Who performs a 3rd reinspection?
an officer responsible for writing citations (inpectors)
If there are still code violations after the 2nd reinspection of a premises, what is the next step of action
- review this occupancy with your Battalion chief

- shedule a 3rd reinspection
What is a class 1 standpipe system
a dry system
What is a class 2 standpipe system
a wet system
What is a class 3 standpipe system
a combination wet standpipe system
If there is more than one standpipe for the building or complex, what do you need to determine
if they are cross connected
When is it prudent to contact an arson investigator Post - incident
when a response to the fire scene will not be warranted (minor fires of suspicous nature)
When responding to suspicious fires keep your eyes open for the unusual, such as
people leaving the scene (most people gravitate towards a fire)

departing vehicle descriptions or license plates if possible
When performing overhaul on a fire where the cause has not been determined, it is important that
you disturb the scene as little as possible, do not move possible evidence and do not clean out or disarrange the scene
Is it Okay to leave the scene before the fire investigation has been completed or the Arson investigator is on scene?
NO
When instructing a business of evacuation plans, what should we tell them about meeting in a safe location in the event of an evacuation
the place should be away from major building access routes and safe from falling glass or debris
How many days after a complaint is filed does the BFP inspector have to investigate
7 days after the date recieved
What should the time limit be for owners to comply with extinguisher and trash violations
7-15 days
The owners are responsible to provide and maintain smoke detectors in which types of occupancies
- condos and town houses
- apartment houses
- hotels/motels
- any other dwelling unit used for sleeping
The owners are responsible to provide the smoke detector, but the tenant is responsible to maintain the smoke detector in which types of occupancies
- single family homes
- duplexes
- mobile homes
Where are smoke detectors supposed to be mounted
on the ceiling or on the wall within 12" of the celing
When inpecting sprinkler and standpipes, what is very important to know when we inspect the operation of any valve or moving part of the system
These parts are to be inspected by the building occupant or owner to protect the FD from liability
How often is a sprinkler/standpipe system required to go through a performance test
every 5 years
If there is more than one standpipe within the building, we check to see if they are ___
cross connected
When we have the owner open the inpectors test valve, what should happen if the system is working correctly
we should hear the alarm sound within 90 seconds
When the owner opens the 2 inch drain valve wide open, residual pressure should generally not be less than ___
80 percent of static pressure
How close to sprinkler heads are stock piles allowed to be that are less than 12 feet high
no closer than 18 vertical inches to sprinkler heads
How close to sprinkler heads are stock piles allowed to be if they are over 12 feet high
no closer than 36 vertical inches to sprinkler heads
Walls should not be more than approximately ___ from a sprinkler measured at a right angle with the wall
7.5 feet
Who can test, service or charge fire extinguishers
ONLY those with a certificate of registration issued by the state fire marshal pursuant to this chapter expressly authorizing such person to perform such acts
Spark arresters shall be constructed of ___
Metal
Spark arresters shall be between ___ and ___ mesh screens
3/8" and 1/2" screens
Spark arresters must have a screen surface area that is ____
4 times the size of the chimney opening