WHAT IS THE PRESSURE LIMITATION FOR OPENNING THE 202-4A/B VALVE? (RECIRC SUCTION VALVE)

< 50 PSID

WHAT IS THE PRESSURE LIMITATION FOR OPENING THE 202-5A/B VALVE? (RECIRC DISCHARGE VALVE)

<200 PSID

HOW FAR OPEN MUST A RECIRC SUCTION VALVE BE BEFORE THE PUMP TRIPS?

90%

WHAT IS RECIRC PUMP MINIMUM SPEED?

32% BY PROCEDURE



CAPABLE OF AS LOW AS 20%

WHAT IS THE RECIRC-FEEDWATER FLOW INTERLOCK?

20% FW FLOW IS REQUIRED TO RAISE RECIRCS ABOVE MIN SPEED



IF FW FLOW DROPS BELOW 20% FOR 15 SECS, RECIRCS RUN BACK TO MINIMUM

WHAT RECIRC SEAL PRESSURES WOULD YOU EXPECT AT 900 PSIG RX PRESSURE?

SEAL 1 - 900 PSIG



SEAL 2 - 450 PSIG

WHERE DOES RECIRC PUMP SEAL LEAKOFF GO?

DWEDS

WHAT IS THE D/P REQUIREMENT FOR STARTING A RECIRC PUMP?

RECIRC PUMP D/P MUST BE <4 PSID TO START A RECIRC PUMP



AFTER PUMP START, D/P MUST INCREASE TO > 4 PSID (30 SECS)

WHAT IS THE SETPOINT FOR THE RELIEF VALVE ON RECIRC SEAL INJECTION?

1300 PSIG

IF THE OUTBOARD RECIRC SEAL READS LOW, WHAT ARE THE POSSIBLE CAUSES?

FAILURE OF THE OUTBOARD SEAL



PLUGGED INBOARD RESTRICTING ORIFICE

WHAT ARE THE RBCCW LIMITS TO PROTECT THE RECIRC PUMPS?

IF EITHER SEAL TEMP REACHES 200F, TRIP PUMP



IF COOLING WATER TEMP (OUTLET) REACHES 170F, TRIP PUMP



RBCCW FLOW LOST:


TRIP THE AFFECTED PUMP(S) WITHIN 1 MINUTE

WHAT IS THE MAXIMUM WINDING TEMPERATURE OF THE RECIRC PUMP MOTORS?

248 F

WHAT IS THE PREFERRED METHOD FOR TRIPPING A RECIRC PUMP?

CLOSE THE 202-5A/B



PUMP WILL TRIP AT 90% OPEN



RE-OPEN VALVE AFTER 5 MINUTES

WHEN IS THE RECIRC PUMP DISCHARGE VALVE OPENED?

1) 5 MINUTES AFTER PUMP TRIP



2) WITHIN 2 MINUTES AFTER PUMP START

WHAT WOULD BE SEEN IF THE RECIRC PUMP WERE OPERATING UNDER RUNOUT?

HIGH PUMP CURRENT



HIGH WINDING TEMPERATURE

WHAT IS THE POWER SUPPLY FOR THE ASD COOLING WATER PUMPS?

MCC 15-1 / MCC 17-2



NORMALLY A/B PUMP, RESPECTIVELY

WHAT COOLS ASD COOLING WATER?

SERVICE WATER

AT WHAT PRESSURE WILL THE ASD COOLING SYSTEM RELIEF VALVE LIFT?

125 PSIG

WHAT POWERS THE ASD UPS?

15-1 (A)



17-2 (B)



EITHER UPS CAN SUPPLY EITHER/BOTH ASD'S

WHICH RECIRC RUNBACK SIGNALS WILL TRANSFER RRCS FROM MASTER TO MANUAL CONTROL?

ALL OF THEM

WHAT IS THE EFFECT OF A RECIRC DEMAND VS ACTUAL SPEED MISMATCH?

IF ACTUAL SPEED AND DEMANDED SPEED DEVIATE BY 15% FOR 35 SECONDS, A SPEED HOLD IS PLACED

WHAT TWO THINGS INITIATE THE 70% RUNBACK?

1) <3 PUMPS RUNNING, TRIP SIGNAL EXISTS, STEAM FLOW>85%, AND RX LVL <26" WITHIN 45 SECS



2) < 4 CONDENSATE PUMPS RUNNING, > 85% STEAM FLOW, >90% FW FLOW

WHAT IS THE REQUIREMENT FOR RECIRC LOOP DELTA-T?

MUST BE WITHIN 50F WHEN OPERATING OR STARTING A PUMP

WHAT ARE THE RECIRC PUMP TEMPERATURE ALARMS?

