Use LEFT and RIGHT arrow keys to navigate between flashcards;
Use UP and DOWN arrow keys to flip the card;
H to show hint;
A reads text to speech;
119 Cards in this Set
- Front
- Back
conductance and resistance related by formula...
|
R= 1/C
|
|
U-value of multiple components...
|
U= 1/ sum of R
|
|
total heat loss formula...
|
q= UA delta t
|
|
design equivalent temperature differnece
|
DETD, takes into account air temp diff., effects of the sun, thermal mass storage, colors of finishes and daily temp range
|
|
design cooling load factor
|
DCLF, takes into account types of glazing, type of interior shading and outdoor design temp
|
|
sensible heat gain
|
225 btu/hr
|
|
heat gain from lighting
|
multiply total wattage load of lights by 3.41
for fluorescent lights, multiply the btu/hr by 1.25 |
|
latent heat gain in residential occupancy equals...
|
30% of the sensible heat gain
|
|
heat loss through infiltrations =
|
qv= V(1.08) delta T
|
|
ton of refridgeration =
|
1 ton of 32 deg F ice melts to water at 32 deg in 24 hrs
12,000bru/hr rule of thumb, divide the total heat gain in btu/hr by 12,000 |
|
two primary means of xporting heat
|
air and water
|
|
direct expansion system
|
DX, self contained unit, (window unit)
|
|
single duct system
|
typical residential, one zone, one thermostat
|
|
variable air volume system
|
VAV,
single duct theremostat and control at each room |
|
dual duct system
|
high velocity system
2 parallel ducts carrying hot and cold, thermostat and mixing at each room |
|
reaheat system
|
constant volume
fresh outdoor air distributed at constant volume and reheat at each room |
|
multizone system
|
central mixing delivered to independently controled zones
|
|
all water system
|
fan coil in each conditioned space connected to one or two water circuits
|
|
air water systems
|
used where return air cannot be recirculated such as hospitals or laboratories
|
|
mechanical room req
|
3-9% of the gross building area
all water req. 1-3% |
|
air ducts
|
round are most efficient and produce least amount of pressure loss
rect ducts make better us aof available space |
|
main trunk duct
|
follow the path of circulation systems
|
|
static head
|
pressure req to overcome this firction loss in air duct
|
|
sizing of low pressure ducts
|
3 ft3 to 6 ft3 for every 1000 sf of floor space served
|
|
amount of energy used by HVAC systems
|
40% 60% of the overall energy consumption
|
|
recuperative gas boiler
|
recovers sensible and latent heat from exhaust flue gases
up to 95% efficient |
|
displacement ventilation
|
supply air originates at floor level and rised to return grilles in the ceiling
personal control require access flooring |
|
water loop heat pumps
|
series of heat pumps for different zones
only need to cool or heat water when most pumps are in the same mode |
|
thermal energy storage
|
allows the use of less expensive off peak hours to cool
store in water, rocks or other thermal mass |
|
energy recovery ventilators
|
air to air headt xchanger
reclaim waste enerfy from the exhause air stream and use it to condition the incoming fresh air most efficient for bldgs occupied 8 hrs per day |
|
energy xfer wheel
|
small openings thru which the air passes. wheels impregnated w/ lithiom chloride or other substance to xfer heat
|
|
water to water heat xchange
|
runaround coil
|
|
extract air window
|
double paned glass w/ another pane over top
|
|
ground coup0le heat xchange
|
pipes buried in the ground
long runs of pipes for operation |
|
BAS
|
building automation system
|
|
TAB
|
testing, adjusting and balancing
traditional commissioning |
|
solar orientation
|
rectangular building is best oriented slightly east of south approx. 15 deg
|
|
bldg w/ less surface area...
|
generally use less energy
minimizing works best in cold climates |
|
long thing bldgs...
|
improve daylighting and ventilation
|
|
external load dominated
|
few occupants
|
|
internal load dominated
|
many occupants, lighting and equipment
|
|
extensive green roof
|
less than 6in soil depth
minimal landscaping |
|
intensive green roof
|
thicker soil and complex landscapes
|
|
electrochromic glazing
|
changes cont. from dark to clear as low voltage elect current is applied
|
|
photochromic glasing
|
darkens under sunlight
like changing sunglasses |
|
thermochromic glazing
|
darkens in response to temp
|
|
dynamic buffer zone
|
outer layer of glazing built around an existing building
controls humidity and condensation issues with new construction |
|
electric lighting and coolign account for.....energy use
|
30 to 40% and as much as 50%
|
|
daylight factor
|
DF
raio of the indoor illuminance at a point on a horizonatal surface to the unobstructed exterior horiz. illum |
|
recommended daylight factors
|
1.5% dfor ordinary visual tasks
4% for dificult tasks |
|
spectral selective glazing
|
gives high VLT and good SHGC
|
|
VLT
|
visible light xmittance
amt of light thru glazing |
|
SHGC
|
solar heat gain coefficient
amt of heat thru glazing |
|
VLT for good glare control
|
50-70%
|
|
minimum surface reflectances
|
80% for ceiling
50-70% for walls 20-40% for floors |
|
LEED credit for glazing factor
|
2-75% for all space being occupied
|
|
LEED credit for renewable energy
|
one each at 5%, 10% and 20%
|
|
ground source heat pump
|
GSHP
extract heat from ground in winter or give off excess heat in summer save from 20-50% on enerfy consumption and 50% on water heating |
|
GSHP pipe needs
|
400ft of pipe for every 12,000 btu/hr
|
|
photovoltaic array angle
|
azimuth: 15 degrees east of south
altitude: latitude of the building plus or minus 15 degrees |
|
ph
|
measure of the relative acidity or alkalinity of water
scale of 0-14 <7 is acidic >7 is alkaline |
|
acidic water
|
w/ oxygen can cause iron and stl to rust
|
|
rainwater is slightly...
