Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
187 Cards in this Set
- Front
- Back
tests have indicated that apparatus may override the parking brake system at engine speeds as low as ___
|
1300 rpm
|
|
if it appears that a pump will have to furnish more than 50% of its rated capacity, it should be put in _____ position
|
parallel (volume)
|
|
NFPA standard, recommended practice for fire flow testing and marking of hydrants.
|
NFPA 291
|
|
hydrant flow by colors
class AA light blue |
1500 gpm or greater
|
|
hydrant flow by colors
class A Green |
1000-1499 gpm
|
|
hydrant flow by colors
class B Orange |
500-999 gpm
|
|
hydrant flow by colors
class C Red |
less than 500 gpm
|
|
when using 2.5 or 3" lines to supply pumper off hydrant pressure, lines should be no longer than ____
|
300ft
|
|
if the master intake gauge drops below ___ do not increase the throttle further
|
20 psi
|
|
percentage method equation for additional water available
|
percent drop=
(static-residual) (100) --------------------------------- static |
|
if psi drop is equal to or less than the first digit of static pressure multiplied by 1, ______additional lines may be added
|
three
|
|
if psi drop is equal to or less than the first digit of static pressure multiplied by 2, ______additional lines may be added
|
two
|
|
if psi drop is equal to or less than the first digit of static pressure multiplied by 3, ______additional lines may be added.
|
one
|
|
the max amount of vacuum that most pumps develop is approx. ___"of mercury
|
22"
|
|
the best indication of cavitation
|
lack of reacion on the pressure gauge to changes in the setting of throttle
|
|
maximum theoretical lift
|
33.8 ft
|
|
there should be ___ft of water over and preferrably all around the strainer
|
2ft
|
|
low level strainers can draft water down to a depth of ___
|
2"
|
|
all fire pumps are rated to pump their capacity at ____ft of lift
|
10
|
|
maximum lift considered reasonable for most pumpers is ___'
|
20ft
|
|
at 20 ft of lift, the amount of water that can be supplied is only about ___% of the rated capacity
|
60%
|
|
the transfer valve should be in _____position for priming
|
parallel (volume)
|
|
most priming pumps are intended to work best when the engine is set between ___ and ___ rpm
|
1000-1200
|
|
vacuum is measured from ______to ______
|
the surface of the water to the eye of the impeller
|
|
if a prime has not been achieved in ___ stop priming
|
30 seconds
|
|
priming typically requires ___to___
|
10-15 seconds
|
|
a ____gpm rated pumper should supply the fdc for every ____sprinklers flowing
|
1000gpm
50 |
|
when charging a system, multistage pumps should be set to_____
|
parallel (volume)
|
|
general rule of thumb is to discharge ____into an FDC
|
150 psi
|
|
add ___psi to the desired nozzle pressure for each floor above the standpipe connection
|
5 psi
|
|
elevation difference between static water supply source and pump.
|
lift
|
|
at sea level a pump could theoretically lift water ____
|
33.8 ft
|
|
every ____'of altitude atmospheric pressure drops ____
|
1000'
.5psi |
|
the maximum height to which any amount of water can be raised through hard intake hose to the pump.
|
maximum lift
|
|
in most circumstances, maximum lift is no more than ___
|
25'
|
|
maximum lift calculation
|
L=1.13Hg
|
|
the height a column of water can be lifted in sufficient quantity to provide a reliable flow
|
Dependable lift
|
|
every pump in good repair should have a dependable lift of at least____'
|
14.7 ft
|
|
Pumping apparatus have their fire pumps rated when drafting from a lift of ___ through ____ of hard intake hose.
|
10ft, 20ft
|
|
the pump is only able to deliver __%of its capacity at a __' lift and ___% at a ___'lift
|
70% at 15'
60% at 20' |
|
pressure correction formula
|
lift+total intake hose friction loss divided by 2.3
|
|
net pump discharge pressure at draft equation
|
NPDP draft= PDP+intake pressure correction
|
|
two primary types of static water supply sources firefighters can draft from
|
natural and man made
|
|
Natural static supply water sources include ___,___,____,____,_____
|
lakes, ponds, streams, rivers, and oceans
|
|
when evaluating a static supply source what two factors must be considered.
|
adequacy and accessibility
|
|
adequacy of small stream equation
|
Q=area x velocity(fpm) x 7.5
|
|
rule of thumb when evaluating pond and small lake capacity.
|
every 1 foot of depth for an area of 1 acre provides 1,000gpm fo 5 hours
|
|
a good rule of thumb for drafting with barrel type strainer is ...
