What is required to start a Main Feed Pump?


Switch to Start.


-


Seal Water d/p >30 psid.


-


Discharge MOV full Shut.


-


Suction Pressure >184#.


-


Oil Pressure >10#.


-


No protective relay trips in.


-


Mini-recirc valve full Open.

What Trips the MFP's?


Switch to Stop.


-


Suction Pressure <135# for 2 minutes.


-


Oil Pressure <9# for 1.5 seconds.


-


Safety Injection.


-


Electrical (undervoltage, overcurrent, ground, bus differential).

What are the normal and alternate lube oil pumps for the MFP's?


The Attached Lube Oil Pump is the normal lube oil supply at power.


-


The AC Lube Oil Pump is used for start up and shut down, and starts automatically on low lube oil pressure.


What starts the AC lube oil pump on the MFP?


-


How is it stopped?


Starts at 9# and lowering.


-


With the switch in Auto & LO pressure >18#, taking the switch to TEST stops the pump.

How do the mini-recirc valves react when starting the MFP's?


Operator places the switch in AUTO.


-


Mini-recircs go full open.


-


Operator places switch in START.


-


Mini-recircs then modulate to maintain 4000 gpm.

What normally supplies Seal Water to the MFP's?


Condensate Pumps.

What auto starts the MFP Seal Water Pumps?


Seal Supply <235# starts both pumps.


-


Seal Water Temp >185F starts both pumps.

What auto trips the MFP Seal Water Pumps?

Low Condensate Pressure 125#.