street boxes are indicative of a _ system
public fire reporting
failures of a power supply or a wiring fault are indicated by a _ signal
trouble
codes and standards usually contain _ requirements
minimum
opens and grounds result in a _ signal
trouble
where an engine driven generator is used to provide secondary power, a minimum of _ hours of batteries are required
4
which of the following devices will detect light energy
radiant energy detector
wall mounted spot-type smoke detector are installed so that the top of the detector is _
4-12 inches from the ceiling
manual fire alarm boxes must be mounted no higher than _ inches for front reach applications
48
which of the following is an audible textual appliance
speaker
fire alarm cables are permitted to be strapped to other conduits
false
according to NFPA 72, how many water-flow alarm-initiating devices may be connected to an initiating device circuit
5
which of the following is least likely to require an emergency voice/alarm communications system
mercantile
emergency voice/alarm communications systems use
speakers
which of the following is most likely to be found in fire alarm specifications
type of equipment used
which of the following are usually found on shop drawings
all of the above
Acoustic sensors detect glass-break frequencies, they cannot detect _ glass
plexi
shock sensors will detect _, but will reduce sensor range up to 50%
plexi-glass
_ glass shatters into thousands of tiny pieces
tempered
the range of an AP 750 motion sensor is _ feet
50
the type of lens pattern needed on a PIR to protect areas under skylights or near roof entries is a _ lens
curtains
the best location when installing a silent panic switch in a walk-in freezer is a point between the floor and _ inches below the door knob
4
to protect doors and windows where drilling holes is desirable, such as thin-frame windows or on sliding glass doors, a Sentrol _ series switch is used
1035
a Kiss Off Tone is generated from _
central station receiver
the _ monitors the environment and trips when the radiant heat energy of an intruder is detected
PIR
the maximum number of conductors permitted in following box is _
(#6 AWG TW 4-inch x 1 1/2 inch square)
4
no conductors larger than _ AWG is recognized by the NEC to be installed in any standard box listed in table 314.16(A)
6
the minimum length (A) for the pull box shown in figure 4-5 is _ inches and the conductors will not be spliced
2" 2"
4" 4"
32
the maximum number of #16 AWG TFF fixture wires permitted in a 1 inch electrical nonmetallic tubing, Type ENT is _
29
the maximum number of #6 AWG THW copper conductors permitted in a 1-inch EMT is
4
the maximum number of #12 AWG THHN copper conductors that are permitted to be pulled directly through (without splice) in a 3/4 inch LB condulet installed in a run of 3/4 inch RMC is _
16
a continuous load is a load where the maximum current is expected to continue for _ hours or more
three
the lighting load for a one-story dwelling unit is 1700 square feet in size is _ VA
5,100
the lighting load for a two-story dwelling unit with outside dimensions measuring 60 feet x 125 feet is _ VA
45,000
a fixed appliance in a dwelling unit has a nameplate marking of 50 amps. the rating of the individual branch circuit required to supply this non-continuous appliance load is _ amperes
50
the minimum branch circuit rating for a range rated 8 3/4 kw shall not be less than _ amperes
40
the neutral feeder demand for household electric ranges is permitted to be _ percent of the feeder demand for the ungrounded conductors
70
a 24-unit apartment complex has a 10 kw range in each apartment and is supplied by 120/240 volt single-phase, the range feeder demand for this complex is _ VA
39,000
a four-plex multi-family dwelling has a 5 kw, 240 volt dryer installed in each unit. the feeder demand in VA for the dryers is _ VA
20,000
an appliance store has 32 feet of multi-outlet assembly. the load rating when all the outlet are to be used at the same time is _ VA
5,760
Article 517 in the NEC is made up of _ parts
7
which of the following determines what area of a health care facility provides normal or general patient care and what area provides critical patient care
the governing body of the health care facility
the conductors between the over-current devices protecting the circuit and the device best defines a _
branch circuit
feeder of electrical power systems are generally required to include an equipment grounding conductor
true
the size of an insulated copper equipment grounding conductor for a 30-ampere branch circuit serving a patient care location shall be not smaller than _ AWG copper
10
Rigid PVC conduit is permitted for branch circuits serving patient care locations
false