What is the min height that a vent can terminate above a door or window? |
1 meter |
|
What is the max # of circuit vented branch traps that can be installed between a circuit vent and a relief vent? |
8 traps |
|
Scd 10 is the lightest scd pipe used when victolic grooving True or false? |
true
|
|
The max # of FU that can drain into a vent stack @ the lowest storey is? |
8 FU |
|
A roof that is 900 square meters and smaller needs how many roof drains? |
2 |
|
What is the purpose of a parabolic weir on a storm drainage system? |
Slow down volume of water going through the roof drain |
|
Minimum size of water service pipe for a single family dwelling? |
3/4" |
|
Expansion joints for RWL's must be installed ___________ from the hopper? |
5 ft |
|
What is the minimum and maximum water pressure @ the point of entry into a building? |
Min = 29 psi or 200 kpa Max =80 psi or 550 |
|
Max temp of water discharge from a sterilizer without a requirement for cooling is? |
170 F |
|
The max allowable temp of water to be delivered from a mixing valve is ________. |
- 120 F or 49 C |
|
A temp sensing valve will deliver water @ a max temp of ________? |
120f or 49C |
|
What is the minimum amount of elbows required to make an expansion joint on a RWL? |
2
|
|
Flow control drains may be installed provided: 1.) The max drain down time doesnt exceed __________? 2.) They are located not more then ______ from the edge of the roof and not more then ______ from adjacent drains? |
1.) 24 hours 2.) 15m and 30m |
|
Distance between cleanouts on a 3 or 4" line from two way rodding is? |
30m |
|
What is the max vertical drop for a WC trap arm? |
1M |
|
When testing a water system with air what pressure must be maintained and for how long? |
100 psi for 2 hours |
|
When a water test is required for underground DWV how much ft of head must it be subjected to? |
10 ft of head |
|
According to environment canada, how is a RWL sized? |
Max amount of rainfall recorded over a 25 year period during a 15min period |
|
When is a vent stack required? |
When a soil or waste stack discharged through 5 stories or more |
|
Can you drain into a Yoke vent? |
Yes, must be vertical section of the Yoke vent. Max 2 fixtures connected symmetrically and each fixture doesnt exceed 1.5 FU |
|
Where must a vent stack connect to the soil/waste stack it's serving? What is the minimum size of vent stack? |
Must connect to a vertical section of the soil/waste stack at or immediately below the lowest pipe connect to the stack |
|
A yoke vent need not be installed provided the the soil/waste stack is interconnected with the vent stack in each storey of the section in which fixtures are located by means of a vent pipe equal in size to the branch or fixture drain or 2", whichever is smaller |
2.5.4.3(4) |
|
When is a Yoke vent required? |
When a soil/waste stack goes through 12 stories or more.It's installed every 5 floors starting from the top down. |
|
How do you size a yoke vent? |
One pipe size smaller then the smallest pipe it is connect to |
|
When a soil/waste stack offsets, it requires a offset relief vent when? |
-Nominally horizontal offset more then 1.5 M -Passes through more then 2 storeys -Hydraulic load more then100 FU |
|
A vent stack is required when fixtures discharge from a min of how many stories? |
5 |
|
The size of a vent for a sewage pump is? |
One size small then the largest inlet. atleast 2" but no more then 4"
|
|
How many FU's can drain into a additional relief vent and a circuit vent? |
Max 2 fixtures connected symmetrically not bigger then 1.5 FU each |
|
When should you install a re-circ line? |
Higher then 4 stories or hot line is longer then 30M |
|
Can fixtures with fixture outlet pipes less then 2" connect to the drain portion of a circuit vent? |
Yes, but they must be separately vented or separately circuit vented |
|
What size of flashing is used for a vent on a roof? |
20"x20" |
|
Where must a vent terminate through a roof? |
-Through a residential roof 150mm
- 3.5M away from a air intake and 1M above -3.5M from another building |
|
What is the smallest vent pipe that can penetrate through a roof? |
3" |
|
1 PSI = how many kpa? |
6.9kpa |
|
What application is a turbine meter best suited for? |
Industrial water pumps and equipment |
|
How many check valves does a RP have? |
2 |
|
The atmospheric vacuum breaker shall not be installed where it is under continuous flow for more then ? |
12 hours |
|
An atmospheric vacuum breaker shall be used on ? (severity) |
non lethal and non toxic |
|
A pressure vacuum breaker device shall never be installed lower then_____ above the flood level rim?
