• Shuffle
    Toggle On
    Toggle Off
  • Alphabetize
    Toggle On
    Toggle Off
  • Front First
    Toggle On
    Toggle Off
  • Both Sides
    Toggle On
    Toggle Off
  • Read
    Toggle On
    Toggle Off
Reading...
Front

Card Range To Study

through

image

Play button

image

Play button

image

Progress

1/119

Click to flip

Use LEFT and RIGHT arrow keys to navigate between flashcards;

Use UP and DOWN arrow keys to flip the card;

H to show hint;

A reads text to speech;

119 Cards in this Set

  • Front
  • Back
conductance and resistance related by formula...
R= 1/C
U-value of multiple components...
U= 1/ sum of R
total heat loss formula...
q= UA delta t
design equivalent temperature differnece
DETD, takes into account air temp diff., effects of the sun, thermal mass storage, colors of finishes and daily temp range
design cooling load factor
DCLF, takes into account types of glazing, type of interior shading and outdoor design temp
sensible heat gain
225 btu/hr
heat gain from lighting
multiply total wattage load of lights by 3.41
for fluorescent lights, multiply the btu/hr by 1.25
latent heat gain in residential occupancy equals...
30% of the sensible heat gain
heat loss through infiltrations =
qv= V(1.08) delta T
ton of refridgeration =
1 ton of 32 deg F ice melts to water at 32 deg in 24 hrs
12,000bru/hr

rule of thumb, divide the total heat gain in btu/hr by 12,000
two primary means of xporting heat
air and water
direct expansion system
DX, self contained unit, (window unit)
single duct system
typical residential, one zone, one thermostat
variable air volume system
VAV,
single duct
theremostat and control at each room
dual duct system
high velocity system
2 parallel ducts carrying hot and cold,
thermostat and mixing at each room
reaheat system
constant volume
fresh outdoor air distributed at constant volume and reheat at each room
multizone system
central mixing delivered to independently controled zones
all water system
fan coil in each conditioned space connected to one or two water circuits
air water systems
used where return air cannot be recirculated such as hospitals or laboratories
mechanical room req
3-9% of the gross building area

all water req. 1-3%
air ducts
round are most efficient and produce least amount of pressure loss
rect ducts make better us aof available space
main trunk duct
follow the path of circulation systems
static head
pressure req to overcome this firction loss in air duct
sizing of low pressure ducts
3 ft3 to 6 ft3 for every 1000 sf of floor space served
amount of energy used by HVAC systems
40% 60% of the overall energy consumption
recuperative gas boiler
recovers sensible and latent heat from exhaust flue gases
up to 95% efficient
displacement ventilation
supply air originates at floor level and rised to return grilles in the ceiling
personal control
require access flooring
water loop heat pumps
series of heat pumps for different zones
only need to cool or heat water when most pumps are in the same mode
thermal energy storage
allows the use of less expensive off peak hours to cool
store in water, rocks or other thermal mass
energy recovery ventilators
air to air headt xchanger
reclaim waste enerfy from the exhause air stream and use it to condition the incoming fresh air
most efficient for bldgs occupied 8 hrs per day
energy xfer wheel
small openings thru which the air passes. wheels impregnated w/ lithiom chloride or other substance to xfer heat
water to water heat xchange
runaround coil
extract air window
double paned glass w/ another pane over top
ground coup0le heat xchange
pipes buried in the ground
long runs of pipes for operation
BAS
building automation system
TAB
testing, adjusting and balancing
traditional commissioning
solar orientation
rectangular building is best oriented slightly east of south approx. 15 deg
bldg w/ less surface area...
generally use less energy
minimizing works best in cold climates
long thing bldgs...
improve daylighting and ventilation
external load dominated
few occupants
internal load dominated
many occupants, lighting and equipment
extensive green roof
less than 6in soil depth
minimal landscaping
intensive green roof
thicker soil and complex landscapes
electrochromic glazing
changes cont. from dark to clear as low voltage elect current is applied
photochromic glasing
darkens under sunlight
like changing sunglasses
thermochromic glazing
darkens in response to temp
dynamic buffer zone
outer layer of glazing built around an existing building
controls humidity and condensation issues with new construction
electric lighting and coolign account for.....energy use
30 to 40% and as much as 50%
daylight factor
DF
raio of the indoor illuminance at a point on a horizonatal surface to the unobstructed exterior horiz. illum
recommended daylight factors
1.5% dfor ordinary visual tasks
4% for dificult tasks
spectral selective glazing
gives high VLT and good SHGC
VLT
visible light xmittance
amt of light thru glazing
SHGC
solar heat gain coefficient
amt of heat thru glazing
VLT for good glare control
50-70%
minimum surface reflectances
80% for ceiling
50-70% for walls
20-40% for floors
LEED credit for glazing factor
2-75% for all space being occupied
LEED credit for renewable energy
one each at 5%, 10% and 20%
ground source heat pump
GSHP
extract heat from ground in winter or give off excess heat in summer
save from 20-50% on enerfy consumption and 50% on water heating
GSHP pipe needs
400ft of pipe for every 12,000 btu/hr
photovoltaic array angle
azimuth: 15 degrees east of south