|
a depth of 2 feet of water above and below
|
|
low level strainers are most commonly used to draft water from __________ and can draw water from down to ________
|
portable water tanks, 1 to 2 inch
|
|
floating strainers also allow safe drafting from water as shallow as ____
|
1 ft
|
|
underground water storage receptacles usually found in areas not serviced by hydrants
|
cisterns
|
|
cisterns vary in capacity from ____to____
|
10,000-100,000
|
|
________ are commonly found on large residential, industrial, and agricultural properties.
|
private water storage tanks
|
|
private water storage tanks range in size from ______to_______
|
several hundred gallons to many thousands of gallons.
|
|
man made impoundments that have the same characteristics of a pond or small lake
|
ground reservoirs
|
|
ground reservoirs typically contain ________of water
|
many millions of gallons
|
|
square/rectangular pool equation
|
capacity=L x W x D(depth) x 7.5
|
|
round pool equation
|
capacity= pie r squared x depth x 7.5
|
|
agriclutural irrigation systems may flow in excess of _____
|
1,000 gpm
|
|
irrigation water is generally transported by two methods:____ or _____
|
open canals and portable pipes
|
|
during a relay, the engine with the largest pump capacity should be where?
|
at the source
|
|
hose tenders usually cary ____ of LDH
|
a mile or more
|
|
intake pressure relief valves that are adjustable should be set within ___psi of the static pressure of the water sytem supplying the pumper or ___ psi above the discharge pressure of the previous pumper in the relay
|
10, 10
|
|
in the most basic sense, relay operation is based on two things: ________________________
|
amount of water required at the emergency
distance from emergency scene to the water source |
|
all pumpers are rated to pump their maximum volume capacity at a net pump discharge pressure of ____psi at draft
|
150 psi
|
|
hose should not be pumped at pressures that exceed ____% of the annual service test pressure
|
90
|
|
Flowing a predetermined volume of water for the maximum distance that it can be pumped through a particula hose lay.
|
maximum distance relay method
|
|
pumpers are rated to flow ___% of their volume at ___psi and ___% of their volume at ____psi
|
70% at 200psi
50% at 250 psi |
|
relay method that provides the maximum flow available from a particular relay setup by using a constant pressure in the system
|
constant pressure relay method
|
|
driver operators in a constant pressure relay should continue to adjust their PDP to ____psi
|
175
|
|
if the intake pressure drops below ___psi there is a danger of cavitation.
|
20 psi
|
|
the maximum capacity of a relay is determined by what
|
the capacity of the smallest pump and the smallest hoseline within the relay.
|
|
it is desirable to maintain an intake pressure of ___ to ___psi
|
20-30
|
|
if the attack pumper is equipped with an adjustable intake relief valve, set it between ___ an ___
|
50-75 psi
|
|
as long as the intake pressure does not drop below ____ or increase above _____ no action should be required
|
10 psi, 100psi
|
|
relay operations should be shut down from the ______ first
|
fire scene
|
|
pumpers used in a water shuttle operation are most commonly the ______ type
|
standard triple combination pumper
|
|
fill site pumpers should have a minimum pump capacity of ______
|
1000 gpm
|
|
NFPA 1901 requires tenders to be designed to be filled at a rate of at least ______
|
1000 gpm
|
|
specially designed fill site pumpers have capacities to _____ at a max of _____psi
|
1600 gpm, 80 psi
|
|
the majority of water tenders in use today carry from ____to____
|
1500-3000 gallons
|
|
single rear axle apparatus are limited to a max tank capacity of _____
|
1500 gallons
|
|
tenders with water tanks less than ____ and rapid unloading capabilities are the most effective in water shuttles
|
2500 gallons
|
|
some tenders with capacities in exess of _____ are used as dump sites instead of portable tanks
|
2500 gallons
|
|
tenders with ____ pumps are often called _______
|
750 gpm or larger, pumper-tenders
|
|
vacuum tenders are self filling from a static water supplt sourceat a rate up to ____ with lift capability up to _____
|
2000 gpm, 22 feet
|
|
vacuum tenders have discharge rates up to
|
1750 gpm
|
|
water tenders equipped with a pump must have a tank to pump line capable of supplying the pump with ___ until at least ____% of the tank is emptied
|
500gpm, 80%
|
|
water tender external fill connection should allow tank to be filled at a minimum rate of ______gpm
|
1000gpm
|
|
external fill connection should be equipped with a ____,____,&______
|
valve, strainer, and 30 degree elbow
|
|
vsalves that are ___or larger must be the slow closing design
|
3"
|
|
water tenders must have at least one large tank discharge that is capable of emptying ___% of the tank volume at an average rate of _____
|
90%, 1000gpm
|
|
because most water tender tanks are less than ___'tall, the back pressure created by a nearly full tank on a bottom fill inlet is less than ___
|
6', 3psi
|
|
gravity dumps usually employ ___" or larger round or square piping with a valve that extends to the exterior
|
8"
|
|
ISO gives extra credit ratings to jurisdictions that have automatic aid agreements for ________
|
water shuttle operations
|
|
when possible, select a fill site that is capable of supplying at least _____
|
1000 gpm
|
|
when a water supply group is established, the person in charge is known as ______
|
water supply group supervisor
|
|
if the IC initiates an operations section, then the _______reports to the operations section chief
|
water supply supervisor
|
|
when two or more shuttles are needed, a water supply branch may be established. The person in charge of this area is called _______
|
water supply branch director
|
|
in line water wiphons should be operated at _____ and provide ___to____ through a ___" pipe
|
150 psi, 700-800gpm, 4"
|
|
when a water tender pumps its tank directly into the attack pumper
|
direct pumping operations
|
|
a single portable tank works on fires requiring a flow rate of _____
|
less than 300 gpm
|
|
it is recommended that portable tanks be at least _____ larger than the tank on the apparatus carrying it.