|
12" normally used in a supply line to a fixture Check this answer |
|
How many shower heads can a single drain handle on a gang shower? What is the floor graded at? |
Max 6 shower head graded at 1/4" per ft |
|
Legionella thrives in what temperature? |
120F or 49C and lower |
|
Why would you install multiple pressure reducing valves in series? |
To allow for pressure reduction greater then that provided by a single valve not 100% on this answer |
|
Why would you install multiple pressure reducing valves parallel from each other? |
To allow the use of 2 smaller, less expensive valves rather then one large expensive valve |
|
Max temp of sewage or clear water waste drained into a drainage system? |
75 C or 170F |
|
How many check valves does a pressure vacuum breaker have? |
1 |
|
What is the distance required above a double check valve assembly when using a sight tubes for testing? |
3 ft |
|
A wet vent extends through more then 1 storey, the total discharge from any 1 storey above the 1st doesnt exceed? |
4 |
|
What is the min height that a vent could terminate above a balcony?(public use) |
2m(6ft6") |
|
What temp should you set your HWT to? |
140F 60C |
|
What type of backwater valve must be installed on a building drain? Norm open or closed? |
Norm open so there can be free flow of air through the system. |
|
Barrier Free Notes
1.5m radius 470 + or - 10 wall to center of WC 430 + or - 30 floor to seat
|
|
|
What feature on a optimal level allows it to be used for measuring distances? |
Stadia lines |
|
What is the spacing distance for shock absorbers on a battery of fixtures? |
20 ft |
|
What is the min distance a water meter must be from any wall or entrance? |
12" |
|
What temp is water cooled for a drinking fountain |
10C |
|
Weeping tile must rest on what size of rock and by what dimension? |
1" rock 12"x12" |
|
A floor drain can be connected to a storm drain true or false? |
true |
|
A floor drain 3" or bigger must be a min of 18" away from the BD or branch. True or false |
true |
|
One trap may serve a group or floor drains, shower drains, a group of washing machines or a group of lab sinks if the fixtures are in the same room and arent located where they can receive food or other organic matter |
|
|
What is the purpose of the shield on the bubbler on a drinking fountain? |
Prevents contamination of the nozzle |
|
Whats the max amount of FU's that can drain into a relief vent? |
6FU |
|
Thermostat anticipator -The anticipator is wired in series with the thermostat contacts. If the heat anticipator burns out due to a incorrect voltage being applied the circuit is broken |
|
|
Can victaulic be used on copper systems? |
Yes |
|
Max distance a cleanout can be from the base of a soil/waste stack? |
10 ft |
|
A double sanitary tee fitting shall not be used to connect the trap arms of? |
Back outlet WC's |
|
Max directional change for a kitchen sink before a vent has to be installed? |
90 degrees |
|
What is the min. cleanout size for a 8" building sewer? |
Manhole |
|
How many toilets can be wet vented? |
2 |
|
Minimum size of trap for a bidet? |
1 1/4" |
|
Mapp gas uses what 2 types of gas? |
Acetylene and propane |
|
Where would you install a cast iron base meter? |
Where freezing might occur. |
|
Most common type of booster pump? |
Centrifugal pump |
|
All meters need to be grounded. true or false? |
true |
|
State 2 advantages of a electric HWT |
Quiet More choice of location(no flue) |
|
What type of backflow preventer is installed on a flush valve? |
Vacuum breaker |
|
Which family does the fill valve belong to? |
Needle |
|
What is the min. trap seal depth? |
1 1/2" |
|
Floor drains cant be installed in high voltage rooms or anywhere toxic or flammable material is stored. true or false? |
true |
|
What is the min. size of a floor drain? |
2" |
|
Min. trap arm length must be how long? |
2x pipe diameter |
|
A sump pump need 3 fittings in what order? |
Union check valve ball or gate valve remember "U check valve" union closest to pump |
|
When fixtures are below grade what must you install to the drainage? |
Norm closed backwater valve |
|
The pressure vacuum device will or will not be used where it is subject to back pressure? |
will not |
|
Gang showerheads must be no closer then? |
30" |
|
When a offset in a soil/waste stack is great then 1.5 meters, how is it sized? |
as a branch or building drain |
|
What side of a pressure reducing valve would you install a pressure RELIEF valve? downstream or upstream? |
downstream |
|
Is a check valve necessary on a booster pump system? |
yes |
|
A downspout from a ease trough connected to sub soil drainage need a cleanout where? |
12" above grade |
|
What are the 2 methods of expansion on a RWL? |
1.) Expansion joint no more then 5ft from the roof drain(installed on vertical) 2.) 2 90 degree elbows, first one 5ft MAX from roof, 2nd MIN 5 ft on horizontal |
|
Does a RWL need a trap if it's draining into a storm system? |
no |
|
What is the minimum clearance a cleanout needs for service? |
12" |
|
You can run drains and waterlines inside exterior walls. true or false? |
false, only vent lines |