pressures will use less air, e.g., at 90 psi operating pressure, an air cylinder will last approximately 4 minutes |
|
|
lockout tagout kit
|
bleed down hyd system or air sys
One crescent wrench Three 1 ½” diameter hasps Five vinyl lockout tags One pad of safety lockout checklist forms Three keyed-alike locks One voltage indicator with instructions |
|
|
thermal imaging camera
|
SPECIFICATIONS: Bullard Model T3 Max
Weight with battery: 2.7 LBS Power Source: NiMH Rechargeable Battery Battery Life: Up to 2.5 hours (varies) Display Size: 3.5 Diagonal LCD |
|
|
co2 trailer
|
100' hose
extinguishers are only effective from 3 to 8 feet after 3 or more cylinders are empty, take out of service and send to Ace Fire Equipment located at 1870 W Bayshore Road in East Palo Alto |
think about 100 years before my birthday
|
|
v-watch
|
Line to Ground Voltage 1st Warning Distance
120V 3 ft. (0.9 m) 277V 4 ft. (1.2 m) 480V 6 ft (1.8 m) 2,400V 14 ft (4.3 m) 7,200V 20 ft (6.1 m) 14,400V 28 ft (8.5 m) 19,900V 30 ft (9.1 m) |
|
|
cellar nozzle
|
Akron Model 535: 2 ½” Bresnan revolving nozzle, 9 vari-angular discharge ports, three of 3/8” and six of 13/32”, at 100 PSI nozzle pressure will deliver 280 GPM.
1. Lower to floor below, then retract the hose approximately 5’. 2. Lower the nozzle approximately 3’ through floor opening. |
|
|
TFT handline nozzles
|
TFT has six indent positions on the flow control value.
1 ½” lines will vary from 50 – 150 GPM: 1 ¾” hose will increase the available flow up to 250 GPM. For obtaining the full 50 – 350 GPM flow of a TFT, 2 ½” hose is used. |
|
|
TFT master stream nozzles
|
MTFT is a constant pressure variable flow automatic nozzle that operates on the principal very similar to that of a pumper relief valve.
The baffle at the front of the nozzle moves to vary the discharge opening of the nozzle. In effect, the nozzle is constantly changing the tip size to match the flow of the water that is being delivered. |
|
|
Akron Apollo Style Monitor
|
1. Lift off portion weighs 22 lbs.
2. Lift off portion and base weighs 45.5 lbs. 3. Pyrolite construction. 4. Multiple application comes with ground base and direct mount for portable and deck operation. designed to stop at 35° above the horizontal should not be operated at more than 500 GPM with one hose line and 800 GPM with two hose lines. (When used in the direct mount unit, it may be operated at up to 1200 GPM. However, this function is not used by PAFD.) |
|
|
Loading 2 ½” Hose Bed
|
All even layers (2nd, 4th, etc) should be folded 6-10” shorter than normal, both front and rear.
Position the female hose coupling in the right rear corner of the hose bed, facing out, with only the swivel extending past the hose bed enough to turn |
|
|
Utility 2 (#6185)
|
tow or move the many PAFD trailers
1999 Ford F550 4WD super duty GVWR - 17500lbs. 38 gals 8 feet wide 21 ft. 4 in The fuel safety shut-off switch is located behind the passenger foot well kick panel. max towing speed 55mph warn M12000 - 125' cable The liftgate is rated at 2000 pounds |
|