Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
24 Cards in this Set
- Front
- Back
Halon 1301
|
Bromotrifluoromethane
|
|
Halon 1211 is applied only with what?
|
portable extinguishers or large units with a hose line
|
|
What is Halon 1301 superpressurized with?
|
nitrogen
|
|
Halon is stored as what
|
a liquid in gas cylinders
|
|
Halon 1211
|
Bromochlorodifluoromethane
|
|
Halon 1211 characteristics
|
colorless with a sweet smell
|
|
Halon 1211 is pressurized with what
|
nitrogen
|
|
How does halon extinguish fire
|
chemically inhibits the chain
|
|
What class fire is Halon used for
|
bravo fires
|
|
How is Halon 1211 used
|
it is not used in total flooding systems, Its lower volatility plus a high liquid density permits the agent to be sprayed as a liquid. used in 20 pound portable fire extinguishers on lcacs or on flightdecks with mobile firefighting apparatuses
|
|
When does halon decompose
|
upon contact with flames or hot surfaces above 900 F .
|
|
When halon decomposes, what is produced
|
hydrogen fluoride and hydrogen bromide
|
|
what is the discharge time for halon
|
its short, 10 seconds maximum.
|
|
How does steam put out a fire
|
it smothers it, as long as the steam blanket is maintained, it will prevent reignition.
|
|
Where are steam smothering systems installed
|
in boiler casings and catapult troughs.
|
|
what size is the discharge piping on Halon
|
1 1/2 inches
|
|
what size is the tubing assembly on halon
|
1/4in
|
|
what is the bend radius of the tubing assembly on halon
|
1 1/4 inch
|
|
What size is the check valve in halon system and what is it used for
|
1/4 inch and is used to isolate actuation stations, time delays, pressure switches.
|
|
what are the 4 things pressure actuated switches initiating
|
halon actuation alarms, ventilation system shutdowns, vent closure operation, and halon discharge alarms.
|
|
how do you manually over ride the time delay
|
quarter turn of the ball valve in the time delay bypass valve
|
|
On the halon cylinder bottles, how big is the check valve and what is it used for
|
its 1 1/2 in and its used so halon doesn't backflow into empty bottles
|
|
what are the 3 types of magazine sprinkling systems
|
automatic dry type, automatic wet, and manually operated dry.
|
|
what is the difference in wet and dry type sprinkler systems
|
dry type are installed with open sprinklers, and wet type systems have been installed with closed sprinklers
|