|
500 gallons
|
|
jet siphons have an inlet for connection of ____ or larger hose
|
1 1/2"
|
|
flow rating for tender calculation
|
GPM= tank size-10%GPM divided by trip time
|
|
travel time formula
|
travel time in minutes=.65 + (1.7) (distance in miles)
|
|
handling time formula
|
handling time=fill site time +dump site time
|
|
tender flow rate calculation
|
water tank size in gallons -10% divided by travel time+ handling time
|
|
to recieve iso full credit, the first water tender must begin dumping wate within ___ of the first pumpers arrival and continue to be supplied with a minimum of ____ for _______
|
5 minutes
250 gpm 2 hours |
|
mechanical foams must be ___ and ____ before they can be used
|
proportioned, aerated
|
|
foam proportioner
|
device that introduces foam concentrate into the water stream
|
|
hydrocarbon fuels such as ___________________________________ are petroleum based and float on water
|
crude oil, fuel oil, gasoline, benzene, naphtha, jet fuel, kerosene
|
|
polar solvent fuels such as ___________________________________ are flammable liquids and mix with water
|
alcohol, acetone, lacquer thinners, ketones, and esters
|
|
class b foam is effective on _____ fuels because it will float on the surface
|
hydrocarbon
|
|
what 3 ways does foam work?
|
seperates, cools, suppresses
|
|
most firefighting foam concentrates are intended to be mixed with ______ water
|
94 to 99.9%
|
|
the _____method of proportioning foam uses the pressure energy in the stream of water ti induct foam concentrate into the fire stream
|
induction
|
|
the ___ method of proportioning foam uses an external pump or head pressure to force foam into the stream
|
injection
|
|
foam storage\
___gallon pails |
5
|
|
foam storage ___gallon barrels
|
55
|
|
foam storage
____gallon totes |
275
|
|
foam concentrate tanks on municipal pumpers range from __to ___
|
20-200 gallons
|
|
foam pumpers and tenders may carry ___ gallons of foam concentrate ot more
|
8000 gallons
|
|
class A foam has been used since the ____
|
1940's
|
|
shelf life of class A foam can be as much as ___
|
20 years
|
|
fire attack and overhaul with standard fog nozzle--- ___% to ___% concentrate
|
.2-.5%
|
|
exposure protection with standard fog nozzle---___to___% concentrate
|
.5-1%
|
|
any application with air aspirating foam nozzle---___to___ concentrate
|
.3-.7%
|
|
any application with CAFS system---____to____concentrate
|
.2-.5%
|
|
the application rate of class A foam is the same as the ____________ of water
|
minimum critical flow rate
|
|
protein based foams have a normal shelf life of about ____
|
10 years
|
|
synthetic based foams will have a shelf life of generally _________
|
20-25 years
|
|
class B foams are mixed in prportions of ___to___
|
1 to 6%
|
|
class B foam is usually __to__ on hydrocarbons and ___to___ on polar solvents
|
1-3%
3-6% |
|
MEDIUM EXPANSION FOAMS ARE TYPICALLY USED AT __,___ OR___ concentrations
|
1 1/2, 2, 3%
|
|
NFPA standard for low, medium, and high expansion foam.
