|
|
The uniform fire code defines a high-rise as any building over 75’ in height In Tucson a high rise is considered four or more stories in height or 50’ All buildings greater than 50’ in city limits are sprinklered and have standpipes Highest building in Tucson is the UniSource building 330’ with 25 floors City communication may refer to high rise as building 3 Many occupancy types: Hospitals Hotels Apartments Office buildings
|
|
General Design Similarities (8)
|
Beyond reach of aerial equipment Height Building setbacks Unopenable windows Potential stack effect Chimney effect Fire and smoke spread to upper floor Unreasonable evacuation time
|
|
Fire Behavior Fire Load (6)
|
High rise building are not fireproof Many have large open floor areas with a high fire load Flashover potential Usually airtight creating smoldering fires Heat usually contained inside building Window failure can result in exterior fire “Lapping Over”
|
|
|
Access Roadway Doors –key box (knox or supra box) Stairs Elevators Communication Occupant load Construction Utlitlies Fire protection system Alarm systems Sprinkler systems Standpipes Water supply Building engineer/plans
|
|
|
A wet or dry system of piping, valves, outlets, and related equipment designed to provide water at specified pressures and installed exclusively for the fighting of fire Standpipe systems provide a means for the manual application of water to fires in buildings They are designed to provide a quick and convenient means for obtaining effective fire streams in large low building or the upper stories of high buildings. These systems are usually dry and have to be supplies with water by the fire department
|
|
|
Class I intended for FD use, usually dry Standpipe outlet located in stairwells, usually protected by fire resistive construction Class II intended for Occupants use; wet Hose cabinet only Class III intended for both FD and Occupants Both FD hookups and Hose Cabinets
|
|
|
Heavy Streams fire department trained personnel advanced stages of fire 2 1/2" connections every stairway enclosure at every floor above the first story. Each side of horizontal exit wall and adjacent to exit 4" <100' 6">100' 275' max unless pressure regulated 500 gpm first standpipe, 250 gpm each additional up to 2500gpm, 30 minute duration, 65 psi at top outlet w/ 500 gpm
|
|
|
Small streams building occupants incipient fire 1 1/2" connections all portions of each sotry or section within 30 feet of nozzle with 100' of hose 2-inch <50' 2 1/2">50' 100 gpm per building, 30-minute duration 65psi w/ 100gpm from topmost outlet
|
|
Class lll - combination (3)
|
Both Class 1 and 2 Same as Class 1 with added 1 1/2" outs or 1 1/2" adapters and hose Pipe and supply same as class 1
|
|
Fire Department Connections
|
Must indicate intended use Automatic sprinklers Dry standpipes Must have removable or breakable caps in place Multiple inlets usually interconnected Must be accessible to FD Cannot be obstructed
|
|
|
Tell at a glance how many systems Engineers ensure correct systems supplied Allows attack team to correctly ID system and floor level Continue clockwise around building
|
|
Standpipe Connections (Exterior)
|
7 x 7 inch diamond shape First system marked “A” Number indicates how many systems
|
|
Standpipe Connections (Interior)
|
5 x 5 inch diamond shape Letter indicates which system Number placement indicates level above or below ground level Roof outlet will not have a number just a letter For outlets above ground level the number will be placed above the letter For outlets below ground level the number will be placed below the letter The outlet on the roof will identified with letter only. No floor number will be necessary
|
|
|
Lay two 2 ½ lines to the standpipe connections and remove the tips and place on ground under the connections Remove swivel caps from lower, center or any caps if only twoi Check for gasket and observe into coupling for obstructions Missing gasket= unused inlet or nozzle tip
|
|
|
FDC damage or obstructed Go to second floor of riser Use siemese with double female and appropriate fitting to create a temporary FDC Note that E & P states use of wye (TFD has no 2 ½ wye) Secure fittings with rope to riser to prevent weight damage to riser and outlet Remember to open valve
|
|
|
Connects a 2 ½ line to second floor outlet and down to the street Station FF at hose discharge outlet Open outlet gate and drain standpipe Use a plastic or wooden implement to open check/clapper calve and drain remainder of riser
|
|
|
Same priorities as low rise fires L.I.P.