altitude: latitude of the building plus or minus 15 degrees
ph
measure of the relative acidity or alkalinity of water
scale of 0-14
<7 is acidic
>7 is alkaline
acidic water
w/ oxygen can cause iron and stl to rust
rainwater is slightly...
acidic, but combies w/ sulfur and nitrogen to fall as "acid rain"
water hardness
caused by calcium and magnesium salts
treated through an ion exchange process
turbidity
suspended material in the water
water color and odor problems caused by...
organic matter, inorganic salts or dissolved gases
two of most important considerations for a well...
depth and yeild
well depth
range from 25 ft (shallow well) to several hundred
well yeild
gallons per minute
5 gpm to 10 gpm is minimum req.
water pumps
suction, deep well jet, turbine and submersible
well components
pump, storage tank or pressure tank
pressure tank
used to maintain a constant pressure for building use
municipal water pressure
approx. 50 psi
primary water supply types
upfeed and downfeed
static head
pressure req to push water vertically
0.433 psi to lift water 1 ft
upfeed system
uses pressure in the water main directly to supply the fixtures
downfeed system
water from the main is pumped to storage tanks near the top of the building or at the top of the zone served and flows by gravity to the fixtures
direct upfeed pumping system
tankless system
several pumps are used together controlled by a pressure sensor
pipe types
copper, steel, plastic or brass
copper most common
where water not corrosive steel or galvanized pipe can be used, but more difficult to assemple
copper pipe
K, L, M
straight lengths (hard temper)
coils (soft temper)
seal by soldering
plastic pipe
PE
ABS-
PVC
PVDC
sealed by melting (sweating) together
golbe valve
water flow is variable, such as faucets and hose bibs
compresses a washer against a seat
gate valve
seats a metal wedge against two metal parts
check valve
backflow valve
prevents flow from returning backward to contaminate
sum of all fixture values...
must be equal or less than the water main pressure
smaller the diameter pipe...
the greater the friction
greater the flow rate in a pipe...
the greater the friction
fixture units
used to determine water demand
equal to 1 cu ft/ min.
flow does not increase in direct proportion to...
an increase in load
expansion of piping
must be accounted for in building design
peak hourly demand
0.4 gal per person for an office bldg
12 gal per unit for a small apt building
recovery rate
number of gallons per hour of cold water that the heater can raise to the desired temp
size hot water piping
number of fixtures requiring hot water is multiplied by 0.75
water heater temperature
set to the highest temp that is req at the point of use
110 deg for shower
180 deg for commercial laundry
direct heating
brings water directly into contact w/ heated surfaces
indirect heating
intermediary xfer medium to heat the water
water heater components
storage tank, tankless, circulating
electric instantaneous heater
remote areas impractical for cont. piping. pricey
solar water heater components
solar collectyor, storage tank, assoc. piping to move fluids and backup heater
solar direct system
open loop
water used in the building is the same water that is heated in the solar collectors
may freeze
solar indirect system
closed loop
separate fluid for heat collection, heat xfer to water
batch system
heats water directly in a block painted tank inside a glazed box
can freeze and lose heat at night
thermosiphon system
relies on natural movement of heated water to circ.
closed loop active system
seperate non freezing fluid pumped through collector and xfer heat to water
lose effieciency in xfer
drain down system
drain out water from system during freeze periods
drain back system
closed loop that drains fluid back to storage tank when sensor finds temp too low
phase change system
closed loop w/ phase change material as collector fluid. takes in latent heat as well
sanitary drainage
drainage including human waste
blackwater
sewage incl human waste
graywater
sewage not incl human waste
trap
locate at every fixture
seal that prevents sewage system
branch circuit
last line on elect diagram
duct lining
effective at removing low freq noise from HVAC system
ADA urinal flush height
44"
high coefficient of thermal expansion
plastic is higher than steel
highest large building operating cost
constant volume reheat
coefficient of utilization
reach the work plane
noise generated in a room can be most easily controlled by...
absorbtion
vaccum breaker
allows air into system to avoid suction of gases through trap
not req. for plumbing drainage system (most important for human waste lines)