Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
54 Cards in this Set
- Front
- Back
which of the following two (2) industry codes or standards contain the specific electrical requirements for health care facilities
|
both B and C
- NFPA 70 national electrical code - NFPA 99 standard for health care facilities |
|
Article 517 applies to health care facilities that provide care for humans and animals
|
false
|
|
article 517 in the NEC is made up of how many parts
|
7
|
|
NFPA 99 standard for health care facilities is made up of how many chapters
|
21
|
|
which three (3) chapters of NFPA 99 provide requirements for electrical equipment and systems
|
chapters 4,8, and 19
|
|
part II of article 517 applies to patient care areas of hospitals only
|
false
|
|
in areas of nursing homes and limited care facilities that are used exclusively for patient sleeping rooms, the electrical wiring is permitted to be in a method as described in chapters 1 through 4 of NEC
|
True
|
|
which of the following is not classified as a patient care area
|
business office and corridors
|
|
which of the following provides the minimum dimensions for a patient care vicinity
|
A space in a patient room not less than 1.8 m (6') horizontally from the bed in its nominal location and up to a height of 2.3 m (7 1/2') above the floor
|
|
which of the following is necessary for a building or portion of a building to qualify as a hospital
|
all of the above
- 24-hr use - medical and surgical care is provided - capacity for four (4) or more inpatients |
|
which of the following topics is not covered in chapter 4 of NEPA 99 standard for health care facilities
|
gas system piping requirements
|
|
NFPA 99 standard for health care facilities is intended primarily for which of the following
|
All of the above
- the design, construction, maintenance, operation, manufacturing, and testing in patient care of health care facilities. Address |
|
which of the following is responsible for classification of patient care areas in a hospital
|
The governing body of the facility
|
|
which of the following determines what area of a health care facility provides normal or general patient care and what area provides critical patient care
|
the governing body of the health care facility
|
|
what is one (1) practical method of reducing patient and personnel shock hazards in patient care areas of a hospital
|
Establishing and maintaining low or zero potential differences between exposed conductive surfaces that could become energized in the vicinity of patients
|
|
how much current in Milli-amperes can cause the heart muscle to malfunction and result in ventricular fibrillation
|
above 6 Milli-amperes
|
|
the location of a patient sleeping bed or the bed of a procedure table of a critical care area is defined as
|
a patient bed location
|
|
Electrical wiring systems in hospitals are required to comply with the applicable rules in chapter 1 through 4 of the NEC, except as modified by article 517
|
True
|
|
areas of nursing homes that are used exclusively as sleeping rooms are required to comply with Part II of article 517
|
false
|
|
the conductors between the final overcurrent device protecting the circuit and the outlet best defines which of the following terms
|
branch circuit
|
|
all circuit conductors between the service equipment, the source of a separately derived system, or other power supply source and the final branch-circuit overcurrent device defines which of the following
|
service-entrance conductor
|
|
all ungrounded conductors of mutiwire branch circuits in health care facilities are required to be provided with a means to simultaneously disconnect all ungrounded conductors at the point where the branch circuit originates
|
false
|
|
which of the following are primary functions of equipment grounding conductors
|
all of the above
|
|
feeders of electrical power systems are generally required to include an equipment grounding conductor
|
true
|
|
branch circuits serving patient care areas of a health care facility are required to provide two (2) independent equipment grounding paths, one in the form of a metallic raceway or cable assembly/armor, and the other in the form of an insulated copper conductor
|
true
|
|
the size of an insulated copper equipment grounding conductor for a 30-ampere branch circuit serving a patient care location shall be not smaller than _ AWG copper
|
10
|
|
where an isolated grounding receptacle in accordance with 406.2(D)(1) and 250.146(D) is installed for a branch circuit serving a patient care location, what is the minimum number of equipment grounding conductor paths required
|
3
|
|
the equipment grounding terminal buses of normal and essential branch panelboards serving the same patient care vicinity shall be bonded together with a continuous insulated copper conductor not smaller than _ AWG
|
10
|
|
which of the following is not acceptable as an equipment grounding conductor according to the NEC
|
flexible metal conduit in lengths longer than 1.8 m (6')
|
|
