WT1
-High Coolant Temp Switch
-Common housing with WT2, left side engine, black device, by thermostatic housing.

-217+-2 F
-CB101 trip, unit shutdown
Causes:
-Engine overload
-high ambient temp
-high altitude
-restricted air flow
-fault water pump
S13 & S14
-Low Coolant Level Switch
-Upper left side of unit behind lauvers

-S13 is 13 cm below top of radiator
-sets off alarm due to coolant leakage

-S14 is 18 cm below top of radiator
-CB101 trip, unit shutdown due to coolant leakage
OT2
-High Lube Oil Temp Switch
-Left side, left device on lower square heater

-242 to 248 F
-Alarm and light

Causes:
-Low oil level
-high coolant temp
restricted lube oil cooler
OP1 & OP2
-Low Lube Oil Pressure
-Left side, black device at back of engine, common housing

OP2
-Alarm and Light
-39+-2 PSI

OP1
-Unit shutdown
-30+-2 PSI

Causes:
-Low Oil Level
-Broken oil pump
FL3
Low Fuel Level Switch
-Under Control Room floor

-Parameter: 30 gal. Usable fuel left in tank

-Alarm and Light (A9DS5)
-Timed shutdown relay (K23)
-In 35 min, CB101 trip, unit shutdown

Causes:
-Fuel supply not replenished
-Fuel transfer pump off
-Solenoid not working
FL4
High Fuel Level Switch
-Under Control Room floor

-Parameter: 110 gal. Usable fuel left in tank, leaves 2" air gap

-Alarm and Light (A9DS6)

Causes:
-Fuel level switch fails
-Fuel transfer solenoid fails
-Fuel transfer pump "Off" fails
SS1, SS2 & SS3
Speed Switch
-Left side, above PT pump, common housing
-driven off the tachometer drive of PT pump

SS1: 600 RPM
-deenergizes M7 crank timer relay

SS2: 1200 RPM
-Arms K14 Shutdown relay circuit

SS3: 2200 RPM
-Energizes Shutdown relays K19A and K19B
M7
-Cabinet A

Parameters: 4 start attempts (15 sec crank, 15 sec rest)

-Alarm and Light (A9DS13) shutdown and Lockout

Causes:
Engine fails to start
SS3
Overspeed Switch

Parameters: 2200 RPM

-Alarm and light (A9DS1)
-CB101 trips, L2A & L2A Air shutoff trips, fuel cutoff

Reset:
-reset overspeed button
-relatch to the open position the air control valves
-reset the auuniciator panel (must be LAST)
S17
Ether Lockout Switch
-right side, ?

Parameters: 40 F opens it

-Prevents ether injection when coolant temp is above 40 F

-Not use in our applications
S7
Red Push Button
-Control panel C rear or on Remote Control Panel

If pressed while operating

-CB101 trips
-will stop the engine by cutting off air to the turbos (L2A & L2B)
-deenergizing fuel solenoid valve (L1) by disconnecting battery positive from DC Control circuits

Reset:
-Restart unit by resetting air control valves
-Reset Annunciator
Emergency Shut Down Handle
Located on unit skid, left side

-pull to operate which will close fuel valve to engine

Under freq, under volt relays will open CB101 as engine decelerates

Restart:
-reset Annunciator faults
-push handle in