Fire Extinguishers
At least one 2A:10BC for every 3000 sq ft. with a maximum 75' travel distance between.
Class K Extinguishers
Shall be provided within 30' of commercial-type food heat-processing equipment.
• Extinguishing systems for commercial cooking equipment shall be serviced & tagged at least every 6 months.
Sprinkler Systems
• Where a sprinkler system or automatic extinguishing system is in place, such system shall be serviced & tagged annually.
Standpipe Systems
Shall be flow-tested & tagged every 5 years.
Egress Doors
Such doors shall swing in the direction of exit travel when servicing any hazardous area, or when occupancy exceeds 50 people.
Means of Egress
• Illumination of Means of Egress is provided in Sect. 14.12.
• Exit Access: Shall include only designated stairs, aisles, corridors, ramps, escalators & passageways leading to an exit.
• Exit Discharge: Includes only designated stairs, aisles, corridors, ramps, escalators, walkways & exit passages leading to a public way.
• Means of egress shall be illuminated when building/structure is occupied.