120F COOLING WATER TEMP (RBCCW OUTLET FROM SEALS / OIL COOLERS)



200 F THRUST BEARING OR UPPER/LOWER BEARING TEMP



248F MOTOR WINDING

WHAT IS THE RECIRC PUMP MOTOR AMP LIMIT?

770A

WHAT IS THE LOW ALARM SETPOINT FOR ASD COOLING FLOW?

90 GPM



(NORMAL 130-180)

WHAT GENERATES THE RECIRC LOOP HI TEMP ALARM?

> 555F

HOW DOES A LOCA SIGNAL IMPACT THE RECIRC PUMPS?

-59" OR 2.5# INITIATES LPCI LOOP SELECT.



LPCI WILL CLOSE THE DISCHARGE VALVE OF THE INTACT LOOP, WHICH TRIPS THE PUMP (ASD INPUT BREAKER)



BOTH PUMPS TRIP AT -59" FOR NPSH CONCERNS

WHAT ARE THE TEMPERATURE REQUIREMENTS FOR STARTING A RECIRC PUMP?

<50F LOOP DIFFERENTIAL TEMP



<145F BETWEEN STEAM DOME AND BOTTOM HEAD DRAIN LINE

WHERE DOES SDC TAKE SUCTION AND INJECT?

SUCTION - B RECIRC LOOP



INJECT - EITHER A OR B LOOP

WHERE DOES RWCU TAKE SUCTION FROM?

B RECIRC LOOP

WHAT IS THE MAKEUP SOURCE FOR ASD COOLING WATER?

CLEAN DEMIN

WHAT IS FED BY MCC 15-1 / 17-2 FOR ASD'S?

COOLING WATER PUMPS


PRECHARGE CIRCUIT


CABINET COOLERS


CONTROL POWER UPS

ON AN ESS FAILURE, WHAT IS LOST IN THE RECIRC SYSTEM?

1 SUPPLY TO THE RRCS CONTROL SYSTEM


LOSS OF RUNBACK PUSHBUTTON


LOSS OF RUNBACK RESET PUSHBUTTON


LOSS OF 70% RUNBACKS

WHAT SUPPLIES POWER FOR THE RECIRC MOV'S?

18/19-5

WHAT IS AFFECTED IN RECIRC BY A LOSS OF 125 VDC?

INPUT BREAKER CONTROL POWER



AOV'S FOR SAMPLING



MOTOR MANAGEMENT RELAYS



OVERFREQUENCY RELAYS

HOW DOES A LOSS OF INSTRUMENT BUS AFFECT THE RECIRC SYSTEM?

1 POWER SUPPLY TO RRCS



LOSS OF SPEED HOLD AT -4 PANEL



LOSS OF SPEED HOLD RESETS AT -4 PANEL

WHEN DOES THE RECIRC SEAL LOW FLOW ALARM ACTUATE?

20 GPM

WHAT IS THE PRESSURE SETPOINT FOR THE LOSS OF ASD COOLING ALARM ACTUATE?

30 GPM

WHAT ARE THE RESULTS OF RISING SCRAM DISCHARGE VOLUME LEVEL?

10 GAL - ALARM



25 GAL - ROD BLOCK



40 GAL - SCRAM

WHAT ARE THE IMMEDIATE ACTIONS WHEN A CONTROL ROD IS DISCOVERED STUCK?

VERIFY SEPARATION CRITERIA

HOW MANY CONTROL RODS ARE ALLOWED TO BE SLOW?

12

HOW MANY CONTROL RODS ARE ALLOWED TO BE OUT OF SERVICE (INOP)?

8

WHEN IS THE LCO FOR ROD OPERABILITY APPLICABLE?

MODES 1 AND 2

WHEN IS THE LCO FOR ROD PATTERN CONTROL APPLICABLE?

MODES 1 + 2, WITH CTP < 10%

HOW MANY SLOW CONTROL RODS MAY BE ADJACENT?

NO MORE THEN 2OPERABLE CONTROL RODS THAT ARE SLOW SHALL OCCUPY ADJACENT LOCATIONS

WHEN IS THE LCO FOR CONTROL ROD ACCUMULATORS APPLICABLE?

MODES 1 + 2

WHAT IS THE SURVEILLANCE REQUIREMENT FOR CONTROL ROD ACCUMULATOR OPERABILITY?


>940 PSIG

MULTIPLE CONTROL RODS ARE LOSING ACCUMULATOR PRESSURE. REACTOR PRESSURE IS 900 PSIG. WHAT IS REQUIRED?

1) RESTORE/VERIFY CHARGING WATER HEADER IS >940 PSIG (20 MINUTES)



2) DECLARE THE ROD(S) SLOW OR INOP (1 HOUR)



IF ACTION NOT MET OR CANNOT BE MET - MODE SWITCH TO SHUTDOWN IMMEDIATELY


MULTIPLE CONTROL RODS ARE LOSING ACCUMULATOR PRESSURE. REACTOR PRESSURE IS UNDER 900 PSIG. WHAT IS REQUIRED?