|
NFPA 11
|
|
low expansion foam has an air/solution ratio up to ____
|
20:1
|
|
medium expansion foam has an air/solution ratio of ___to___ through hydraulically operated nozzle style delivery devices
|
20:1- 200:1
|
|
high expansion foam air/solution ratio is ___to___
|
200:1 to 1000:1
|
|
alcohol resistant fluoroprotein foam maintains its alcohol resistive properties for about ___
|
15 minutes
|
|
_______ is the most commonly used foam today
|
AFFF
|
|
on most polar solvents AFFF's are used at ___to____
|
3-6%
|
|
the pressure at the outlet of the eductor must not exceed ___to___% of the eductor inlet pressure
|
65-70%
|
|
foam solution concentrate is only correct at the rated inlet pressure of the inductor, usually ___to____
|
150-200 psi
|
|
the foam concentrate inlet to the eductor should not be more than___' above the surface of the foam concentrate
|
6'
|
|
self educting master stream nozzles are used when floes in excess of ___ are required
|
350 gpm
|
|
self educting master stream nozzles are available with flows up to _____gpm
|
14,000 gpm
|
|
the jet ratio controller allows the foam concentrate to be up to ____' away from the self educting master stream nozzle.
|
3000'
|
|
The JRC allows an elevation change up to ___'
|
50'
|
|
the JRC proportions the concentrate to ___%
|
66 1/2%
|
|
installed in line eductors are most commonly used to proportion class __ foams
|
B
|
|
variable flow rate direct injection systems provide foam concentrates from ___to___
|
0.1-3%
|
|
smoothbore nozzle foam application is limited to _______
|
class A CAFS
|
|
expansion ratios using fog nozzles are between ___and___
|
2:1 and 4:1
|
|
the only type of nozzle that can be used with protein and fluoroprotein foams
|
air aspirating foam nozzle
|
|
NFPA standard on foam chemicals for fire in class A fuels
|
NFPA 1150
|
|
when used for firefighting durable agents are normally applied at a ratio of _____
|
1:100
|
|
when used for line construction durable agents are normally applied at ___to____
|
1 1/2 to 2%
|
|
when used for structure protection, durable agents are normally applied at ___to___
|
2 to 3 %
|
|
NFPA _____ requires that driver operators be able to perform functional tests on foams systems
|
NFPA 1002
|
|
NFPA ____, _____, &_____ are used as a basis for most bid specs.
|
NFPA 1901, 1906, and 414
|
|
apparatus must accelerate to _____from a standing start within ____
|
35mph, 25 seconds
|
|
apparatus must achieve a minimum top speed of ___
|
50 mph
|
|
apparatus must come to a full stop from ___mph within ____feet
|
20 mph
35 ft |
|
pumps are tested hydrostatically at ___ for ___
|
250 psi, 3 minutes
|
|
apparatus with less than 750 gpm are required to undergo the same tests with the exception of the __________
|
pumping engine overload test
|
|
NFPA standard for service tests of fire pump systems on fire apparatus
|
NFPA 1911
|
|
when using a static water supply source the water must be at least __ft deep and the strainer must be submerged at least __ft below the water. the surface of the water may be no more than __ft below the centerline of the pump intake, and ___ft of hard intake hose should be used for testing
|
4ft
2ft 10ft 20ft |
|
air temp during testing should be between ___ and ___
|
0-100 degrees F
|
|
water being used for testing should be between ___and___
|
35 and 90 degree F
|
|
barometric pressure should be at least ______ corrected at sea level
|
29"Hg
|
|
__"drop in barometric pressure reduces a pumpers maximum possible static lift by about ___'
|
1"
1' |
|
lifting ability drops by about ___ per ___ft of elevation increase
|
1foot
1,000 ft |
|
gasoline engines have ___less efficiency per ____
|
3.5%
1000ft increase in altitude |
|
pump service tests are conducted at ___,___,___,&____ net pump discharge pressure
|
150, 165, 200, & 250 psi
|
|
pressure correction formula
|
lift + intake hose friction loss divided by 2.3
|
|
NFPA 1911 requires that all gauges have been calibrated withing __days of testing
|
60
|
|
pump intake pressure gauge should have a range of ___to___vacuum and ___to___ for compound
|
30 in Hg to 0
30in Hg to 150 psi |
|
pump discharge gauge should have a range from ___to___ psi
|
0-400 psi
|
|
pitot tube should have a range of ___to___
|
0-160 psi
|
|
vacuum test
no more than ___ of vacuum should be lost in ___ minutes |
10 in
5 minutes |
|
pumping test
___psi for __minutes ___psi for ___minutes delivering 70% capacity. ___psi for ___ minutes delivering 50% capacity |
150 psi for 20 minutes
200 psi for 10 minutes 250 psi for 10 minutes |
|
pressure control test
pump discharge pressure should rise no more than ___ when all gauges are closed |
30 psi
|
|
any gauges that are off by more than ___ should be recalibrated, repaired, or replaced
|
10 psi
|
|
the flow measured from the nozzle and the flowmeter should not be more than ___% off
|
10
|
|
the fire pump must test to at least ___% of its original capabilities to remain in service with the same ratings
|
90%
|
|
foam solution refractivity test is used for ____and ____foams
|
protein and fluoroprotein
|