Who performs a 3rd reinspection?
|
an officer responsible for writing citations (inpectors)
|
|
If there are still code violations after the 2nd reinspection of a premises, what is the next step of action
|
- review this occupancy with your Battalion chief
- shedule a 3rd reinspection |
|
What is a class 1 standpipe system
|
a dry system
|
|
What is a class 2 standpipe system
|
a wet system
|
|
What is a class 3 standpipe system
|
a combination wet standpipe system
|
|
If there is more than one standpipe for the building or complex, what do you need to determine
|
if they are cross connected
|
|
When is it prudent to contact an arson investigator Post - incident
|
when a response to the fire scene will not be warranted (minor fires of suspicous nature)
|
|
When responding to suspicious fires keep your eyes open for the unusual, such as
|
people leaving the scene (most people gravitate towards a fire)
departing vehicle descriptions or license plates if possible |
|
When performing overhaul on a fire where the cause has not been determined, it is important that
|
you disturb the scene as little as possible, do not move possible evidence and do not clean out or disarrange the scene
|
|
Is it Okay to leave the scene before the fire investigation has been completed or the Arson investigator is on scene?
|
NO
|
|
When instructing a business of evacuation plans, what should we tell them about meeting in a safe location in the event of an evacuation
|
the place should be away from major building access routes and safe from falling glass or debris
|
|
How many days after a complaint is filed does the BFP inspector have to investigate
|
7 days after the date recieved
|
|
What should the time limit be for owners to comply with extinguisher and trash violations
|
7-15 days
|
|
The owners are responsible to provide and maintain smoke detectors in which types of occupancies
|
- condos and town houses
- apartment houses - hotels/motels - any other dwelling unit used for sleeping |
|
The owners are responsible to provide the smoke detector, but the tenant is responsible to maintain the smoke detector in which types of occupancies
|
- single family homes
- duplexes - mobile homes |
|
Where are smoke detectors supposed to be mounted
|
on the ceiling or on the wall within 12" of the celing
|
|
When inpecting sprinkler and standpipes, what is very important to know when we inspect the operation of any valve or moving part of the system
|
These parts are to be inspected by the building occupant or owner to protect the FD from liability
|
|
How often is a sprinkler/standpipe system required to go through a performance test
|
every 5 years
|
|
If there is more than one standpipe within the building, we check to see if they are ___
|
cross connected
|
|
When we have the owner open the inpectors test valve, what should happen if the system is working correctly
|
we should hear the alarm sound within 90 seconds
|
|
When the owner opens the 2 inch drain valve wide open, residual pressure should generally not be less than ___
|
80 percent of static pressure
|
|
How close to sprinkler heads are stock piles allowed to be that are less than 12 feet high
|
no closer than 18 vertical inches to sprinkler heads
|
|
How close to sprinkler heads are stock piles allowed to be if they are over 12 feet high
|
no closer than 36 vertical inches to sprinkler heads
|
|
Walls should not be more than approximately ___ from a sprinkler measured at a right angle with the wall
|
7.5 feet
|
|
Who can test, service or charge fire extinguishers
|
ONLY those with a certificate of registration issued by the state fire marshal pursuant to this chapter expressly authorizing such person to perform such acts
|
|
Spark arresters shall be constructed of ___
|
Metal
|
|
Spark arresters shall be between ___ and ___ mesh screens
|
3/8" and 1/2" screens
|
|
Spark arresters must have a screen surface area that is ____
|
4 times the size of the chimney opening
|