1) RESTORE/VERIFY CHARGING WATER HEADER IS >940 PSIG (IMMEDIATELY)



2) DECLARE THE ROD(S) INOP (1 HOUR)



IF ACTION NOT MET OR CANNOT BE MET - MODE SWITCH TO SHUTDOWN IMMEDIATELY

WITH THE UNIT <10% POWER, IT IS DISCOVERED THAT THE CURRENT ROD PATTERN VIOLATES THE ANALYZED STARTUP SEQUENCE. NINE CONTROL RODS WERE WITHDRAWN TOO EARLY. WHAT ACTION IS REQUIRED?

IF NINE OR MORE OPERABLE CONTROL RODS ARE NOT COMPLYING WITH THE ANALYZEDRO SEQUENCE:



1) STOP ROD WITHDRAWALS (IMMEDIATE)



2) MODE SWITCH TO SHUTDOWN (1 HOUR)

WHAT DOES THE BLUE LIGHT ON THE -53 PANEL MEAN FOR HWC?

ALL TRIP CONDITIONS HAVE CLEARED



20 MINUTE RESTART TIMER HAS TIMED OUT



O2 AND AIR FLOW ARE ZERO

WHAT DOES THE AMBER LIGHT ON THE -53 PANEL MEAN FOR HWC?

HWC SYSTEM IS SHUTDOWN DOE TO TRIP (AUTO OR MANUAL)

WHAT IS THE ALARM SETPOINT FOR HIGH OFFGAS H2 CONCENTRATION?

2%



WHAT IS THE NORMAL SETPOINT FOR THE AUTOCLAVE TEMPERATURE CONTROLLER?

135F

WHAT IS THE ALARM SETPOINT FOR HIGH H2 FLOW RATE?

20 SCFM



ALARM ONLY

WHAT IS THE ALARM SETPOINT FOR HIGH AREA H2 CONCENTRATION?

10% OF LEL = ALARM



20% OF LEL


(HWC TRIP)


(ALSO CLOSES HSIV)

WHAT ARE THE TRIPS FOR HYDROGEN WATER ADDITION?

MANUAL TRIP (HMI, -83 PANEL, PUSHBUTTON)


REACTOR SCRAM


AREA CONCENTRATION >20% LEL


LOW H2 FLOW (<1.25 SCFM FOR 45 SECS)


MAIN STEAM FLOW <5% AFTER BEING:


>25%, OR


>20% FOR ONE HOUR


EFCV -4 CLOSURE (@ TANK FARM)

WHAT IS THE ALARM SETPOINT FOR LOW O2 OFFGAS CONCENTRATION?

<5% EXCESS O2 AT THE H2/O2 ANALYZER



ALARM ONLY

HOW IS O2 CONTROLLED AFTER A HYDROGEN ADDITION TRIP?

HOLDS O2 FLOW CONSTANT FOR 15 MINUTES



RAMPS TO ZERO FLOW FOR ADDITIONAL 5 MINUTES

WHAT ARE THE SETPOINTS FOR THE EXCESS FLOW CHECK VALVES?

HYDROGEN


-4 @ TANK FARM


-9 @ T-1



OXYGEN


-33 @ @ TANK FARM



ALL 180-220 SCFM

WHAT IS THE PURPOSE FOR THE HYDROGEN INJECTION SOLENOID ISOLATION VALVES?

PREVENTS H2 FROM BEING DRAWN BACK INTO THE CONDENSER THROUGH OFFLINE CONDENSATE PUMP ANTI-SYPHON LINE

IF STEAM FLOW DROPS <5% BEFORE OPERATING AT HIGH POWER DURING STARTUP, HOW DOES HYDROGEN INJECTION RESPOND?

FCV'S CLOSE AND HISIV'S CLOSE



CONDITION RESETS ABOVE 20% STEAM FLOW AND INJECTS IF IN AUTO/START

WHAT OCCURS ON A HWC TRIP?

FCV'S CLOSE


HISIV'S CLOSE


20 MINUTE RESTART TIMER INITIATES


02 FLOWS FOR 15 MINUTES, THEN RAMPS FOR 5


AMBER TRIP LIGHT ILLUMINATES

HOW IS HWC TRIPPED FROM THE -84 PANEL?

TAKE CONTROL SWITCH FOR HSIV TO CLOSED



HWC TRIPS ON LOW FLOW

WHAT ARE THE SETPOINTS FOR THE H2 PUMPS TO SUPPLY THE 6-PACK?

START @ 700 PSIG



STOP AT 2100 PSIG

WHAT DOES THE SYS ENABLE PUSHBUTTON ON THE -53 PANEL DO FOR HWC?