|
|
|
2 battalion chief 4 engine companies Includes RIC 2 ladder companies 2 paramedic units 2 EC Includes RIC 1st company actions will determine direction and outcome Exterior size up Smoke and flame= automatic 2nd alarm Designated level II staging from fire building Ensure adequate water supply Hydrants, sprinklers, FDC connections
|
|
|
1 engine and 1 ladder crew with high rise equipment Enter and obtain information, keys, plans Observe annunciator Bring elevators to lobby Do not use for fires on 6th floor or below Do not use unless absolutely sure combustion by products will not affect elevator operations
|
|
|
Select one stairwell for attack and another for evacuation Proceed to fire floor Give exact location of fire Fire extend and ventilation needs Resources needed Life safety concerns
|
|
|
Ensure not used until evacuation complete if smoke handling capable Sit down if unsure as to use it Notify building engineer asap Oxygen delivered can reinforce fire
|
|
|
Radios- may not work because of construction types Telephones- secure a lobby phone number PA system in building Emergency phone systems Runners simplex channel on radio
|
|
|
Best life safety is aggressive fire attack and ventilation Designate evacuation and firefighting stairwells Consider occupant mobility Move occupants from fire floor Designate elevator monitors Confine occupants to one stairwell if possible Move to 3 floors below fire floor or 10 above, designate as “Safe Refuge” Total evacuation impractical and unnecessary Search and empty rooms should have M-T tags in place on door-knobs or in jamb Designate elevator monitors
|
|
|
Electrical primary energy source Underground vauts could present problems from water drainage Separate power control room Each floor has panel room Use building engineer or TEPCO Protect phone lines if possible
|
|
|
Bring elevators to lobby and shut down all unneeded cars place in fire service mode When used, full scba required plus an extinguisher, handlight and entry tool Up elevator designated as number one to take resources up, look up hoistway for fire Down elevator designate as number two to take resources down Prior to using, note stairwell locations on base (staging) floor Up passengers will be in full PPE Look up shaft for flames or smoke Stop two floors below fire floor after Prevent water in hoistway
|
|
|
Until fire floor is confirmed stairwells will be used Could take as much as 10 – 20 minutes to reach fire floor- pace yourself Use exterior wall of smoke tower when climbing. Smoke will be near center Establish separate firefighting and evacuation stairs Bring door keys and forcible entry tools Use wedges to hold open door Use stop-locks to hold open door latches Use duct tape to hold open door latches Keep all unneeded doors closed as well as those searched Place MT tags where rooms/floors have been searched and found empty
|
|
|
High rise lay Command “high rise lay” Similar equipment as in reverse lay plus 2 hand folds (100’) rappelling bag, extinguisher and high rise pack Scba donned High rise pack Handy folds Connecting to system Fire attack Ventilation Salvage and overhaul
|
|
Position Responsibilities
|
Captain: SCBA, radio, handlight, TIC FF1: scba, hand folds, forcible entry tools, extinguisher FF2: scba, handy folds, high rise pack, rope/ rappelling bag
|
|
|
Wear backpack and mask Slide regulator hose up through shoulder harness. Do not connect Wear scba like this until reaching base staging area below fire floor Wear fully when riding in elevators
|
|
|
Rappelling equipment Hose reducer Door wedge MT tags Spanner wrench Gated wye Sprinkler stops Duct tape Stop lock
|
|
|
One sections 1 ¾ hose folded in a one person fold Bound- to permit easier carrying May use section from wye setup when prepacked handy folds are gone Break coupling at sections and at wye Hold nozzle and female Rotate ½ turn so coupling is on tip
|
|
|
Stage two floors below fire= base Connect to outlet one floor below fire floor Flake hose up stairs from fire floor landing Second hose should flake down stairs to prevent tangling Open outlet and charge line Bleed air prior to entering fire floor Feel floor, open and wedge
|
|
|
Resource intensive 4 crews to use one line Equipment carried to base Backup line RIC line Crew to backup backup line crew Never abandon lines, have crews ready Hose stream should be straight streams when water pressure is low or maximum flow is required Consider hallways, corridors and open areas
|
|
|
Usually horizontal unless on top floor Positive pressure in stairwells following evacuation HVAC only after building engineer notified Glass 2 types: plate and tempered Corners & every 50 linear feet should be tempered and marked as such Break only in coordination with command Perimeter will be established for plate glass debris
|
|
|
water/smoke greatest damage starts floor below fire floor starts asap examine concealed spaces (chases) for fire extension beyond fire floor
|