|
acidic, but combies w/ sulfur and nitrogen to fall as "acid rain"
|
|
water hardness
|
caused by calcium and magnesium salts
treated through an ion exchange process |
|
turbidity
|
suspended material in the water
|
|
water color and odor problems caused by...
|
organic matter, inorganic salts or dissolved gases
|
|
two of most important considerations for a well...
|
depth and yeild
|
|
well depth
|
range from 25 ft (shallow well) to several hundred
|
|
well yeild
|
gallons per minute
5 gpm to 10 gpm is minimum req. |
|
water pumps
|
suction, deep well jet, turbine and submersible
|
|
well components
|
pump, storage tank or pressure tank
|
|
pressure tank
|
used to maintain a constant pressure for building use
|
|
municipal water pressure
|
approx. 50 psi
|
|
primary water supply types
|
upfeed and downfeed
|
|
static head
|
pressure req to push water vertically
0.433 psi to lift water 1 ft |
|
upfeed system
|
uses pressure in the water main directly to supply the fixtures
|
|
downfeed system
|
water from the main is pumped to storage tanks near the top of the building or at the top of the zone served and flows by gravity to the fixtures
|
|
direct upfeed pumping system
|
tankless system
several pumps are used together controlled by a pressure sensor |
|
pipe types
|
copper, steel, plastic or brass
copper most common where water not corrosive steel or galvanized pipe can be used, but more difficult to assemple |
|
copper pipe
|
K, L, M
straight lengths (hard temper) coils (soft temper) seal by soldering |
|
plastic pipe
|
PE
ABS- PVC PVDC sealed by melting (sweating) together |
|
golbe valve
|
water flow is variable, such as faucets and hose bibs
compresses a washer against a seat |
|
gate valve
|
seats a metal wedge against two metal parts
|
|
check valve
|
backflow valve
prevents flow from returning backward to contaminate |
|
sum of all fixture values...
|
must be equal or less than the water main pressure
|
|
smaller the diameter pipe...
|
the greater the friction
|
|
greater the flow rate in a pipe...
|
the greater the friction
|
|
fixture units
|
used to determine water demand
equal to 1 cu ft/ min. |
|
flow does not increase in direct proportion to...
|
an increase in load
|
|
expansion of piping
|
must be accounted for in building design
|
|
peak hourly demand
|
0.4 gal per person for an office bldg
12 gal per unit for a small apt building |
|
recovery rate
|
number of gallons per hour of cold water that the heater can raise to the desired temp
|
|
size hot water piping
|
number of fixtures requiring hot water is multiplied by 0.75
|
|
water heater temperature
|
set to the highest temp that is req at the point of use
110 deg for shower 180 deg for commercial laundry |
|
direct heating
|
brings water directly into contact w/ heated surfaces
|
|
indirect heating
|
intermediary xfer medium to heat the water
|
|
water heater components
|
storage tank, tankless, circulating
|
|
electric instantaneous heater
|
remote areas impractical for cont. piping. pricey
|
|
solar water heater components
|
solar collectyor, storage tank, assoc. piping to move fluids and backup heater
|
|
solar direct system
|
open loop
water used in the building is the same water that is heated in the solar collectors may freeze |
|
solar indirect system
|
closed loop
separate fluid for heat collection, heat xfer to water |
|
batch system
|
heats water directly in a block painted tank inside a glazed box
can freeze and lose heat at night |
|
thermosiphon system
|
relies on natural movement of heated water to circ.
|
|
closed loop active system
|
seperate non freezing fluid pumped through collector and xfer heat to water
lose effieciency in xfer |
|
drain down system
|
drain out water from system during freeze periods
|
|
drain back system
|
closed loop that drains fluid back to storage tank when sensor finds temp too low
|
|
phase change system
|
closed loop w/ phase change material as collector fluid. takes in latent heat as well
|
|
sanitary drainage
|
drainage including human waste
|
|
blackwater
|
sewage incl human waste
|
|
graywater
|
sewage not incl human waste
|
|
trap
|
locate at every fixture
seal that prevents sewage system |
|
branch circuit
|
last line on elect diagram
|
|
duct lining
|
effective at removing low freq noise from HVAC system
|
|
ADA urinal flush height
|
44"
|
|
high coefficient of thermal expansion
|
plastic is higher than steel
|
|
highest large building operating cost
|
constant volume reheat
|
|
coefficient of utilization
|
reach the work plane
|
|
noise generated in a room can be most easily controlled by...
|
absorbtion
|
|
vaccum breaker
|
allows air into system to avoid suction of gases through trap
not req. for plumbing drainage system (most important for human waste lines) |