When _ a hoist to a structure, make sure the structure is strong enough.

Attaching

When a 3 phase, 4w supply delivers 120/240 volts, the system has B-phase-to-neutral voltages that are ___ volts.

208v

What formula is required to find the line current of a single phase system?

Line current = P (single phase) / line voltage.

What formula is required to find the line current of a 3 phase system?

Line current = 3phase power / (line voltage x 1.732)

Another name for "rated power output"?

Capacity

The rated power output can be delivered by a generator is given on the nameplate in ___ or ___.

Watts or KW

Another formula to find line current of a 3phase system is ____?

Line current = (3phase power / line voltage) / 1.732.

An examples of a "straight voltage rating" are ___ and ___?

2400v 3phase 3-w...... Or...... 480v 3phase 4-w

Straight voltage rated systems are typically Wye or Delta setup?

Delta

A voltage system that has 2 voltage outputs are referred to as___?

Slash voltage rating.

An example of a Slash voltage rated system is?

120/280v 3ph 4-w

120/240v system is Wye or Delta configuration? Why?

Delta, because 240 / 2 = 120

120/208v system is Wye or Delta configuration? Why?

Wye configuration. Because 120 x 1.732 = 208.

What is the other common type of transformer configuration? And Which is typically the Primary, and which is the secondary?

Delta (primary) - Wye (secondary).

In a 480/277v 3ph 4w panel, what is the current in circuit 1, with a 2.1 KVA load?

2100va / 277v = 7.58a

In a 480/277v 3ph 4w panel, what is the current in circuit 2 (on a 2 pole breaker), with a 7.9 KVA load?

7900va / 480v = 16.46 amps

In a 480/277v 3ph 4w panel, what is the current in circuit 6 (on a 3 pole breaker), with a 41.3KW load?

(41300va / 480v) / 1.732 = 49.6 amps

In a 3ph 4w system, which phase is circuit 1 typically on? Which phase is circuit 2 typically on?

A. Also A

In a 3ph 4w system, which phase is circuit 5 typically on? Which phase is circuit 3 typically on?

C phase. B phase.

Match up the windings

Is this a delta or Wye configuration?

Delta