What is the function of the Closed Cooling Water System?
Remove heat generated in components located in the Turbine Building and transfer the heat to the Service Water System.
What chemicals are added to the Closed Cooling Water System?
Sodium Molybdates to maintain a passive film on piping. Sodium Tolytriazole is used as a copper corrosion inhibitor.
The function of the Closed Cooling Water surge tank is to:
Provides expansion and contraction of the cooling water and provides for leakage from the system and makeup.
Where is the Closed Cooling Water System pump and heat exchangers physically located?
Turbine building 2000' elev., north end.
Question: Which components of the Main Generator System does the Closed Cooling Water System cool?
Answer: Generator exciter and isophase bus duct cooler.
Temperature control valve, EB TV-9, loses its instrument air supply. What happens to the valve and system flow?
EB TV-9 fails closed sending full system flow through the heat exchangers.
Can leakage from the Closed Cooling Water System be discharged directly to the environment without contacting the Chemistry Department?
No. Due to chemical treatment, liquids lost from the system during seal leakage, draining, and venting shall be collected and disposed of according to Chemistry Department instructions.