How do we prevent THERMAL STRATIFICATION of the PZR Surge Line? |
By limiting the Delta T between the PZR Liquid Space and the Hot Leg to less than 210 DEGREES. - (OP-3C P&L 3.1.5) |
|
According to OP-4C, PRT pressure should NOT be allowed to rise above what pressure, or below what pressure?
|
Should not be allowed ABOVE 75 psig. - Should not be allowed BELOW 1 psig. |
|
Why do we not want a vacuum on the PRT?
|
To prevent drawing Containment Atmosphere (ie Oxygen) into the PRT, which could contain Hydrogen.
|
|
At what pressure does the PRT Rupture Disc rupture?
|
100 psid. - In other words: 100 pounds above Containment Pressure. |
|
What is the interlock associated with RC-527 and the PRT? - What is the reason for that interlock? |
If the PRT pressure rises to 7 psig, RC-527 goes shut. - Prevents over-pressurizing the Vent Header. |
|
What are the Inputs to the PRT?
|
PORV's Safeties RHR Suction Reliefs RHR Discharge Reliefs Letdown Relief (downstream of orifices) Seal Water Return Line Relief SI Test Line Relief RC Gas Vent System |
|
What alarms are associated with the PRT?
|
HI Press (5 psig) HI Temp (125 degrees) HI Level (76%) LO Level (71.5%) |
|
PZR Level is linearly proportional to what?
|
Average Coolant Temperature (between no-load Tave and 577 degrees) |
|
What is the range of PZR level?
|
20% to 47%
|
|
What are the power supplies to the BLOCK VALVES?
|
1(2)B-32 - 1(2)B-42
|
|
What is required to get the LTOP Enabled Red Light lit?
|
Key switch to Enable - Block Valve full open |
|
At what pressure do the PORV's open? |
2335 psig.
|