• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
  • Read
    Toggle On
    Toggle Off
Reading...
Front

Card Range To Study

through

image

Play button

image

Play button

image

Progress

1/23

Click to flip

Use LEFT and RIGHT arrow keys to navigate between flashcards;

Use UP and DOWN arrow keys to flip the card;

H to show hint;

A reads text to speech;

23 Cards in this Set

  • Front
  • Back
What are not considered Core Alts
Movement of source range monitors, local power range monitors, intermediate range monitors, traversing incore probes, or special moveable detectors, including undervessel replacement. Control rod movement provided there are not fuel assemblies in the associated core.
State several of the mgmt. expectations for fuel handling and refueling.
Error free, all movements in accordance with STS procedures. Qualified, proficient, and guarded from schedule pressure. Universal HALT rule. Notify refuel SRO of abnormal or degraded conditions. FME controls. Obey Rad. Protection requirements. Bridge/Mast movements, no more than two directions at a time. Turnovers controlled by Refuel SRO, and no movements during turnovers and ops. Do not assume, ask questions or verify for self.
Define FME Zone #1
Any activity that could introduce foreign material into systems or components that are not retrievable and could adversely impact safety relate equipment or station power generation.
What is used to track items that are taken in to the FME Zone?
Log
Action if items are dropped in the pool?
Observe closely to identify exact final location of item. Notify supervisor immediately. RP assistance required to retrieve items from pools. Initiate a CR
Max weight load capable of traveling over the fuel assemblies?
1200 pounds.
During cask operations, fuel gates must be kept ______ to prevent water loss from the Spent Fuel Pool in the event of a cask drop accident.
Closed
Air compressor supplies air to the grapple at an operating range of ______ to _______?
70, 110 p.s.i.
Moves telescoping mast. Consists of a cable drum with air/electrical take up reels.
Main Hoist
Handles control rods, blade guides and reactor vessel internals?
Frame mounted Aux. hoist
Design of cask pool?
Load spent fuel/waste for shipment
The FHM's air supply is provided by?
Service air
What is the location of the air isolation valves?
Bridge end electrical panel
Gate seals are normally ______ and switch to nitrogen bottles at ____ p.s.i.
open 32
What raises steam quality and also directs steam to Main Steam Lines?
Steam dryer assembly and steam outlet
This is a barrier to separate upward flow from downward flow in downcomer annulus
Core Shroud
This is a lateral support for fuel, NIs and installed neutron sources and is visible while moving fuel in the core (core alts)
Top Guide
What puts Feedwater outside shroud in downcomer?
Feedwater Spargers
RHR stands for what?
Residual Heat Removal
What directs forced flow into the fuel assemblies?
Core Plate
What provides forced flow through the reactor vessel?
Jet Pumps (20 total)
A loss of RWCU would cause what to happen?
Loss of water clarity
What maintains water quality during operation and refueling?
RWCU, reactor water clean up