ENABLES HWC


CLEARS BOTH BLUE AND AMBER LIGHTS



BLUE LIGHT MUST BE LIT FOR RESET

WHAT IS THE INTERLOCK FOR OPENING AN HISIV?

THE ASSOCIATED CONDENSATE PUMP MOTOR MUST BE RUNNING

WHAT IS THE MAXIMUM H2 ADDITION FLOW RATE?

20 SCFM

HOW DOES H2 FLOW RATE VARY WITH POWER?

0-5% STEAM FLOW = NO FLOW


5-25% = 2 SCFM



ONCE OVER 25% FOR 1 HOUR, OR 40%


RAMPS TO FULL SETPOINT AS POWER RISES


(10-11 SCFM)

HOW DOES O2 FLOW RATE VARY WITH POWER?

BASED ON FEEDBACK FROM H2/O2 ANALYZERS



IF <2% H2, SUPPLIES ENOUGH O2 TO SCAVENGE H2



IF H2>2%, INJECTS 9 SCFM O2 TO LOWER H2 LEVEL

HOW LONG IS THE COOLDOWN CYCLE BEFORE AN H2 PUMP STARTS TO SUPPLY THE 6 PACK?

20 MINUTES

WHERE IS HYDROGEN INJECTED INTO THE SYSTEM?

DISCHARGE OF THE CONDENSATE PUMPS

WHERE IS OXYGEN INJECTED INTO THE SYSTEM?

UPSTREAM OF THE SJAE



ALTERNATE FOR U2: AFTER SJAE, BEFORE PREHEATERS

WHEN IS THE TECH SPEC FOR MAIN CONDENSER OFFGAS APPLICABLE?

MODE 1



MODES 2 AND 3 WHEN SJAE IN OPERATION

WHERE IS THE O2 FLOW CONTROL VALVE?

SJAE FLOOR

WHERE ARE THE H2 FCV'S?

CONDENSATE PIT

WHEN IS THE TRM REQUIREMENT FOR EXPLOSIVE GAS <4% APPLICABLE?

DURING OFFGAS HOLDUP OPERATION

WHEN IS THE TRM REQUIREMENT FOR EXPOSIVE GAS MONITORING APPLICABLE?

DURING OFFGAS HOLDUP OPERATION

WHAT IS THE LCO FOR MAIN CONDENSER OFFGAS?

GAMMA ACTIVITY < 251,100 PRIOR TO HOLDUP LINE AFTER 30 MINUTE HOLD

WHAT IS THE NORMAL LEVEL BAND FOR THE H2 TANK?

2.5" - 5.2"

WHAT IS THE NORMAL HYDROGEN SUPPLY PRESSURE?

180 PSIG (IN CONDENSATE PIT)

WHAT IS THE PURPOSE OF NITROGEN IN THE H2 SYSTEM?

PURGE LOCAL CONTROL PANEL


PNEUMATIC CONTROL OF VALVES AT TANK FARM


FIRE SUPPRESSION


LINE PURGING FOR MAINTENANCE

WHAT POWERS THE HWC PLC AND CONTROLS?

COMPUTER UPS

WHAT POWERS COMPONENTS AT THE TANK FARM?

13.8 FROM A CANAL SPRAY HOUSE MCC 42

WHICH AOV'S IN HWC FAIL CLOSED ON LOSS OF INSTRUMENT AIR (OR NITROGEN)?

ALL OF THEM

WHAT IS THE DESIGN BASIS FOR HPCI?

INSURE ADEQUATE CORE COOLING FOR BREAK SIZES LESS THAN THOSE FOR WHICH LPCI OR CORE SPRAY IS NEEDED



NO OFFSITE POWER



NO HOTWELL INVENTORY

WHAT IS THE DESIGN BASIS FOR ADS?

BACKUP TO HPCI TO DEPRESSURIZE THE SYSTEM FOR SMALL BREAKS

WHAT IS THE DESIGN BASIS FOR LPCI?

ONE MODE OF RHR



RESTOR AND MAINTAIN COOLANT INVENTORY AFTER A LOCA TO PREVENT EXCEEDING PEAK CLAD TEMPERATURE LIMITS. 9000 GPM AT 20 PSIG WITH A MIN FLOW VALVE OPEN

WHAT IS THE DESIGN BASIS FOR CORE SPRAY?

PREVENT FUEL CLAD MELTING AS A RESULT OF LOCA ABOVE THE CAPABILITIES OF HPCI. DOUBLE ENDED SHEAR. 4500 GPM PER PUMP AT 90 PSIG

WHAT IS THE PURPOSE OF ECCS KEEP FILL?

TO KEEP LPCI AND CORE SPRAY DISCHARGE LINES FULL OF WATER TO MINIMIZE WATER HAMMER.