SRM Power Range
10-9 % power to 10-3 % power
IRM Power Range
10-4 % power to 40 % power
LPRM Power Range
10-3 % power to 125 % power
APRM Power Range
0 % power to 125 % power
Rodblock Setpoint & When Bypassed

SRM Upscale
Setpoint - < 1x10-5 CPS

Bypassed
• Any time associated SRM channel is bypassed
• Any time all four associated IRM channels are on Range 8 or above
• Reactor Mode Switch in "RUN"
Rodblock Setpoint & When Bypassed

SRM Inoperative (INOP)
• Channel module unplugged
• Channel Mode Switch (AER) not in "OPERATE"
• Low detector high voltage (<90%)

Bypassed
• Any time associated SRM channel is bypassed
• Any time all four associated IRM channels are on Range 8 or above
• Reactor Mode Switch in "RUN"
Rodblock Setpoint & When Bypassed

SRM Downscale
< 3 CPS

Bypassed
• Any time associated SRM channel is bypassed
• Any time all four associated IRM channels are on Range 3 or above
• Reactor Mode Switch in "RUN"
Rodblock Setpoint & When Bypassed

SRM Not Fully Inserted And Indicating £ 100 CPS
Associated SRM channel count rate
< 100 CPS AND all four associated IRM channels on Range 2 or below

Bypassed
• Any time associated SRM channel is bypassed
• Any time all four associated IRM channels are on Range 8 or above
• Reactor Mode Switch in "RUN"
• Any time associated SRM channel count rate >100 CPS
• Any time all four associated IRM channels are on Range 3 or above
SCRAM Setpoint & When Bypassed

SRM Upscale (High-High)
> 2x10-5 CPS

Bypassed
• When associated shorting links are installed
• Any time associated SRM channel is bypassed
SCRAM Setpoint & When Bypassed

SRM Inoperative (INOP)
Loss of power to associated SRM channel only

Bypassed
When associated shorting links are installed
Rodblock Setpoint & When Bypassed

IRM Upscale
> 85/125

Bypassed
• Any time associated IRM channel is bypassed
• Reactor Mode Switch in "RUN"
Rodblock Setpoint & When Bypassed

IRM INOP
• Channel module unplugged or other hardware failure
• Channel Mode Switch (AER) not in "OPERATE"
• Low detector high voltage (<90V)

Bypassed
• Any time associated IRM channel is bypassed
• Reactor Mode Switch in "RUN"
Rodblock Setpoint & When Bypassed

IRM Downscale
< 5/125

Bypassed
• Any time associated IRM channel is bypassed
• Reactor Mode Switch in "RUN"
• Any time associated IRM channel is on Range 1
Rodblock Setpoint & When Bypassed

IRM Not Fully Inserted
Associated IRM detector not fully inserted

Bypassed
• Any time associated IRM channel is bypassed
• Reactor Mode Switch in "RUN"
SCRAM Setpoint & When Bypassed

IRM Upscale (High-High)
> 120/125

Bypassed
• Any time associated IRM channel is bypassed
• Reactor Mode Switch in "RUN"
SCRAM Setpoint & When Bypassed

IRM Inoperative (INOP)
• Channel module unplugged or other hardware failure
• Channel Mode Switch (AER) not in "OPERATE"
• Low detector high voltage (<90V)

Bypassed
• Any time associated IRM channel is bypassed
• Reactor Mode Switch in "RUN"
PRNMS ROD WITHDRAWAL BLOCK
STP Upscale
(Mode Switch NOT in RUN)
> = 12%

(Reactor Mode Switch not in "RUN")
PRNMS ROD WITHDRAWAL BLOCK
Neutron Flux Downscale
< = 3.2%

(Reactor Mode Switch in "RUN")
PRNMS ROD WITHDRAWAL BLOCK
LPRM Low Count
< 20 per channel
< 3 per axial level
PRNMS ROD WITHDRAWAL BLOCK
Simulated Thermal Power
·         Two Recirc Loop Operation
> = 0.65W + 54.3%

(Reactor Mode Switch in "RUN")
PRNMS ROD WITHDRAWAL BLOCK
Simulated Thermal Power
·         Single Recirc Loop Operation
> = 0.65(W - 7.6) + 54.1%