which of the following is required in order for a 1.2 m (4') length of flexible metal conduit to be used as an equipment grounding conductor
|
all of the above
|
|
under which of the following conditions is metal-clad cable acceptable as a wiring method for branch circuits serving a patient care location
|
the cable is listed with armor that is acceptable as an equipment grounding path and it includes an insulated copper equipment grounding conductor and is installed with listed fittings
|
|
flexible metallic tubing is permitted for branch-circuit wiring in dry locations in lengths not exceeding 1.8 m (6')
|
true
|
|
rigid PVC conduit is permitted for branch circuits serving patient care location
|
false
|
|
what is the minimum size copper equipment grounding conductor (wire-type) for a 600 ampere feeder to a panelboard installed in PVC conduit where the branch circuits of the panelboard serve a patient care location
|
1 AWG
|
|
a jack or terminal that serves as the collection point for redundant grounding of electric appliances serving a patient care vicinity or for grounding other items in order to eliminate electromagnetic interference problems best defines which of the following
|
patient equipment grounding point
|
|
ground-fault circuit-interrupter protection is required for receptacles within 1.8 m (6') of a sink in a critical care location of a hospital
|
false
|
|
in a critical care wet procedure location of a hospital where interruption by ground-fault circuit interrupter cannot be tolerated, receptacles and fixed equipment shall be supplied by an isolated power system
|
true
|
|
equipment ground-fault protection is required for a 1200-ampere service disconnect when served by which of the following voltage and phase configurations
|
480Y/277 volts 3-phase, 4-wire wye-connected
|
|
for ground-fault protection of equipment, the maximum time delay for ground-fault currents of 3000 amperes or more is not to exceed
|
1 second
|
|
where an additional level of ground-fault protection is provided in the level feeder disconnecting means towards the load in accordance with 517.17(B), the ground-fault protection has to be fully selective and a minimum of _ separation between the service and feeder ground -fault protection tripping bands is required
|
6 cycles
|
|
overcurrent devices installed in essential emergency systems of health care facilities are required to be selectively coordinated
|
true
|
|
ground-fault protection for equipment in a hospital or other health care facility is required to be performance tested according to which of the following
|
when it is first installed on site
|
|
additional levels of ground-fault protection in a hospital distribution system shall not be installed in which of the following locations
|
not permitted in any of the above locations
|
|
isolated power systems used in compliance with section 517.20(A) are required to meet which of the following
|
the system is required to be listed
|
|
equivalent insulation and isolation to that required for the electrical distribution systems must be provided for communications, signaling systems, data system circuits, fire alarm systems, and systems less than 120 volts, nominal in patient care areas
|
true
|
|
a ground fault protection system that includes a current transformer around all phase conductors and the neutral conductor simultaneously is which type of ground fault protection system
|
zero sequence type
|
|
metal receptacles plates installed in patient care locations of a health care facility are required to be grounded by which of the following methods
|
by connection to the receptacle with a 6-32 machine screw
|
|
luminaires that are installed at a height greater than 2.3 m (7 1/2') are considered to be located outside the patient care vicinity and thereforecan be connected to one (1) branch-circuit equipment grounding conductor in accordance with 517.13(A)
|
true
|
|
the circuit conductors between the service equipment and the final branch-circuit overcurrent devices are best defined as which of the following
|
feeders
|
|
an additional level of ground-fault protection for equipment is required for hospitals' other buildings, including multiple-occupancy buildings that provide critical care or utilize life support equipment, and where the buildings provide the required essential utilities or services for the operation of critical care areas or life support equipment
|
true
|
|
based on the drawing provided, what is the minimum size insulated copper equipment grounding conductor for this circuit which serves a general care patient bed location
|
12 AWG
|
|
based on the drawing provided, what is the minimum size wire type copper equipment grounding conductor required for the feeder to panelboard
|
1/0 AWG
|
|
based on the drawing provided, what is the minimum size insulated copper equipment grounding conductor required for the branch circuit serving a critical care patient bed location
|
10 AWG
|
|
based on the drawing provided, where is ground fault protection for equipment (GFPE) required
|
location 1 and 2
|