  • Front
  • Back

What are the power supplies for the Spent Fuel Pool and Refueling Water Purification Pumps?

North Spent Fuel Pool Pump - 11C


Sout Spent Fuel Pool Pump - 21C


RWPP - 11D

Spent Fuel Pool Pump Trips



RWPP Trip

1. Load shed


2. Load conservation


3. Overload/Overcurrent



1. Load Conservation


U1 is in a refueling outage in Mode 6 during core offload. SFP Boron concentration is 2300 ppm. What is required?

TS 3.7.15 - with SFP boron concentration less than 2400 ppm, suspend fuel movement and restore boron IMMEDIATELY OR performa a SFP verification IMMEDIATELY.

Design requirements in TS 4.3.2 ensure what SFP parameters are being maintained?

1. keff less than/equal to 0.95


2. Drainage of the SFP does not exceed 629'4"

How many trains of Fuel Handling Air Exhaust Ventilation is required to be in service during fuel movement?

TS 3.7.13 - 1 train shall be operable and in operation. If inoperable, suspend fuel movement IMMEDIATELY.

TS 3.7.14 ensure there is > 23 feet over irradiated fuel in the SFP at all times. What is the bases for this TS?

Min water level meets the assumptions of iodine DF following a fuel handling accident. 2 hour thyroid dose per person at the site boundary is < 10 CFR 100 limits.

Match the following:


Region 1 High burnup fuel


Region 2 Intermediate burn up fuel


Region 3 New fuel

Region 1 - New fuel


Region 2 - High burnup fuel


Region 3 - Intermediate burn up fuel

Following a U1 entire core offload, it was determined that enrichment of a fuel assembly stored in a Region 2 (or Region 3) rack is not within limits of Table 3.7.16-1. What actions are required?

Move offending fuel out of region 2 (or 3) IMMEDIATELY.

What is the limit of ppm boron during refueling canal activity while connected to the RCS?

TS 3.9.1


> 2400 ppm - if less than 2400 ppm, suspend canal activity and restore boron concentration IMMEDIATELY.

One loop of SFP cooling can maintain ________ assemblies at < ________ degrees F with a max time to boil of ________ hours.

3420 assemblies (3613 with core offload)


160 (180)


5.8 hours

The Refueling Water Purification Pump can take suction on what three sources?

1. Spent fuel pool.


2. Either unit RWST.


3. Either unit's refueling cavity.

What is the major difference between the units to ensure RWST Temperatures are maintained within limits?

U1 has heat trace.


U2 has two heaters and a recirc pump.

U1 has just received a Phase A signal. What automatic actions will follow?

CCW to the SFP Hx isolates via CCR-445.

Helium provides what three advantages for dry cask storage?

1. Cooling via natural circulation


2. Inert - prevents chemical reactions.


3. Leak testing.

The MPC base plate, shell, lid, and closure ring are all components of what?

Confinement barrier

10 CFR 72.75 report ability requirements for a damage to a confinement boundary is:

Emergency declaration per the Emergency Plan within 1 hour.

COC ISFSI Modes of Operation include:

1. Loading


2. Transport


3. Storage


4. Unloading

COC LCO requires cask duct temperatures to be less than or equal to 155 deg F. What action(s) are required if this is exceeded?

If inoperable, measure dose rates IMMEDIATELY.

ISFSI Dose limits are:

25 mRem/yr for ISFSI operations.



5 Rem/yr (1 cask) - DBA