(Reactor Mode Switch in "RUN")
PRNMS ROD WITHDRAWAL BLOCK
Simulated Thermal Power
·         Clamped
108%

(Reactor Mode Switch in "RUN")
PRNMS ROD WITHDRAWAL BLOCK
Inoperative
Critical self-test fault
Chassis mode switch in "INOP"
Watchdog timer times out
Loss of both power supplies to APRM channel
PRNMS ROD WITHDRAWAL BLOCK
Recirculation Flow Upscale
> = 113.4% (see COLR)
PRNMS SCRAM
Neutron Flux Upscale
(Mode Switch NOT in RUN)
> = 15%

(Reactor Mode Switch not in "RUN")
PRNMS SCRAM
Neutron Flux Upscale
> = 118.3%

(Reactor Mode Switch in "RUN")
PRNMS SCRAM
Simulated Thermal Power
·         Two Recirc Loop Operation
> = 0.65W + 61.7%

(Reactor Mode Switch in "RUN")
PRNMS SCRAM
Simulated Thermal Power
·         Single Recirc Loop Operation
> = 0.65(W - 7.6) + 61.5%

(Reactor Mode Switch in "RUN")
PRNMS SCRAM
Simulated Thermal Power
·         Clamped
116.6%

(Reactor Mode Switch in "RUN")
PRNMS SCRAM
Inoperative
Critical self-test fault
Chassis mode switch in "INOP"
Watchdog timer times out
Loss of both power supplies to APRM channel
PRNMS SCRAM
OPRM
·         Period Based Detection Algorithm (PBDA)
> = 14 counts and > = 1.12 amplitude (see COLR)

Active only when OPRMs are ENABLED:
STP >= 29.5%
AND
Total Recirc Drive Flow < 60%
AND
Reactor Mode Switch in "RUN"
PRNMS SCRAM
OPRM
·         Amplitude Based Algorithm (ABA)
> = 1.30

Active only when OPRMs are ENABLED:
STP >= 29.5%
AND
Total Recirc Drive Flow < 60%
AND
Reactor Mode Switch in "RUN"
PRNMS SCRAM
OPRM
·         Growth Rate Based Algorithm (GRBA)
> =1.30

Active only when OPRMs are ENABLED:
STP >= 29.5%
AND
Total Recirc Drive Flow < 60%
AND
Reactor Mode Switch in "RUN"
"PRNMS ROD WITHDRAWAL BLOCK
APRM Channel Trouble"
< 3 LPRM detector input signals per axial level
< 20 total LPRM detector input signals to associated APRM channel
Any Critical or Non-Critical Self-Test Fault detected in the APRM or LPRM chassis
Loss of either of the redundant power supplies to the APRM channel (*AY185 or *BY185)
PRNMS Alarms
OPRM Alarm
·         Period Based Detection Algorithm (PBDA)
> = 14 counts

Active only when OPRMs are ENABLED:
STP >= 29.5%
AND
Total Recirc Drive Flow < 60%
AND
Reactor Mode Switch in "RUN"
PRNMS Alarms
OPRM Alarm
·         Amplitude Based Algorithm (ABA)
> = 1.20

Active only when OPRMs are ENABLED:
STP >= 29.5%
AND
Total Recirc Drive Flow < 60%
AND
Reactor Mode Switch in "RUN"
PRNMS Alarms
OPRM Alarm
·         Growth Rate Based Algorithm (GRBA)
> =1.20

Active only when OPRMs are ENABLED:
STP >= 29.5%
AND
Total Recirc Drive Flow < 60%
AND
Reactor Mode Switch in "RUN"
RBM Rod Block Setpoint & when Active
LPSP
> 121.5%

When STP% is above 28.1%
AND
Less then 63.1%
RBM Rod Block Setpoint & when Active
IPSP
> 116.5%

When STP% is above 63.1%
AND
Less then 83.1%
RBM Rod Block Setpoint & when Active
LPSP
>=111.0%

When STP% is above 83.1%
RBM Rod Block Setpoint & when Active
Downscale
< 5.0%
RBM Rod Block Setpoint & when Active
INOP
• RBM chassis INOP/OPER Keylock Switch in the “INOP” position
• Number of operating LPRM detectors is less than the required minimum and a control rod is selected
• More than one control rod is selected
• Loss of input power
• Critical self-test fault
• Firmware watchdog timer timed out